Turbine Emergency Procedure
Turbine Emergency Procedure
Normal/Emergency supply
After grid failure, DCEOP, DC SEAL OIL PUMP should
come in auto start. if not come on auto, this DC
pumps should be started manually by the desk
engineer.
Ensure seal steam of above 300mmwc & temperature
above 280 Deg C. If not maintained, immediately kill
the vacuum. Isolate seal steam at 0.8 ksc abs to avoid
cold air ingress via turbine seals.
One JOP should come at 510rpm
Barring gear valve should open at 210rpm
Rise the Lube oil header temp to 50 Deg C
If turbine speed reduces below 60 rpm, start one
more AOP.
If speed is further dropping below 40rpm, Stop
JOP, wait for JO Pressure reduced to Zero and
restart JOP.
Check the healthiness of DC EOP& DC SOP in
every shift/every day and check the pressure
developed at local.
During start up, ensure no water is available in
CRH/MS line to avoid hanger failure due to
hammering
When both GTs got tripped and no standby
transformer in service