Charging System
Charging System
MODULE-3 (PART-II)
CHARGING SYSTEM
Results- When your test shows a steady or intermittent high or low voltage output, the
voltage regulator is possibly bad. Most voltage regulators fail by allowing a high voltage
output, though. However, before going any further, check that all the connections to the
alternator and battery are good and clean.
Cut out Relay
When the generator speed is very low, due to which the
output is not sufficient to balance the battery voltage, the
necessity to cutout the generator from the battery arises,
because otherwise the battery would discharge into the
generator.
When the engine and hence the generator speed has
reached a sufficiently higher value to match its output to
the battery voltage the generator should be automatically
connected to the battery.
In this electromagnet consists of two coils, the shunt
(voltage) and the series (current). When the generator is
producing sufficient voltage so that the field due to both
the current and the voltage coils support each other, the
electromagnet pulls down the armature, the contacts are
closed and the generator-battery circuit is completed.
When due to low engine speeds the generator voltage falls
below the battery voltage, the current flows from the
battery to the generator. Then the fields due to current and
voltage windings become opposed to each other. Hence
the pull on the armature decrease, the contacts open out
and the battery is cut from the generator.
Combined Voltage and Current Regulator
It consists of three main units like cutout relay, current regulator and voltage regulator.
The voltage regulator consists of a series winding and a shunt winding, both wound on a single
core. The series winding is made of a few turns of thick wire and one end of this is connected to the
field terminal of the regulator while the other end is grounded via the contact points. The shunt
winding is made of a few turns of thin wire, whose one end is connected to the cutout relay while
the other end is grounded. Both the series and the shunt winding are wound in such a manner that
the fields due to these support each other.
When the generator is producing higher voltage than for which the regulator is set, the force due to
shunt and series windings will pull the armature down, thereby separating the contact points. This
inserts a resistance in series in the generator field circuit as a result of which the voltage drops
When the voltage has decreased, so that magnetic force is not sufficient to pull the regulator
armature down, it goes up again making the contacts and thereby grounding the generator field
Continuation…
The current regulator consists of a heavy series
winding. When the regulator is not operating, the
contact points are closed and the generator field
circuit is grounded.
When the load on the generator increases and the
generator voltage is not sufficient to operate the
voltage regulator, the generator current continues to
rise till the stage is reached where the current in the
regulator coil is sufficient to pull the armature
down separating the contacts, thus inserting the
resistance in the generator field circuit which brings
down the generator output, until the current
decrease to a value such that the series winding in
the current regulator cannot exert enough force to
keep the contacts separated.
The contacts then close and the generator field
circuit is grounded again thus increasing its output.
In this way it maintains the current output at a
preset constant value.
Regulators for Alternators
The vibrating contact points are used to insert the resistance into the
alternator field circuit to prevent excessive voltage or current output.
The load relay is a circuit breaker that connects the alternator to the
battery for charging and disconnecting the two when the alternator
slows down or stops.
A separate load relay rectifier is used to operate the windings of the
load relay.
Advantages of Alternator over dc
Generators
About 30% higher speeds can be achieved when compared with a dc generator whose
operating speed is restricted to 9000 rpm. An alternator can run safely at about 2.5 times
the engine speed, whereas a dc generator is limited to about 1.75 times the engine speed.
For a given output, the alternator can be made appreciably smaller and lighter. In other
words, it has a high output weight ratio.
An alternator does not require much maintenance attention because of the use of light
slip ring brushes when compared with the dc generator heavy brush gear and
commutator. The life of these brushes is much higher than that of commutator type
brushes because there is no commutator with temperature and wear problems.
An alternator is simple and robust in design when compared with a dc generator and
hence more reliable.
A high output at low engine speed can be obtained. The battery can be charged even
when the engine is idling, which is not so with a dc generator, with its cutout relay.
The cutout relay is not essential because any reverse current flow due to fall in voltage
below that of the battery is not allowed by the rectifier.
The alternator can be made to provide self-regulation due to its winding reactance which
eliminates the use of external control as required in the case of a dc generator.
Disadvantage of Alternator
The present disadvantage of the alternator is its initial cost which is
more than that of a dc generator. It is because of the high cost of
rectifiers.
Charging System Troubleshooting
Defects Causes Remedies
Brushes sticking Free; brushes and springs may be
replaced as required.
Commutator dirty (dc) Clean; turn down commutator and
undercut mica if required.
Commutator burned (dc) Clean; turn down commutattor and
undercut mica, if required; check
1. No Output
setting of current regulator.
Loose connections broken leads Tighten connection; replace leads.
Armature earthed Check with test lamp; repair or
replace.
Armature open Repair or replace.
Armature shorted Test on growler; repair or replace.
Field earthed Test it with test lamp; repair or
replace.
High open circuit voltage Reset regulator
Voltage regulator shunt winding Locate and rectify if possible, else
open replace regulator.
2. Overcharging/excessive
output Field circuit earthed Check with test lamp; repair or
replace.
Field circuit shorted Test with ammeter; repair or replace
Charging System Troubleshooting
Defects Causes Remedies