BEF 23803 - Polyphase Circuit Analysis - Lecture 2
BEF 23803 - Polyphase Circuit Analysis - Lecture 2
BALANCED THREE-PHASE
SYSTEMS
INTRODUCTION
Industrial loads are supplied with the three-phase system; the line
voltage is generally 400 V (so that the single-phase supply is
approximately 230 V). Several methods of connection are possible:
1. Three-Phase Four wire
2. Three phase Three wire
3. Balanced Delta
Three-phase four wire star-connected balanced loads
Notes
1. We can make the assumption with a balanced load that what is
happening in each phase does not affect what is happening in
any other phase.
2. We can also say that whatever happens in phase A will occur in B
phase 120o later and again in C phase 240o later, assuming a
positive phase sequence.
Three-phase four wire star-connected balanced loads
Notes
3. The last condition that is taken is that there is no resistance in the
connecting conductors (including the neutral conductor). This
means that the two neutral points or star points are at the same
potential.
Calculations of currents in star-connected balanced
loads
We will now consider what the current values are in Figure 2.
If we consider each phase in isolation for the calculation of each
current, the result is as follows:
V AN
IA
ZA
E0 o
Z o
E
o
Z
Calculations of currents in star-connected balanced
loads
V BN
IB
ZB
E 120 o
Z o
E
120 o o
Z
VCN
IC
ZC
E 240 o
Z o
E
240 o o
Z
Calculations of currents in star-connected balanced
loads
Now, if we add, I A I B I C the resultant should flow in the neutral
conductor since all three phases are flowing to the neutral point of
the load.
I A I B IC I N 0
I A I B I C I N
E E E
I A I B IC o 120 o o 240 o o 0
Z Z Z
I ph I L
Notes
1. IA, IB and IC form a balanced set of phasors of equal magnitude
and at 120o spacing since the angle of is the same for each.
2. The resultant must be zero.
3. The condition of balanced currents can only exist for equal
impedances in the load.
4. The current in each phase is the same current in the line
supplying it so that the line currents are equal to the phase
currents.
Example
V AN E AN 0 o 2400 o o
IA 24 30
ZA Z A o 1030o
24120 o 30 o 2490 o
Solution
I A I B I C I N
Phasor diagram
POWER FACTOR
• The power factor in a three-phase system must have the same
meaning as the power factor in a single-phase system.
• It must be the cosine of the angle which the current lags or leads
the voltage which causes that current.
• Because of the number of voltages both phase to neutral and
phase-to-phase in a three-phase circuit we must be careful that
we use the correct voltage with the current for which we are trying
to find the power factor. In all cases we use the phase voltage
and the respective phase to determine the angle.
POWER FACTOR
Notes
1. The power factor of any load can be determined by the
impedance angle of the load.
2. A positive impedance angle indicates an inductive load so the
power factor must be laggging.
One-line equivalent circuits for star-connected balanced
loads
• For a star-connected balanced load all the currents can be
obtained by considering each phase separately.
• Since each current was equal in magnitude and only varied in
angles, if we are given one current and the phase sequence, we
can calculate the other two currents.
Example
Solution
V AN E AN 0 o 2400 o o
IA 24 30
ZA Z A o 1030o
Solution
VBN E 120o
VCN E 120o
3000 o
V AN 1730 o V
3
V AN 1730 o o
IA o
9.6 20 A
Z 18 20
VCN 173120o o
IC o
9.6140 A
Z 18 20
Effect of phase reversal on star load currents
All the examples given earlier have been using the positive sequence
of ABC. We will now consider the effect on a three-phase four wire
star-connected load with a negative phase sequence of CBA.
Example
VBN 240120 o
IB VBN = 240120o
Z 1030 o
2490 o A
VCN = 240-120o
24 120 o - 30 o
24 150 o A
IB and IC are in the reverse positions which is consistent with the voltage
VBN and VCN being in the reverse positions.
The conclusion is that reversing the phase sequence on a balanced
star-connected load does not alter the magnitudes of the currents, only
the currents appear in the same order as the voltage sequence (see
figure).
Calculation of power in star-connected balanced loads
The figure shows a wattmeter is connected in one leg of the star load
to measure the power in that leg.
Ptotal
Pph
3
Then the wattmeter uses IA the line current, which
is equal to the phase current and VAN the phase-to-
neutral voltage.
Calculation of power in star-connected balanced loads
1
Since V ph V phaseto phase
3
Vline
or V ph
3
Then
Vline
Pph I line cos Z
3
Calculation of power in star-connected balanced loads
Ptotal 3Pph
Then
1
Ptotal 3 Vline I line cos z
3
or
Ptotal 3 Vline I line cos z W
where
The most significant difference with voltages for the balanced delta
load is that there no neutral point, so that there are only phase-to-
phase voltages. Each voltage is across one leg of the delta but it is
also across two other legs in parallel with the first leg. For example,
VAB is across ZAB which is in parallel with ZCA and ZBC.
Calculation of currents in delta-connected balanced loads
When we consider the delta-connected load, there is a
significant difference to the star-connected load. In the star-
connected load the line currents and the phase currents were
equal to as they were the same currents.
We now compare the star case with the delta by looking at the
following figure.
Calculation of currents in delta-connected balanced loads
Consider first the supply voltages which cause currents to flow
through the impedances.
Consider VAB which causes current IAB to flow where
VAB
IAB amperes
ZAB
VCA
ICA amperes
ZCA
These phase current also form a balanced set of phasors as they did
in the star connection. They have equal magnitudes and are out of
phase with each other by 120o.
Calculation of currents in delta-connected balanced loads
The line currents are obtained by using Kirchhoff’s current laws at
each node of the delta.
At Node A:
I A I AB I CA
At Node B:
I B I BC I AB
At Node C:
I C I CA I BC
Calculation of currents in delta-connected balanced loads
We have said that as this is also a balanced load as in the
connection considered, then
I A I B IC 0
Then
I A I B I C I AB I CA I BC I AB I CA I BC 0
I AB I amperes