0% found this document useful (0 votes)
32 views

BEF 23803 - Polyphase Circuit Analysis - Lecture 2

1. The document discusses balanced three-phase systems with balanced loads that have the same impedance in each phase. 2. Industrial loads are often supplied using three-phase systems with either a three-wire or four-wire configuration. 3. For a star-connected balanced load, the current in each phase has the same magnitude and is 120 degrees out of phase. The neutral current is the sum of the three phase currents.

Uploaded by

James Liew
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views

BEF 23803 - Polyphase Circuit Analysis - Lecture 2

1. The document discusses balanced three-phase systems with balanced loads that have the same impedance in each phase. 2. Industrial loads are often supplied using three-phase systems with either a three-wire or four-wire configuration. 3. For a star-connected balanced load, the current in each phase has the same magnitude and is 120 degrees out of phase. The neutral current is the sum of the three phase currents.

Uploaded by

James Liew
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 46

Lecture 2

BALANCED THREE-PHASE
SYSTEMS
INTRODUCTION

In the following discussion we are only going to consider three-phase


systems with balanced loads.
These are loads which have the same impedances in each phase.
They may be resistive or a combination of resistance and inductance
or capacitance. The only essential feature is that the same
impedance exists in each phase.
INDUSTRIAL LOADS

Industrial loads are supplied with the three-phase system; the line
voltage is generally 400 V (so that the single-phase supply is
approximately 230 V). Several methods of connection are possible:
1. Three-Phase Four wire
2. Three phase Three wire
3. Balanced Delta
Three-phase four wire star-connected balanced loads

This is a star connected system in which the neutral makes the


fourth wire, as shown in Figure x.
Three-phase four wire star-connected balanced loads

Notes
1. We can make the assumption with a balanced load that what is
happening in each phase does not affect what is happening in
any other phase.
2. We can also say that whatever happens in phase A will occur in B
phase 120o later and again in C phase 240o later, assuming a
positive phase sequence.
Three-phase four wire star-connected balanced loads

Notes
3. The last condition that is taken is that there is no resistance in the
connecting conductors (including the neutral conductor). This
means that the two neutral points or star points are at the same
potential.
Calculations of currents in star-connected balanced
loads
We will now consider what the current values are in Figure 2.
If we consider each phase in isolation for the calculation of each
current, the result is as follows:

V AN
IA 
ZA
E0 o

Z  o
E
   o
Z
Calculations of currents in star-connected balanced
loads
V BN
IB 
ZB
E  120 o

Z  o
E
   120 o   o
Z

VCN
IC 
ZC
E  240 o

Z o
E
   240 o   o
Z
Calculations of currents in star-connected balanced
loads
Now, if we add, I A  I B  I C the resultant should flow in the neutral
conductor since all three phases are flowing to the neutral point of
the load.

I A  I B  IC  I N  0

I A  I B  I C  I N

E E E
I A  I B  IC     o   120 o   o   240 o   o  0
Z Z Z

This is indicated in the finicular diagram in Figure x.


Voltage- Current Relationships in star-connected
balanced loads
The voltage and current relationships for the balanced star-
connected load are
VL
V ph 
3

I ph  I L
Notes
1. IA, IB and IC form a balanced set of phasors of equal magnitude
and at 120o spacing since the angle of  is the same for each.
2. The resultant must be zero.
3. The condition of balanced currents can only exist for equal
impedances in the load.
4. The current in each phase is the same current in the line
supplying it so that the line currents are equal to the phase
currents.
Example

A four-wire three-phase supply is connected to a balanced three-


phase load, the connections being three phases plus a neutral
conductor.
If VAN = 240 0o and ZA = 1030o and the phase sequence is ABC,
find IA, IB and IC and IN (the current in the neutral).
Solution

V AN E AN 0 o 2400 o o
IA     24  30
ZA Z A  o 1030o

VBN E BN   120 o 240  120 o


IB   
ZB Z B  o 1030 o

 24  120 o  30 o  24  150 o

VCN ECN   120 o 240  120 o


IC   
ZC Z C  o 1030 o

 24120 o  30 o  2490 o
Solution

I A  I B  I C  I N

24  30 o  24  150 o  2450 o   I N

20.78  j12   20.78  j12  j 24  0   I N

Phasor diagram
POWER FACTOR
• The power factor in a three-phase system must have the same
meaning as the power factor in a single-phase system.
• It must be the cosine of the angle which the current lags or leads
the voltage which causes that current.
• Because of the number of voltages both phase to neutral and
phase-to-phase in a three-phase circuit we must be careful that
we use the correct voltage with the current for which we are trying
to find the power factor. In all cases we use the phase voltage
and the respective phase to determine the angle.
POWER FACTOR
Notes
1. The power factor of any load can be determined by the
impedance angle of the load.
2. A positive impedance angle indicates an inductive load so the
power factor must be laggging.
One-line equivalent circuits for star-connected balanced
loads
• For a star-connected balanced load all the currents can be
obtained by considering each phase separately.
• Since each current was equal in magnitude and only varied in
angles, if we are given one current and the phase sequence, we
can calculate the other two currents.
Example

Consider the previous example as a one-line equivalent circuit.

Solution

V AN E AN 0 o 2400 o o
IA     24  30
ZA Z A  o 1030o
Solution

Since the phase sequence is positive then

VBN  E  120o

VCN  E  120o

then the currents

I B  24  120o  30o  24  150o

I C  24120o  30o  2490o


Three-phase Three wire star-connected balanced loads

If the load connected to the four-wire star connected system is


balanced and the supply voltages and currents are symmetrical, then
the current in the neutral wire is zero, and the neutral wire may be
omitted. The resulting connection is the three-wire system as shown
in the figure below.
Example

A 300 V three-phase three-wire star-connected load has an


impedance of 18-20  in each phase. Find the line currents and
draw the phasor diagram. The phase sequence is ABC.
Solution

We must use phase-to-neutral voltages.


The 300 volts given is the phase-to-phase value.

3000 o
V AN   1730 o V
3

V AN 1730 o o
IA   o
 9.6 20 A
Z 18  20

VBN 173  120o o Phasor diagram


IB   o
 9.6  100 A
Z 18  20

VCN 173120o o
IC   o
 9.6140 A
Z 18  20
Effect of phase reversal on star load currents

All the examples given earlier have been using the positive sequence
of ABC. We will now consider the effect on a three-phase four wire
star-connected load with a negative phase sequence of CBA.
Example

Consider the three-phase system below with a negative phase


sequence. The supply voltage is VAN = 240 0 volts and ZA =
1030o .
Solution
V AN 2400 o o
IA   o
 24  30 A
Z 1030

VBN 240120 o
IB   VBN = 240120o
Z 1030 o

 24120 o - 30 o VAN = 2400o

 2490 o A
VCN = 240-120o

ACB phase sequence


Solution

VCN 240  120 o


IC  
Z 1030 o

 24  120 o - 30 o

 24  150 o A

IB and IC are in the reverse positions which is consistent with the voltage
VBN and VCN being in the reverse positions.
The conclusion is that reversing the phase sequence on a balanced
star-connected load does not alter the magnitudes of the currents, only
the currents appear in the same order as the voltage sequence (see
figure).
Calculation of power in star-connected balanced loads

The figure shows a wattmeter is connected in one leg of the star load
to measure the power in that leg.

Since we have assumed that the load is balanced,


then the power dissipated in ZA (called Pph) will be

Ptotal
Pph 
3
Then the wattmeter uses IA the line current, which
is equal to the phase current and VAN the phase-to-
neutral voltage.
Calculation of power in star-connected balanced loads

Then Pph  V ph I line cos Z

1
Since V ph  V phaseto  phase
3
Vline
or V ph 
3
Then
Vline
Pph  I line cos Z
3
Calculation of power in star-connected balanced loads

The total true or real power for the three-phase load

Ptotal  3Pph

Then
1
Ptotal  3  Vline I line cos z
3
or
Ptotal  3  Vline I line cos z W

where

z is the impedance angle of load in A phase. This is the angle


between the current in A phase, IA and the phase to neutral
voltage VAN.
Calculation of power in star-connected balanced loads

The total apparent power is

Stotal  3  Vline I line VA

and the total reactive power is

Qtotal  3  Vline I line sin  z VAr


THREE-PHASE DELTA-CONNECTED BALANCED LOADS
Consider the figure below.

Supply voltage phasor diagram

The most significant difference with voltages for the balanced delta
load is that there no neutral point, so that there are only phase-to-
phase voltages. Each voltage is across one leg of the delta but it is
also across two other legs in parallel with the first leg. For example,
VAB is across ZAB which is in parallel with ZCA and ZBC.
Calculation of currents in delta-connected balanced loads
When we consider the delta-connected load, there is a
significant difference to the star-connected load. In the star-
connected load the line currents and the phase currents were
equal to as they were the same currents.
We now compare the star case with the delta by looking at the
following figure.
Calculation of currents in delta-connected balanced loads
Consider first the supply voltages which cause currents to flow
through the impedances.
Consider VAB which causes current IAB to flow where

VAB
IAB amperes
ZAB

Now consider VCA which causes ICA to flow where

VCA
ICA amperes
ZCA

These phase current also form a balanced set of phasors as they did
in the star connection. They have equal magnitudes and are out of
phase with each other by 120o.
Calculation of currents in delta-connected balanced loads
The line currents are obtained by using Kirchhoff’s current laws at
each node of the delta.
At Node A:

I A  I AB  I CA
At Node B:

I B  I BC  I AB

At Node C:

I C  I CA  I BC
Calculation of currents in delta-connected balanced loads
We have said that as this is also a balanced load as in the
connection considered, then

I A  I B  IC  0
Then
I A  I B  I C  I AB  I CA  I BC  I AB  I CA  I BC  0

To find the relationship between IA and IAB, that is the relationship


between the line current and the phase current in a delta load,
consider the following.
If we let

I AB  I amperes

then in the ABC sequence


I BC  I   120o amperes and I CA  I   120o amperes
Solution

Let the voltage VAN be the reference phasor.


Solution
Solution
Solution
Solution
Solution
Exercises

You might also like