Basics of Transformer
Basics of Transformer
CORPORATE ENGINEERING
ROBINSONS LAND CORPORATION
A transformer has no internal moving parts, and it transfers energy from one
circuit to another by electromagnetic induction. External cooling may include
heat exchangers, radiators, fans, and oil pumps. Radiators and fans are evident in
figure 1. the large horizontal tank at the top is a conservator. Transformers are
typically used because a change in voltage is needed. Power transformers are
defined as transformers rated 500 kVA and larger. Larger transformers are oil-
filled for insulation and cooling; a typical GSU transformer may contain several
thousand gallons of oil. One must always be aware of the possibility of spills,
leaks, fires, and
environmental risks this oil poses.
Transformers smaller than 500 kVA are generally
called distribution transformers. Pole-top and small,
pad-mounted transformers that serve residences and
small businesses are typically distribution transformers.
Generator step-up transformers, used in Reclamation
power plants, receive electrical energy at generator
voltage and increase it to a higher voltage for
Figure 1 – Typical GSU Three-
transmission lines. Conversely, a step down
Phase transformer receives energy at a higher voltage and
Transformer.
delivers it at a lower voltage for distribution to various
loads.
All electrical devices using coils (in this case, transformers) are constant wattage
devices. This means voltage multiplied by current must remain constant;
therefore, when voltage is “stepped-up,” the current is “stepped-down” (and vice
versa). Transformers transfer electrical energy between circuits completely
insulated from each other. This makes it possible to use very high (stepped-up)
voltages for transmission lines, resulting in a lower (stepped-down) current.
Higher voltage and lower current reduce the required size and cost of
transmission lines and reduce transmission losses as well. Transformers have
made possible economic delivery of electric power over long distances.
When an external circuit is connected to the second coil, the induced voltage in
the coil will cause a current in the second coil. The coils are said to be
magnetically coupled; they are, however, electrically isolated from each other.
Many transformers have separate coils, as shown in figure 3, and contain many
turns of wire and a magnetic core, which forms a path for and concentrates the
magnetic flux. The winding receiving electrical energy from the source is called
the primary winding. The winding which receives energy from the primary
winding, via the magnetic field, is called the “secondary” winding.
Either the high- or low-voltage winding can be the primary or the secondary.
With GSUs at Reclamation power plants, the primary winding is the low-
voltage side (generator voltage), and the high-voltage side is the secondary
winding (transmission voltage). Where power is used (i.e., at residences or
businesses), the primary winding is the high-voltage side, and the secondary
winding is the low-voltage side.
The amount of voltage induced in each turn of the secondary winding will be
the same as the voltage across each turn of the primary winding. The total
amount of voltage induced will be equal to the sum of the voltages induced in
each turn. Therefore, if the secondary winding has more turns than the primary,
a greater voltage will be induced in the secondary; and the transformer is known
as a step-up transformer. If the secondary winding has fewer turns than the
primary, a lower voltage will be induced in the secondary; and the transformer
is a step-down transformer. Note that the primary is always connected to the
source of power, and the secondary is always connected to the load.
In actual practice, the amount of power available from the secondary will be
slightly less than the amount supplied to the primary because of losses in the
transformer itself.
When an AC generator is connected to the primary coil of a transformer (figure
4), electrons flow through the coil due to the generator voltage. Alternating
current varies, and accompanying magnetic flux varies, cutting both transformer
coils and inducing voltage in each coil circuit.
Figure 4 – Transformer.
The voltage induced in the primary circuit opposes the applied voltage and is
known as back voltage or back electro-motive-force (back EMF). When the
secondary circuit is open, back EMF, along with the primary circuit resistance,
acts to limit the primary current. Primary current must be sufficient to maintain
enough magnetic field to produce the required back EMF.
When the secondary circuit is closed and a load is applied, current appears in the
secondary due to induced voltage, resulting from flux created by the primary
current. This secondary current sets up a second magnetic field in the transformer
in the opposite direction of the primary field. Thus, the two fields oppose each
other and result in a combined magnetic field of less strength than the single field
produced by the primary with the secondary open. This reduces the back voltage
(back EMF) of the primary and causes the primary current to increase. The
primary current increases until it reestablishes the total magnetic field at its
original strength.
In transformers, a balanced condition must always exist between the primary and
secondary magnetic fields. Volts times amperes (amps) must also be balanced (be
the same) on both primary and secondary. The required primary voltage and
current must be supplied to maintain the transformer losses and secondary load.
TRANSFORMER VOLTAGE AND CURRENT
If the small amount of transformer loss is ignored, the back-voltage (back EMF)
of the primary must equal the applied voltage. The magnetic field, which
induces the back-voltage in the primary, also cuts the secondary coil. If the
secondary coil has the same number of turns as the primary, the voltage induced
in the secondary will equal the back-voltage induced in the primary (or the
applied voltage). If the secondary coil has twice as many turns as the primary, it
will be cut twice as many times by the flux, and twice the applied primary
voltage will be induced in the secondary. The total induced voltage in each
winding is proportional to the number of turns in that winding. If E1 is the
primary voltage and I1 the primary current, E2 the secondary voltage and I2 the
secondary current, N1 the primary turns and N2 the secondary turns, then:
Note that the current is inversely proportional to both voltage and number of
turns. This means (as discussed earlier) that if voltage is stepped up, the current
must be stepped down and vice versa. The number of turns remains constant
unless there is a tap changer (discussed later).
The power output or input of a transformer equals volts times amperes (E x I).
If the small amount of transformer loss is disregarded, input equals output or:
If the primary voltage of a transformer is 110 volts (V), the primary winding
has 100 turns, and the secondary winding has 400 turns, what will the
secondary voltage be?
If the primary current is 20 amps, what will the secondary current be?
Since there is a ratio of 1 to 4 between the turns in the primary and secondary
circuits, there must be a ratio of 1 to 4 between the primary and secondary
voltage and a ratio of 4 to 1 between the primary and secondary current. As
voltage is stepped up, the current is stepped down, keeping volts multiplied by
amps constant. This is referred to as “volt amps.”
Note that kVA (amps times volts) remains constant throughout the above circuit
on both sides of each transformer, which is why they are called constant wattage
devices.
The two common arrangements of the magnetic path and the windings are
shown in figure 6 and 7. In the core-type (core form) transformer, the windings
surround the core.
A section of both primary and secondary windings are wound on each leg of the
core, the low voltage winding is wound next to the core, and the high voltage
winding is wound over the low voltage.
where V is the voltage drop or, in this case, 72 volts; and I is the full load
current in the primary winding. If the full load current is 10 amps:
Of course, one must remember that impedance is made up of both resistive and
reactive components.
INTERNAL FORCES
During normal operation, internal structures and windings are subjected to
mechanical forces due to the magnetic forces. By designing the internal structure
very strong to withstand these forces over a long period of time, service life can
be extended. However, in a large transformer during a “through fault” (fault
current passing through a transformer), forces can reach millions of pounds,
pulling the coils up and down and pulling them apart 60 times per second. The
internal low-voltage coil is being pulled downward, while the high-voltage
winding is pulled up, in the opposite direction. At the same time, the high- and
low-voltage coils are being forced apart. Keep in mind that these forces are
reversing 60 times each second. It is obvious why internal structures of
transformers must be built incredibly strong.
Many times, if fault currents are high, these forces can rip a transformer apart
and cause electrical faults inside the transformer itself. This normally results in
arcing inside the transformer that can result in explosive failure of the tank,
throwing flaming oil over a wide area. There are protective relaying systems to
protect against this possibility, although explosive failures do occur
occasionally.
AUTOTRANSFORMERS
It is possible to obtain transformer action by means of a single coil, provided
that there is a “tap connection” somewhere along the winding. Transformers
having only one winding are called autotransformers, shown schematically
in figure 9.
An autotransformer has the usual magnetic core but only one winding, which
is common to both the primary and secondary circuits.
The primary is always the portion of the winding connected to the AC power
source. This transformer may be used to step voltage up or down. If the
primary is the total winding and is connected to a supply, and the secondary
circuit is connected across only a portion of the winding (as shown), the
secondary voltage is “stepped-down.”
If only a portion of the winding is the
primary and is connected to the supply
voltage and the secondary includes all the
winding, then the voltage will be
“stepped-up” in proportion to the ratio of
the total turns to the number of connected
Figure 9 – Autotransformers.
turns in the primary winding.
When primary current I1 is in the direction of the arrow, secondary current, I2,
is in the opposite direction, as in figure 9b. Therefore, in the portion of the
winding between points b and c, current is the difference of I1 and I2. If the
requirement is to step the voltage up (or down) only a small amount, then the
transformer ratio is small—E1 and E2 are nearly equal. Currents I1 and I2 are
also nearly equal. The portion of the winding between b and c, which carries the
difference of the currents, can be made of a much smaller conductor, since the
current is much lower.
Under these circumstances, the autotransformer is much cheaper than the two-
coil transformer of the same rating. However, the disadvantage of the
autotransformer is that the primary and secondary circuits are electrically
connected and, therefore, could not safely be used for stepping down from high
voltage to a voltage suitable for plant loads. The autotransformer, however, is
extensively used for reducing line voltage for step increases in starting larger
induction motors. There are generally four or five taps that are changed by
timers so that more of the winding is added in each step until the full voltage is
applied across the motor. This avoids the large inrush current required when
starting motors at full line voltage. This transformer is also extensively used for
“buck-boost” when the voltage needs to be stepped up or down only a small
percentage. One very common example is boosting 208 V up from one phase of
a 120/208-V three-phase system, to 220 V for single-phase loads.
INSTRUMENT TRANSFORMERS
Instrument transformers (figure 10) are used for measuring and control purposes.
They provide currents and voltages proportional to the primary, but there is less
danger to instruments and personnel.
Figure 15 – Single-
Phase Transformer.
Each section has the same number of turns and, consequently, the same voltage.
Two primary leads (H1, H2) are brought out from the top through porcelain
bushings. Three secondary leads (X1, X2, X3) are brought out through insulating
bushings on the side of the tank, one lead from the center tap (neutral) (X2) and
one from each end of the secondary coil (X1 and X3). Connections, as shown, are
typical of services to homes and small businesses. This connection provides a
three-wire service that permits adequate capacity at minimum cost. The neutral
wire (X2) (center tap) is grounded. A 120-volt circuit is between the neutral and
each of the other leads, and a 240-volt circuit is between the two ungrounded
Parallel Operation of Single-Phase Transformers for
Additional Capacity
In perfect parallel operation of two or more transformers, current in each
transformer would be directly proportional to the transformer capacity, and the
arithmetic sum would equal one-half the total current. In practice, this is seldom
achieved because of small variations in transformers. However, there are
conditions for operating transformers in parallel. They are:
1. Any combination of positive and negative polarity transformers can be used.
However, in all cases, numerical notations must be followed on both
primary and secondary connections. That is H1 connected to H1, H2
connected to H2, and X1 connected to X1, X2 connected to X2, X3
connected to X3. Note that each subscript number on a transformer must be
connected to the same subscript number on the other transformer as shown in
figure 16.
2. Tap settings must be identical.
3. Voltage ratings must be identical; this, of course, makes the turns ratios also
identical.
4. The percent impedance of one transformer must be between 92½% and
107½% of the other. Otherwise, circulating currents between the two
transformers would be excessive.
5. Frequencies must be identical. Standard frequency in the United States is 60
hertz and usually will not present a problem.
One will notice, from the above requirements, that paralleled transformers do
not have to be the same size. However, to meet the percent impedance
requirement, they must be nearly the same size. Most utilities will not
parallel transformers if they are more than one standard kVA size rating
different from each other; otherwise, circulating currents are excessive.
Three-Phase Transformer Connections
Three-phase power is attainable with one three-phase transformer, which is
constructed with three single-phase units enclosed in the same tank or three
separate single-phase transformers. The methods of connecting windings are
the same, whether using the one three-phase transformer or three separate
single phase transformers.
The other method, figure 17b, is known as the star or wye connection. The wye
differs from the delta connection in that it has two phases in series. The common
point “O” of the three windings is called the neutral because equal voltages exist
between this point and any of the three phases.
When windings are connected wye, the voltage between any two lines will be
1.732 times the phase voltage, and the line current will be the same as the
phase current. When transformers are connected delta, the line current will be
1.732 times the phase current, and the voltage between any two will be the
same as that of the phase voltage.
Three-Phase Connections Using Single-Phase
Transformers
As mentioned above, single-phase transformers may be connected to obtain three
phase power. These are found at many Reclamation facilities, at shops, offices,
and warehouses. The same requirements must be observed as in section 2.18,
“Parallel Operation of Single-phase Transformers for Additional Capacity,” with
one additional requirement—in the manner connections are made between
individual single-phase units. ANSI standard connections are illustrated below in
the following figures. There are other angular displacements that will work but
are seldom used. Do not attempt to connect single-phase units together in any
combination that does keep the exact angular displacement on both primary and
secondary; a dangerous short circuit could be the result. Additive and subtractive
polarities can be mixed (see the following figures). These banks also may be
paralleled for additional capacity if the rules are followed for three-phase
paralleling discussed below. When paralleling individual three-phase units or
single phase banks to operate three phase, angular displacements must be the
same.
Figure 18 shows delta-delta connections. Figure 19 shows wye-wye connections,
which are seldom used at Reclamation facilities, due to inherent third harmonic
problems. Methods of dealing with the third harmonic problem by grounding are
listed below.
Figure 19 – Wye-Wye Connections, Using Single-
Phase Transformers for Three-Phase Operation.
Figure 18 – Delta-Delta Connections, Single-Phase
Transformers for Three-Phase Operation.
Paralleling Three-Phase Transformers
Two or more three-phase transformers, or two or more banks made up of three
single-phase units, can be connected in parallel for additional capacity. In
addition to requirements listed above for single-phase transformers, phase
angular displacements (phase rotation) between high and low voltages must be
the same for both. The requirement for identical angular displacement must be
met for paralleling any combination of three-phase units and/or any combination
of banks made up of three single-phase units.
Some systems are designed to add nitrogen automatically (figure 24) from
pressurized tanks when the pressure drops below a set level. A positive pressure
of approximately 0.5 to 5 pounds per square inch (psi) is maintained in the gas
space above the oil to prevent ingress of air. This system includes a nitrogen gas
cylinder; three-stage, pressure-reducing valve; high-and low-pressure gauges;
high and low pressure alarm switch; an oil/condensate sump drain valve; an
automatic pressure relief valve; and necessary piping.
The function of the three-stage, automatic
pressure-reducing valves is to reduce the
pressure of the nitrogen cylinder to supply the
space above the oil at a maintained pressure of
0.5 to 5 psi.
The high-pressure gauge normally has a range
of 0 to 4,000 psi and indicates nitrogen cylinder
pressure. The low-pressure gauge normally has
a range of about -5 to +10 psi and indicates
nitrogen pressure above the transformer oil.
In some systems, the gauge is equipped with
high- and low-pressure alarm switches to alarm
when gas pressure reaches an abnormal value;
the high-pressure gauge may be equipped with
a
pressure switch to sound an alarm when the supply cylinder pressure is running low.
A sump and drain valve provide a means for collecting and removing condensate and oil from
the gas. A pressure-relief valve opens and closes to release the gas from the transformer and,
thus, limit the pressure in the transformer to a safe maximum value. As temperature of a
transformer rises, oil expands, and internal pressure increases, which may have to be relieved.
When temperature drops, pressure drops, and nitrogen may have to be added, depending on the
extent of the temperature change and pressure limits of the system.
Indoor Transformers
When oil-insulated transformers are located indoors, because of fire hazard, it is
often necessary to isolate these transformers in a fireproof vault.
Today, dry-type transformers are used extensively for indoor installations. These
transformers are cooled and insulated by air and are not encased in sealed tanks
like liquid-filled units. Enclosures in which they are mounted must have sufficient
space for entrance, for circulation of air, and for discharge of hot air. Dry-type
transformers are enclosed in sheet metal cases with a cool air entrance at the
bottom and a hot air discharge near the top. They may or may not have fans for
increased air flow.