Chiller Ahu and Fcu Systems
Chiller Ahu and Fcu Systems
Chiller Ahu and Fcu Systems
WEEKS 9-10
2018-2019/1T
Prepared by:
Engr. Manuel B. Rustria
September 2019
Objectives
Explain the basic design concepts for chiller, AHU and FCU
systems; and
Calculate chiller, AHU, and FCU capacity and select standard
equipment size from available catalogs.
Fundamental HVAC
Concepts
Fundamental HVAC Concepts
Five subsystems or loops of HVAC
Air-side
Chilled water
Refrigeration equipment
Heat rejection
Controls
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Fundamental HVAC Concepts
Air Handling Units
Air Handling Units
Air Handling Units
TERMINAL UNIT OR DEVICE
fan coil units
VAV boxes
Air Handling Units
AIR HANDLING UNIT (AHU)
Primary equipment of the air system
Handle & condition the air, control it to a required state, and
transport it
Basic components:
• Supply fan, water cooling coil, filters, mixing box, dampers,
controls & outer casing
• A return or relief fan is optional, so as a humidifier
Air Handling Units
TYPES OF AHU’s
Horizontal or vertical
Draw-through or blow through
Factory-fabricated and field built-up
Rooftop and indoor
Make-up (primary) air
Recirculating
Air Handling Units
Air Handling Units
Air Handling Units
PACKAGE UNITS
A self-contained air conditioner
Equipped with a DX (direct expansion) coil
“Air handler”: the portion inside that handles air
Air Handling Units
ROOFTOP PACKAGE UNITS
Gas heating / electric cooling
Electric heating / electric cooling
Heat pump system
Air Handling Units
Air Handling Units
INDOOR PACKAGE UNITS
Factory-assembly unit installed in a fan room or machinery
room
Floor-mounted or ceiling-mounted
Cooling, cooling/heating, heat pump
Heat rejection:
• Connected to an air-cooled condenser, OR
• Water-cooled condenser
Air Handling Units
SPLIT PACKAGE UNITS
Indoor air handler + outdoor condensing unit
Air Handling Units
RATING CONDITIONS & MINIMUM PERFORMANCE
ARI and ASHRAE standards
Rating indices:
• Energy efficiency ratio (EER)
• Seasonal EER
• Integrated part-load value (IPLV)
• Heating seasonal performance factor (HSPF)
Air Handling Units
COILS
Indirect contact heat exchangers
Heat transfer between air flowing over the coil and water,
refrigerant, steam or brine insider the coil
Fins: extended (secondary) surfaces
• Fin spacing and density
Water circuits
• Number of water flow passages
Air Handling Units
DIRECT EXPANSION (DX) COIL
Refrigerant is fed (e.g. R-22 and R-134a)
Air and refrigerant flow:
• Usually counterflow and cross flow
Typical evaporating temperature = 3-10 oC
Condensate drain pan (to collect condensation)
Performance factors:
• Face velocity, heat transfer coefficients, air-side pressure
drop, physical size
Air Handling Units
WATER COOLING COILS - DRY-WET COIL
Chilled water flowing at 4-10 oC
Brine or glycol-water at 1-4 oC
Temperature rise (typical) = 7-14 oC
WATER COOLING COILS - DRY COIL
Sensible cooling (dry); no condensation
Poorer heat transfer coefficient
STEAM HEATING COIL
Air Handling Units
Air Handling Units
Air Handling Units
Air Handling Units
Air Handling Units
AIR FILTERS
Air cleaning and filtration
Operating performance:
• Efficiency or effectiveness of dust removal
• Dust holding capacity
• Initial & final pressure drop
• Service life
Types: low-, medium-, and high-efficiency filters + carbon
activated filters
Air Handling Units
TEST METHODS OF AIR FILTERS
Weight arrestance test
• For low-efficiency air filters
Atmospheric dust spot efficiency
• For medium-efficiency air filters
DOP (dioctyl phthalate) penetration and efficiency test
• For high-efficiency air filters
o HEPA (high-efficiency particle air)
o ULPA (ultra-low penetration air)
Air Handling Units
Air Handling Units
Air Handling Units
HUMIDIFIERS
Steam humidifiers
Air washers
Air Handling Units
SELECTION OF AHUs
Face velocity < 3 m/s to prevent entrained droplets
Proper size of the equipment (energy efficiency)
Medium-efficiency filter >50% dust spot eff.:
• improve IAQ,
• prevent smudging &
• discoloring
Air economizer: save energy
Air Handling Units
Air Handling Units
Air System Basics
Air System Basics
FAN-DUCT SYSTEMS
Flow resistance , pressure drop and volume flow rate