Transformers
Transformers
TRANSFORMERS
Presentation outline
Need
Working Principle
Types of Transformers
Construction Features
Transformers Accessories
Major Transformers in Power Plants
Transformer Losses
Condition Monitoring of Transformers
WHY TRANSFORMER
• TO OPTIMISE COST OF BULK TRANSMISSION
OF POWER FROM GENERATORS TO
CONSUMERS
• REDUCTION IN TRANSMISSION LOSS
• TO REDUCE OR INCREASE VOLTAGE IN AC
SYSTEM
• ENABLES SAFE SUPPLY VOLTAGE TO
CONSUMERS
• ISOLATION OF TWO SYSTEMS FOR VOLTAGE
REGULATION
Definition of Transformer as per Stds
IEC 60076-1
IEEE C57.12.80-2002
A static device consisting of a winding, or two or more
coupled windings with or without a magnetic core for
introducing mutual coupling between electrical
circuits.
What are the Types of
Transformers
Power transformers : Used in transmission
network of higher voltages, deployed for step-up
and step down transformer application (400 kV,
200 kV, 110 kV, 66 kV, 33kV,22kV)
Vp/Vs = Np/Ns
where
• Vp and Vs are the voltages across the primary
winding and secondary winding,
• Np and Ns are the numbers of turns in the
primary winding and secondary winding,
• dΦP / dt and dΦS / dt are the derivatives of the
flux with respect to time of the primary and
secondary windings.
Classifications
and also
Insulation
•Cooling
•Protection
•Supporting accessories
COMPONENTS - CORE
Core
conservator
Breather
GENERATOR
4UA 4UB
SA SB
IN THE EVENT OF UNIT TRIPPING AUTO CHANGEOVER
FROM UT TO STATION WILL TAKE PLACE
Station Transformers
3. Acoustic PD measurement.
In case DGA results indicate the presence of high discharges
Acoustic PD measurement is done.
Acoustic PD detector consists of sensor which can sense
sound vibrations produced due to occurrence of discharges in
oil.
The sensor has pre-amplifier and filter circuit to eliminate
environmental noise
4 Infrared thermography
With the help of infrared thermo-vision camera, the thermo-
image of transformer is prepared
This scanning helps in detecting overheated zones, loose &
corroded connection.
OFF LINE MONITORING
1. Frequency Response Analysis
• Short circuit forces could move the winding.
• Can also change winding inductance and capacitance.
• Conventional tests are not sensitive to winding
movement.
• Such changes can be effectively detected by FRA
Method
• Sweep frequency input is given in the winding.
• Input & response recorded.
• FFT analysis of response to obtain the finger print of the
winding.
• These finger prints are compared periodically to assess
the condition of winding.
2. Recovery voltages measurement
It indicates the content of water in the insulation.
PRINCIPLE
•Sample of discharged insulation
•Charge with DC voltage and note time
•Sample to be short circuited for predetermined period of
time ( approximately half of the charged time)
•Open the terminal and measure voltage.
3. Tan- & Capacitance by standard bridge.
4. Resistance & magnetizing current.
5. Maintenance schedule call for daily , quarterly, yearly, two
yearly maintenance requirement. Over and above after 7 to
10 years, thorough overhauling and inspection of core-coil
assembly by lifting tank top cover / core-coil assembly
needed
In overhauling sludge deposited on coil is removed and coil
assembly which may become loose is tightened. All other
clampings & cleats etc. are also tightened
THANK YOU