Field Bus
Field Bus
课程目的
2
1. Introduction
1. 1 What’s Fieldbus
Fieldbus is a digital, two-way, multidrop communication link among
intelligent measurement and control devices. This communication
method replaces the conventional standard communication, i.e., 4 to
20mA analog communication. The following eight types of definitions
are made in the IEC Fieldbus Communication Standard:
• Current IEC TS 61158
• FOUNDATION fieldbus
• FOUNDATION fieldbus High Speed Ethernet
• PROFIBUS
• Control Net
• P-Net
• Swift Net
• World FIP
• Interbus
• Profi Net
CENTUM CS 1000/CS 3000 support the FOUNDATION fieldbus and
PROFIBUS-DP communication standards.
3
1. Introduction
1.2 Features of Fieldbus
Fieldbus has the following features:
• Because multiple devices can be connected, and multivariables can
be transmitted on a single cable, thus reducing the number of cables,
wiring costs are reduced.
• A digital transmission protocol ensures accurate information
processing and hence strict quality control.
• Multiplex communications allow other information as well as PV and
MV to be transmitted from field devices.
• Communication between field devices allows truly distributed control.
• Interoperability enables devices from different manufacturers to be
combined.
• A broad choice of devices from any manufacturer permits flexible
system construction.
• Some adjustments and inspections of field devices can be performed
from the control room.
4
1. Introduction
5
1.Introduction
6
1.Introduction
Type of Fieldbus Cables and Transmissible Length
7
1.Introduction
8
1.Introduction
1.4.1 Tree or Chicken Foot Topology
A tree topology is used when several related instrument
s are physically located close to each other. A Fieldbus
junction box is located close to the instruments with sp
urs extending from it to each instrument. An example o
f a tree topology is shown in the figure below.
To ALF111 Junction
JB Box
Card
Trunk Spur
Tree
Topology
9
1.Introduction
To ALF111 JB JB JB JB
Card
Trunk
Spur
Bus or Spur
Topology
10
1.Introduction
Trunk Spur
Spur
Combination
Topology
11
1.Introduction
1.4.4 Daisy-Chain Topology
Daisy-Chain Topology is chained from device to device.
• Important to ensure that a device may be
disconnected without other devices also being
disconnected
• Daisy chain is NOT recommended.
12
2. Engineering
This section describes the procedures followed in configuring the Fieldbus dev
ices in the Centum CS3000 system
• Basic Device: A Basic Device is any device not having the capability to co
ntrol communications on an H1 Fieldbus segment.
13
2. Engineering
Link Active Scheduler (LAS): A Link Active Scheduler (LAS) is a determi
nistic, centralized bus scheduler that maintains a list of transmission times f
or all data buffers in all devices that need to be cyclically transmitted. Only
one Link Master (LM) device on an H1 Fieldbus Link can be functioning as t
hat link's LAS.
Link Master (LM): A Link Master (LM) is any device containing Link Activ
e Scheduler (LAS) functionality that can control communications on an H1 F
ieldbus Link. There must be at least one LM on an H1 Link; one of those L
M devices will be elected to serve as LAS.
14
2. Engineering
Segment: A Segment is a section of an H1 Fieldbus that is terminated in
its characteristic impedance. Segments can be linked by Repeaters to for
m a longer H1 Fieldbus. Each Segment can include up to 32 H1 devices.
15
2. Engineering
Difference between Offline initial Download, Offline Master
data Download, online Download, Upload
16
2. Engineering
2.2 System Builder
The following configuration tools are provided in the CS3000 system in the Fieldb
us system configuration.
• System View – This builder defines the basic structure of Field Control Stations
(FCS) and Input/Output Modules (IOM). I/O nodes and ALF111 cards are defined
in this builder.
• Control Drawing Builder – This builder defines the function blocks and FF facepl
ate blocks of the FCS.
17
2. Engineering
2.3 Configuration Work Flow
Start
Operation in
Creation of ALF111
System View
Registration of Operation in
Device Fieldbus Builder
Creation of FF
Faceplate Blocks
Operation in
Control Drawing
Connections and Builder
Detailed Definition
Download
End
18
2. Engineering
2.4 Typical CS3000 Fieldbus System Configuration
A typical configuration of the Fieldbus system implementation in Y
okogawa Centum CS3000 is shown below.
HIS EWS PRM
VNET/IP
NETWORK
FCS
FCU
ESBbus
Local Node
Fieldbus
Terminator
H1 Fieldbus
FF Power
Supply
FF Marshalling Cabinet
Fieldbus
Terminator
H1 Fieldbus
FF Power
Supply
FF Marshalling Cabinet
19
2. Engineering
20
2. Engineering
2.5 Integrated Engineering Function
The Centum CS3000 System View provides integrated engineering and co
nfiguration environment for the Fieldbus control loops. A Fieldbus control
loop is configured in the CS3000 Control Drawing Builder using FF facepla
te blocks (or shadow blocks). The FF faceplate block is part of the FCS fu
nction blocks library that represents a Fieldbus function block in a device.
21
2. Engineering
The figures below shows typical e
xamples of a Fieldbus control loop
s configured in the CS3000 Contr
ol Drawing Builder.
22
3. FF Loop Check Procedure
23
3. FF Loop Check Procedure
24
3. FF Loop Check Procedure
25
3. FF Loop Check Procedure
• Double click device in device panel, call the device information
window, make sure all item is match except “Device ID” and “Software
Revision”, if any item not match, it will be highlight with yellow colour.
26
3. FF Loop Check Procedure
• if “Manufac_ID” , “DEV_TYPE” , DEV_REV” or “Block structure” not m
atch, confirm with EPC, if device in field is correct, revise FF device info
rmation in DCS to match actual device. Back to FF builder, and execut
e update DD_ file as below, choose correct “Manufac_ID”, “DEV_TYPE”
etc.
27
3. FF Loop Check Procedure
28
3. FF Loop Check Procedure
• After confirm every thing match between DCS and FF device, back to
FF build and execute initial download
29
3. FF Loop Check Procedure
• Confirm on FF Faceplate Block that the download has been successful.
Check the faceplate display for CNF, O/S, IOP or OOP indication. The
alarm status of O/S, IOP and OOP are less important, because this alarm
may occur depending on the process condition or wrong XD_SCALE. It
is important to remove the CNF alarm. Because when the FF Faceplate
Block detects an abnormality in the communication with the FFB, it
notifies process alarm CNF.
30
3. FF Loop Check Procedure
3.2 FF Loop Check
There are many kind of Loop Check methods that can be considered.
Whatever, the difference between method for Loop Check, the
purpose is confirmation of loop connectivity.
Whatever the kind of the check method will be applied by EPC, the
following items should be confirmed on DCS Standard Function Block.
31
3. FF Loop Check Procedure
32
3. FF Loop Check Procedure
33
3. FF Loop Check Procedure
34
3. FF Loop Check Procedure
35
3. FF Loop Check Procedure
36
3. FF Loop Check Procedure
3). Type of no setting (e.g. Endress Houser Level Flex)
Change the “ENABLE_DISABLE” of “SIMULATE” parameter in FB to
“Active “
Change the “SIMULATE_VALUE” parameter in FB to any value.
Confirm the DCS value is the same with value set in above.
Confirm the display value of FF device (if available).
Change back the “ENABLE_DISABLE” of “SIMULATE” parameter in
FB to “Disable “
37
3. FF Loop Check Procedure
38
3. FF Loop Check Procedure
39
3. FF Loop Check Procedure
3.2.4 Valve Positioner
This method can be applied to valve positioner (connected to the
valve with air supply). Give output from DCS and confirm at field the
actual valve position and valve movement direction.
1). Give output to 0% from DCS and confirm valve fully close.
2). Give output to 50% from DCS and confirm valve opening is 50%
and valve movement direction.
3). Give output to 100% from DCS and confirm valve fully open and
valve movement direction.
4). Give output to 0% from DCS and confirm valve fully close.
40
4. Trouble Shooting
4.1 Trouble Shooting
The Loop Check has many factors involved that make the trouble
shooting became complicated.
The most important thing to do trouble shooting, is to separate
whether the issue DCS portion or Local portion (FF Device).
41
4. Trouble Shooting
Q2: Even the spur cable is disconnected, the Alarm (CNF) is not
generate
A2: Confirm as follows:
• Reconnecting the spur cable to FF Device again, and confirm whether
FF Tools is able to access any block parameters or not. If yes the issue
will be the DCS direction side.
• If the other alarm of FF Device is generated when the spur cable is
disconnected, location of FF Device is wrong, or cables connection is
wrong, or Device Tag and Node Address are mismatch. Ask to EPC for
identify the cause.
• Check the Control Drawing Builder settings, “Bad Connection Alarm”
should be “YES”.
42
4. Trouble Shooting
Q3: For Temperature Element, even the signal cable is disconnected
for TC or shorted for RTD, the Alarm (IOP) is not generated.
43
4. Trouble Shooting
44
4. Trouble Shooting
45
4. Trouble Shooting
Q6: Valve is not working properly as the given DCS output
A6: Confirm as follows;
• Whether the air has been already supplied or not.
• Confirm the “ACT_FAIL_ACTION” parameter of TB whether set
correctly or wrong.
• AFC (Air Fail to Close) Valve : Self-closing
• AFO (Air Fail to Open) Valve : Self-opening
Confirm that the “IO_OPTS” settings for “Increase to close” is
“DISABLE”
46
4. Trouble Shooting
47
4. Trouble Shooting
4.2 Some Example
4.2.1 MICRO MOTION Transmitters (Model 2700)
The Micro Motion Model 2700 transmitter measures mass flow, volume
flow, density and temperature. In addition, the Model 2700 measures
corrected volume flow, concentration and other enhanced density
variables.
48
4. Trouble Shooting
This device has an extra power supply, Commission team need confirm
power on before DCS config it, Otherwise this device can’t be find from
device panel.
After initial download, the FF block status will change from CNF to IOP,
open FF I/O builder, change the channel for AI_01 to “Mass Flow”, default
is “None”.
49
4. Trouble Shooting
50
4. Trouble Shooting
FF-AO block will stay in OOP IMAN status after initial download; it will b
ack to normal until air supply. This FF device has a PID control block; If
we used FF-PID control block, we need confirm Bypass parameter in PI
D_01 is choose “off” as following. Default is “Uninitialized”.
51
4. Trouble Shooting
52
4. Trouble Shooting
After initial download, FF-IS (DCS block) will back to normal, but in the
remote display will show “Invalid”, check the parameter BLK_TYPE_1 a
nd PARAM_INDEX_1 in Transduce_T01-01, and select the parameter a
s below.
53
4. Trouble Shooting
54
4. Trouble Shooting
55