1-Dist Part 1
1-Dist Part 1
1-Dist Part 1
0,6s 0,3s
0,6s 0,3s
0,6s 0,3s
0,6s 0,3s
non-selective trip
relay A
relay A
selectivity
IL2 ZL = RL + j X L
IL3
IE ZE ZE = RE +j XE
Measured current
measured voltage
06.08.97
dtgerdis3
IL2
ZL = RL + j XL
IL3
IE ZE ZE = RE +j XE
phase-ground-loop:
UL1 = L1 · ( RL + j XL )- E · ( RE +j XE)
06.08.97
dtgerdis3
Fault area
X RF RF
ZL F1 F2 ZLoad
D
ZLF2 Phase - Phase Fault
RR ZF2
RR RF / 2
ZLoad
RR Phase - Earth Fault
ZLF1 ZF1 ad
as i ng l o RR RF /(1 + RE/RL)
Incre
L
Minimum Load Impedance:
SC2
R Minimum voltage 0,9 Un
Fault in SC1
Maximum current 1,1 In
reverse Maximum angle 30°
direction
Load area
ZSC
E
Relay design:
comparator operation if
U1< U2
i.e. ZSC< ZReplica
X ZReplica
U2=k2 ISCZReplica Ext. fault
ZReplica (line replica impedance)
Internal fault
(corresponds to the set zone reach)
R
internal
centre
fault
R
R
polarised
MHO-circle quadrilateral
X
X
ZS = 0
RF XA
ZL settable arc
ZSC-L compensation
R Rarc
ZS small
RA R
ZS high ZS
Power Automation
Progress. It‘s that simple.
Z3
t = grading time
time Z2 t3
Z1 t2
t1
A B C D
D1 D2 D3
distance
Grading rules:
Safety margin is 15 %:
Z1 = 0,85 ZAB
- line error
Z2 = 0,85 (ZAB + 0,85 ZBC) - CT, VT error
- measuring error
Z3 = 0,85 (ZAB + 0,85 (ZBC + 0,85 ZCD))
+ errors of the distance relay internal timers mechanical: 5% of the set time, minimum 60-100 ms
static: 3% of the set time, minimum 10 ms
digital: 1% of the set time, minimum 10 ms
+ distance protection starting time *) mechanical: O/C starter: 10 ms, impedance starter: 25 ms
static: O/C stater: 5 ms, impedance starter: 25 ms
digital: generally 15 ms
*) only relevant if the set relay times relate to the instant of fault detection / zone pick-up. This is the case with all
Siemens relays. There are other relays where the time is adapted by software to relate to the instant of fault
inception. In the latter case the starting time has to be dropped.
SC Z'SC
Current area for Impedance area for
reverse faults reverse faults
Power Automation
Progress. It‘s that simple. Why impedance measurement and directional determination separately?
A B
line characteristic
X
fault with arc resistance
in forward direction
fault in forward direction
close-in fault
R
fault in reverse
direction
Method 1 Method 2
Vf
VL1
If VL1
VL1 Vf
VL3
Vf
VL2
faulty phase voltage
If If
VL3 VL2
VL3 VL2-L3 VL2
voltage memory
healthy-phase voltage (pre-fault voltage)
(phase to phase voltage)
Directional measurement
Summery of all 3 methods
Power Automation
Progress. It‘s that simple.
uRI = uL2-L3
uf = uL1
if(t)
uL1
Distance measurement
Measuring uL1 if
Direction measurement
window if
with voltage memory
uL2-L3
Direction measurement
with unfaulted voltage
if
06.08.97
dtgerdis9
Not in 7SA522
1,0 UN · 1,1
ISC(2) =
I>start = 600 A 2 · (ZS + ZS + Z L' · l)
N T
0,5
There is a limitation
to the reach
10 20 30 40 50 60 l [km]
reach of OC starter
approx. 32 km
G SC
Power line
system digital
USC U
electro-mechanical
G
Relay UN
ZS ISC ZSC
UI>
E USC
UI>>
I> I>> I
E
USC
U/UN
100 %
50 %
for
Progress. It‘s that simple.
wa
X
rd
Line
Distance zones
s
Z5
Inclined with line angle
Z4 Angle prevents overreach of Z1
Z2 on faults with fault resistance
Z1B that are fed from both line
ends
Z1
rev
ers
e
Load Load
forw
ard
s
Fault detection
no fault detection polygon: the
Z3
largest zone determines the
fault detection characteristic
simple setting of load
rev
Z3
Z2
A Z1 B C D
D D D >> ZT
>t
Z1 = 0.85 ZA-B
Grading according
Z2 = 0.85 (ZA-B + 0.85 ZB-C) the recommendation
with the safety margin
Z3 = 0.85 [ ZA-B + 0.85 (ZB-C+ 0.85 ZC-D) ]
of 15%.
grading time
(s)
0.6
0.3
L2
Z1 L3
L1
Z2
L4
The impedances of the Z2 and Z3 must be grading with the shortest impedance