Eee3352 L6&7&8
Eee3352 L6&7&8
Eee3352 L6&7&8
AND MACHINES
TRANSFORMERS
INTRODUCTION
• A transformer consists of at least two windings having a
common magnetic circuit.
• In practice, it is arranged that all or nearly all of the flux
linking the first winding also passes through the second
winding.
• This is achieved by having a well defined low reluctance
magnetic circuit between the two windings.
• When two inductors (or coils) are in a close proximity to
each other, the magnetic flux caused by current in one coil
links with the other coil, thereby inducing voltage in the
latter. This phenomenon is known as mutual inductance.
BASIC RELATIONS
APPLICATIONS
• Transformers are the largest, the heaviest, and
often the costliest of circuit components.
• Nevertheless, they are indispensable passive
devices in electric circuits.
• The main application is converting energy from
electrical energy to electrical energy.
• They are among the most efficient machines, 95%
efficiency being common and 99% being achievable.
• Transformers are used:
To step up or step down voltage and current,
making them useful for power transmission and
distribution.
To isolate one portion of a circuit from another
(i.e., to transfer power without any electrical
connection).
As an impedance-matching device for
maximum power transfer.
In frequency-selective circuits whose operation
depends on the response of inductances.
TRANSFORMER DESIGNS
• Due to diverse uses, there are many special
designs for transformers:
Voltage transformers, current transformers,
power transformers, distribution
transformers, impedance-matching
transformers, audio transformers, single-
phase transformers, three phase transformers,
rectifier transformers, inverter transformers,
and more.
Transformer Photos
POWER TRANSFORMER
POWER TRANSFORMER HVDC TRANSFORMER
POLE-MOUNTED TRANSFORMER
CAPACITIVE VT
i1 N 2 V N i
i1 N1 i2 N 2 and . Thus, 1 1 2
i2 N1 V2 N 2 i1
E.M.F. Equation of a Transformer
• On the primary side:
E1 4.44 fN1m
• On the secondary side:
E2 4.44 fN 2m
• The current both on the primary and secondary sides
and phase angles between voltage and current are
determined by the consumer’s load (not by power
station).
• The voltage level is determined by the power station.
Examples
The maximum flux density in the core of a 250/3000
volts , 50 Hz single-phase transformer is 1.2 Wb/m 2.
If the e.m.f. per turn is 8 volts, determine (i) primary
and secondary turns (ii) area of the core.
The core of a 100 kVA, 11000/550 V, 50-Hz, 1-phase,
core type transformer has a cross-sectional area of
20 cm×20 cm. Find (i) the number of HV and LV
turns per phase and (ii) the emf per turn if the
maximum core density is not to exceed 1.3 Tesla.
Assume a stacking factor of 0.9. What will happen if
its primary voltage is increased by 10% on no-load?
A single-phase transformer has 400 primary and
1000 secondary turns. The net cross-sectional area
of the core is 60 cm2. If the primary winding is
connected to a 50-Hz supply at 520-V, calculate (i)
the peak value of flux density in the core (ii) the
voltage induced in the secondary winding.
A 25 kVA transformer has 500 turns on the primary
and 50 turns on the secondary winding. The
primary is connected to 3000-V, 50-Hz supply. Find
the full-load primary and secondary currents, the
secondary emf and the maximum flux in the core.
Neglect leakage drops and no-load primary current.
Practical (Real) Transformer
• A real transformer has:
Leakage flux
Finite reluctance
Copper loss
Iron loss
Winding resistances: R1 and R2-the designer
ensures that these are small.
Ro, iron loss element (no-load element)-the
designer aims for a very high Ro to have low PFe.
• Leakage reactances, jX1 and jX2, represent the
effect of leakage flux. They are small compared to
any other reactances.
• Magnetizing reactance, jXo, comes about because
of finite reluctances.
I1 N1 I 2 N 2 S ; for ideal case, S 0, thus, I1 N1 I 2 N 2 .
For real transformers, S 0. Thus, let S I N1 and I1 N1 I 2 N 2 I N1
I1 I I O and I O I I
'
2
2
w
2 1/ 2
VECTOR
DIAGRAM OF A
TRANSFORMER
ON NO-LOAD
Phasor Diagrams Cont.
• The primary voltage V1 has three components:
1. -E1, the induced e.m.f. which opposes V1
2. I1 R1, the drop across the resistance, in phase with I1
3. I1 X1, the drop across the reactance, leading I1 by 90o
E2 V2 I R cos 2 I 2 X 2 sin 2
Voltage regulation(%) 100% 2 2 100%
E2 E2
Effect of Load Power Factor on Regulation
• For total equivalent reg f ( I 2 )
circuit: I 2' Z eq
VR primary cos( eq 2 )
V1
I 2 Z eq
VRsec ondary cos( eq 2 )
V2 I2
f ( I 2 , 2 )
• Define I x (FL=full load or rated value, S V I ).
2
I 2 FL
r r r
• X gives the value of the full load constant.
V2 xI 2 FL cos 2 xS r cos 2
V2 xI 2 FL cos 2 x 2 I 22FL RT sec PFe xS r cos 2 x 2 PCuFL PFe
Maximum Efficiency
1. Consider variable power factor for a specific full load
current:
xSr
2
x PCuFL PFe
xSr
cos 2
• We need the denominator to be minimum for
maximum η, this occurs when cosθ2=maximum, i.e.
cosθ2=1 at unity power factor.
2. Consider variable load current:
S r cos 2
PFe
S r cos 2 xPCuFL
x
• For maximum η, we need denominator to be
minimum:
d PFe
S r cos 2 xPCuFL 0
dx x
PFe 2 PFe
0 2
PCuFL 0, x PCuFL PFe , x
x PCuFL
• The maximum η occurs when the variable
copper loss has the value of the constant iron
loss, i.e. PCu=PFe.
1
• For half full load x
2 and for full load
x 1.
• The graph on top
here shows how
a 75 kVA
Transformer
losses vary with
load, whereas
the one below
shows how the
efficiency varies
with load.
Transformer Temperature rises
PRACTICE QUESTIONS
1. (a) A 2200/200 V transformer draws a no-load primary current of
0.6 A and absorbs 400 watts. Find the magnetising and iron loss
currents.
(b) A 2200/250 V transformer takes 0.5 A at a p.f. of 0.3 on open
circuit. Find the magnetising and working components of no-load
primary current.
2. A single-phase transformer has 500 turns on the primary and 40
turns on the secondary windings. The mean length of the magnetic
path in the iron core is 150 cm and the joints are equivalent to an air
gap of 0.1 mm. When a p.d. of 3000 V is applied to the primary, the
maximum flux density is 1.2 Wb/m2. Calculate (a) the cross-sectional
area of the core, (b) no-load secondary voltage, (c) the no-load
current drawn by the primary, (d) power factor on no-load. It is given
that At/cm for a flux density of 1.2 Wb/m2 in iron is 5 and the
corresponding iron loss is 2 watt/kg at 50 Hz, the density of iron
being 7.8 g/cm3.
3. A 11000/230 V, 150 kVA, 1-phase, 50-Hz
transformer has core loss of 1.4 kW and full-load
copper loss of 1.6 kW. Determine
(a) the kVA load for maximum efficiency and value
of maximum efficiency at unity power factor.
(b) the efficiency at half full-load 0.8 power factor
leading.
4. A 600 kVA, 1-phase transformer has an efficiency
of 92% both at full-load and half-load at unity
power factor. Determine its efficiency at 60% of
full-load at 0.8 power factor lagging.
5. A12 kVA, 1,000/100 V, 50 Hz, single-phase transformer has the
following test results:
OC test (LV side): 100 V, 0.7 A, 85 W
SC test (HV side): 60 V, 10 A, 95 W
Determine the following:
(a) Core loss of the transformer.
(b) Equivalent resistance and leakage reactance referred to HV side.
(c) Equivalent resistance and leakage reactance referred to LV side.
(d) Regulation of the transformer at full load and half load at 0.8
power factor lagging.
(e) Transformer terminal voltage at full load at 0.8 power factor
lagging.
(f) Efficiency of the transformer at full load and half load at 0.8
power factor lagging.