Generator Protection by ALSTOM
Generator Protection by ALSTOM
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Generator Protection
Generator Protection - P 2
Generator Protection
1. Direct :
2. Via Transformer :
Generator Protection - P 4
Generator Protection Requirements
− Urgent
− Non-urgent
− Alarm
Generator Protection - P 5
Generator Faults
Faults include :-
• Insulation Failure
− Stator
− Rotor
• Excitation system failure
• Prime mover / governor failure
• Bearing Failure
• Excessive vibration
• Low steam pressure
• etc.
Generator Protection - P 6
System Conditions
• Short circuits
• Overloads
• Loss of load
• Unbalanced load
• Loss of synchronism
Generator Protection - P 7
Generator Failure
Generator Protection - P 8
Generator Failure
Generator Protection - P 9
Generator Failure
Generator Protection - P 10
Generator Failure
Generator Protection - P 11
Stator Earth Fault Protection
Generator Protection - P 12
Method of Earthing
Generator Protection - P 13
Method of Earthing
Generator Protection - P 14
Method of Earthing
IF ~ 10 15 A
IF ~ 200 300 A
Generator Protection - P 15
Method of Earthing
− limits damage
− reduces possibility of developing into phase - phase fault
Generator Protection - P 16
Method of Earthing :
Limitation of Earth Fault Current
Generator Protection - P 17
Method of Earthing :
Limitation of Earth Fault Current
• Most popular.
Generator Protection - P 18
Stator Earth Fault Protection
51N
50N 51N
Unearthed Generators : Other generators connected in parallel
will generally be unearthed.
Generator Protection - P 19
Percentage Winding Protected
11.5kV; 75,000KVA
xV
xV
ΙF
250/1A IS R For operation
ΙS(PRIMARY) ΙF
xV
R
R 33 x.6600
x.200
33
1
ΙS(SECONDAR Y) x.200 x 0.8x
250
Generator Protection - P 20
Stator Earth Fault Protection
Generators connected via step-up transformer (resistance earthed) :
51N 50N
System earth faults ARE not seen by generator earth fault protection
instantaneous relay may be used.
Set to 10% of resistor rating (avoids operation due to transient surges passed
through generator transformer interwinding capacitance).
Advantage : Fast
Generator Protection - P 21
Stator Earth Fault Protection
Generator Protection - P 22
Restricted Earth Fault Protection
RSTAB
64
Generator Protection - P 23
Connections for Biased REF
2000/1 ?
500/1 ?
P342/3 Relay
Terminal
CT
Inputs
z
E/F CT
Input
=I +I +I +k.I 2 Operate
A B C N
2
eK
op
Sl
1
Restrain
• High sensitivity (5%)
K1
• Unit Protection
0 1 2 3 4
• FAST
Effective bias (x In) = Max. phase current + k . I
N
2
Generator Protection - P 25
Neutral Displacement / Residual
Overvoltage - Earth Fault Protection
1
2
3 P340
Relay
Generator Protection - P 27
100% Stator Earth Fault Protection (27TN)
1
2
3 P340
Relay
Generator Protection - P 30
Overcurrent Protection
51
Generator Protection - P 31
Overcurrent Protection
51
Generator Protection - P 32
Differential Protection
Relay
Generator Protection - P 34
Differential Protection - Biased
BIAS BIAS
OPERATE
Generator Protection - P 35
Differential Protection
INTERPOSING
C.T.
Overall Differential Scheme
Generator Protection - P 36
Interturn Protection (50DT)
IA2
IB2
IC2
Generator Protection - P 37
Neutral Displacement / Residual
Overvoltage - Interturn Protection (59N)
1
2
3 Gen
Relay
Generator Protection - P 38
Prime Mover Failure
Isolated Generators :
Machine slows down and stops. Other protection initiates shut down.
Parallel Sets :
System supplies power - generator operates as a motor.
Seriousness depends on type of drive.
Generator Protection - P 39
Prime Mover Failure
Generator Protection - P 40
Prime Mover Failure
Generator Protection - P 41
Reverse Power
Operational limits
Q
an a tu r a l = 0 .1 6 o
as ta b le = 0 .5 o
-P= P0
U n sta b le a re a U n sta b le a re a
Trip a re a
Generator Protection - P 42
Low Forward Power
Operational limits
Trip a re a
U n sta b le a re a
Exte n d e d Trip a re a
P
a s ta b le = 0 . 5 o
P= P0
0 Q
Trip a re a
Effects
Single Generator :
− Loses output volts and therefore load.
Parallel Generators :
− Operate as induction generator (> synch speed)
− Flux provided by reactive stator current drawn from system-leading pf
− Slip frequency current induced in rotor - abnormal
heating
Situation does not require immediate tripping,
however,
large machines have short thermal time constants - should be unloaded
in a few seconds.
Generator Protection - P 44
Loss of Excitation
Load Impedance
R
Impedance Offset – Prevents
Locus operation
on pole slips
Diameter
Typically : Relay Characteristic
Offset 50-75%X’d
Diameter 50-100% XS Time Delayed
Generator Protection - P 45
Pole Slipping
Sudden changes or shocks in an electrical power system
may lead to power system oscillations - regular variations
of I and V and angular system separation
In a recoverable situation these oscillations will die away -
a power swing
In an unrecoverable situation the oscillations become so
severe that synchronisation between the generator and the
power system is lost - out of step/pole slipping
Causes
− Transient system faults
− Failure of the generator governor
− Failure of the generators excitation control
− Reconnection of an islanded system without
synchronisation
− Switching transients on a weak system
Generator Protection - P 47
Pole slipping
Recoverable
Out-of-Step
Power Swing (Power System)
Unrecoverable
Loss of Synchronism
Pole-Slipping
(Generator)
Generator Protection - P 48
Theory of pole slipping
Where:
EG represents the generator terminal voltage;
ZG represents the generator reactance;
ZT is the reactance of step-up transform;
Zs represents the impedance of the power system connected to the generation unit
Es represents the system voltage.
Generator Protection - P 49
Loss of synchronisation Characteristics
X S
EG/ES>1
EG/ES=1
G EG/ES<1
Generator Protection - P 51
Conventional Pole Slipping Protection
Blinder
X
ZA
Reactance Line Zone 2 ZC
Zone 1
a
q R
Lens
ZB
Generator Protection - P 53
Pole Slipping Protection - 78
Generator Protection - P 54
Pole Slipping Protection - 78
Generator Protection - P 55
State Transition Diagram
(R ese t_ T im e r T im e O ut)
A ctio ns are the sa m e a s S ta te M a ch in e E n try
S ta te M achine E n try R eset Trip_ S ignals;
N o S ign a l C o n d itio n* R eset S tart_ S ig nals;
R eset F la g_Z o ne 1;
A ctio ns are the sam e as
R eset A ll C ounte rs;
S tate M achin e E n try
R ese t A ll T im ers;
V T S -F A S T -B LO C K
Actio ns a re the sa m e as Zm = R1 or R3
State M achine E n try
Zm = R 4
IF (M ode_B oth)
ID LE Flag_ M o d e= !F lag _M od e;
Zm = R1 .
R eset S tart_ S ignals;
R eset F la g_Z on e1 ; Zm = R2
IF (Any T rip_S ign al) S tart T im e r1
R eset C o u nte rs;
R eset T rip _S igna ls; Zm = R1 or R4
R eset T im e r1
Z m = R 3 b ut T im er1< T 1
R eset T im er1
Zm = R1 or R2
R ese t F lag _Z on e1; Zm = R 2
Z m = R 4 bu t Tim e r2 < T 2 R ese t T im e r2 ;
R e se t F lag _Z one 1;
Zm = R 4 or R2 or R3 DETECTED R ese t T im er2 ; START
*N o S ig na l C o nd itio n
(V A <1 V o r I <0.0 2 A )
Zm = R3
Generator Protection - P 56
RTDS Pole Slip Simulation
Local Load
132 kV BUS
T/line 140 km 11 kV BUS
132/13.5 kV
Yd1
Grid System Generator with
AVR and Governor control
Generator Protection - P 57
Pole Slipping - 80% Load, Local 3 ph fault
Generator Protection - P 58
Loss of excitation at 100% machine loading
Generator Protection - P 59
Rotor Thermal
Protection
Generator Protection - P 60
Unbalanced Loading
Generator Protection - P 61
Unbalanced Loading
Generator Protection - P 62
Overload Protection
Governor Setting
Generator Protection - P 63
Stator Thermal Protection
Current operated
− Over power protection
− Overcurrent element
− Thermal replica
Generator Protection - P 64
Overload Protection (1)
Time
Current
Generator Protection - P 65
Rotor Earth Fault Protection
Generator Protection - P 66
Rotor Earth Fault Protection
Potentiometer Method
Exciter
AC Injection Method
AC Auxiliary
Supply
• Brushless Machines R
Brushless Machine
A brushless generator has an excitation system consisting of:
− A main excitor with rotating armature and stationary field windings
− A rotating rectifier assembly, carried on the main shaft line out
− A controlled rectifier producing the d.c. field voltage for the main
exciter field from the a.c. source (often a small `pilot` exciter)
Hence:
− No brushes are required in the field circuit
− All control is carried out in the field circuit of the main exciter
− Detection of rotor circuit earth fault is still necessary
− Based on dedicated rotor-mounted system that has a telemetry link
to provide an alarm/data
Generator Protection - P 69
Generator Back-Up Protection
Overcurrent Protection
Typical use :
− Very or extremely inverse for LV machines
− Normal inverse for HV machines
with AVR
Full
Load
no AVR
Cycles
Generator Protection - P 70
Generator Back-Up Protection
Overcurrent Protection
Voltage Restrained
• Operating characteristic is continuously varied depending on measured
volts.
• Alternatively, use impedance relay.
Voltage Controlled
• Relay switches between fault characteristic and load characteristic
depending on measured volts.
Generator Protection - P 71
Generator Back-Up Protection (2)
10
O/L CHARAC
1.0
FAULT CHARAC
LARGEST
OUTGOING 6.6kV
t
sec FEEDER 5MVA
115% XS
0.1 GENERATOR
DECREMENT 500/5
CURVE 200/5
0.01
100 240 600 1000 3000 10,000 AMPS
Generator Protection - P 72
Voltage Dependent Overcurrent
Protection (51V)
I> I>
Load Load
Fault Fault
k.I> k.I>
Generator Protection - P 73
Impedance Relay
Load
Fault
R
Underimpedance
• 2 Zones of protection
− Zone 1 - Set to operate at 70% rated load impedance. Back-up
protection for generator-transformer, busbar and outgoing feeders.
Time delayed for co-ordination with external feeder phase fault
protection.
− Zone 2 – Set to 50% transformer impedance. Back-up protection for
generator phase faults. Faster time delay to co-ordinate with
generator phase fault protection
Generator Protection - P 74
Under & Over Frequency Conditions
Over Frequency
Generator Protection - P 75
Under & Over Frequency Conditions
Under Frequency
Generator Protection - P 77
Under & Over Voltage Conditions
Protection
Generator Protection - P 78
Under & Over Voltage Conditions
Over Voltage
• Results from generator over speed caused by sudden loss of
load.
• May be due to failure of the voltage regulator.
• An over voltage condition :
− Causes overfluxing at nominal frequency
− Endangers integrity of insulation
Under Voltage
• No danger to generator. May cause stalling of motors.
• Prolonged under voltage indicates abnormal conditions.
Generator Protection - P 79
Generator Abnormal Frequency Protection (81AB)
Generator Protection - P 80
Generator Abnormal Frequency Protection (81AB)
Band 1
f nom
Band 2
Band 3
Band 4
Timer 1
Timer 2
Timer 3
Timer 4
Generator Protection - P 81
Application
Negative Sequence Overvoltage (47)
CB Generator/Motor
a b
b a
c c
Block
CB Close
Generator/Motor
47 Negative Sequence Overvoltage
1 2 3 4
When the units pump water the protection
applied will change Four groups
available
Generator Protection - P 83
Phase Rotation
P340
CT1 CT2
G x
Phase
Reversal
Switches
P343/4/5
Generator Protection - P 84
Phase Rotation
Generator Protection - P 85
Unintentional Energisation at Standstill
50
27 & Trip
tPU
&
tDO
VTS
• Overcurrent element detects breaker flashover or starting
current (as motor)
• Three phase undervoltage detection
• VTS function checks no VT anomalies
Generator Protection - P 86
Check Synch (25)
Generator Protection - P 87
Check Synchronising (25)
Generator Protection - P 88
Check Synchronising (25)
Generator Protection - P 89
Check Synch (25)
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Protection Package for Diesel Generator
87
G 32 Reverse Power
64R Rotor Earth Fault
64S Stator Earth Fault
51V Voltage Dependent Overcurrent
64
R 87G Generator Differential
32 51
V Protection P343
64
R
Generator Protection - P 93
Overall Protection of Generator Installation
Generator
Feeder Protn.
Overcurrent
Voltage Restraint 51 V
Restricted
E/F
Buchholz Winding
Temp.
Reverse Power 32
Field Failure 40
Generator Differential 87
Rotor E/F Prime Mover Protection
64R
Negative Phase Sequence 46
Overall
Gen/Trans Diffl
Protn. Stator E/F 64S
Generator Protection - P 94
Overall Protection of Generator Installation
Generator Feeder
Protection
O/C Circuit Breaker Fail
Busbar Protection
Restricted
E/F
Buchholz Winding
Temperature
O/C + E/F
Buchholz O/C V.T.s
Transformer
Overfluxing
Generator Protection - P 95
Embedded Generation
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
Co-generation/Embedded Machines
AR?
PES
system
81U/O Frequency
50/51N O/C & E/F
27/59 Voltage
Residual Voltage 47/46 NPS Voltage Islanded load
59N
NPS O/C fed unearthed
df/dt ROCOF 25 Check Synch
dV Voltage Vector Shift
Generator Protection - P 97
Embedded Generation
USED TO PROVIDE:
Generator Protection - P 98
Engineering Recommendation G59
• ER G59 COVERS:
− Safety Aspects
− Legal Requirements
− Operation
− Protection
Generator Protection - P 99
Engineering Recommendation G59
− Protection tripping
FAULT
− Accidentally due to
SECTIONALISING
network reconfiguration
SWITCH
400V DG
STABILITY
Network faults
SENSITIVITY
Generator/demand Imbalance
Generator Protection - P 104
Existing Loss of Mains Methods
• Passive Methods
− Under/over frequency and voltage
• Requires large change in load, time delayed
− Df/dt – rate of change of frequency
• Sensitive, fast operating
− Voltage vector shift
• Not as sensitive as df/dt, fast operating
− Direct inter-tripping
• Not load dependent, fast, expensive, signalling can be complex
• Active Methods
− Active frequency drift
− Reactive Error export
• There is an abundance of active methods proposed in the technical literature,
however, their application in practice has been limited to date. The
traditional protection philosophy of independence from other systems makes
the introduction of these methods difficult.
IL
E VT
IL X
VT ILR
IL
E
ILX
VT
ILR
IL VT
ILX”
IL
df/dt
The rate of change of speed, or frequency, following a power disturbance
can be approximated by:
P.f
df/dt =
2GH
df/dt = F n - f n - 3 cycle
3 cycle
Two consecutive calculations must give a result above the setting
threshold before a trip decision can be initiated
t
Start
Pick up cycles
Trip
f
Time delay
df/dt Setting
Generator Protection - P 112
G59 Other Protection
• Neutral voltage
• Overcurrent
• Earth fault
• Phase unbalance
• Reverse power
− Used when generator does not export power during normal
operation
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.