Electricalsystemsinabuilding 150911082119 Lva1 App6892
Electricalsystemsinabuilding 150911082119 Lva1 App6892
Electricalsystemsinabuilding 150911082119 Lva1 App6892
Introduction
• Since the end of the nineteenth century virtually all buildings are
provided with electric lightings installation for use at night. With
the advent of fluorescent lamp that is compatible with daylight,
cheap to run and not emitting heat gain in buildings, it made possible
to install electric lighting supplementing day light and in extreme
cases provide the only source of light in a windowless environment.
• Several factors can exercise a critical influence on the success of
lighting installations apart from proper level of illumination on the
work plane.
Introduction
Introduction
• The first use of electric supply were established in 1882 by
Thomas Edison, Thereafter there have been constant effort
throughout the world to set-up power stations for more than one
purposes.
• The power generation in India in 1947-48 was only 4.1 billion and
today we generate more than 600 billion kw.
Electricity Generation
Entry in the buildings
• In Urban areas electrical cables are Usually underground and are brought
up to entry point at ground level or into basement service cable cannot
be bent to small radiee and this should be borne in mind when considering
point of entry.
• In small buildings the cable run is kept as short as possible, terminating
in a distribution board at the first convenient position. In these buildings
the distribution board will be fitted with a seal box to prevent moisture
from entering the insulation of the service cable, a main fuse for the
premises in a box sealed by the supply authority and the consumer unit
or other switch and fuse gear belonging to the building.
• The position chosen for the distribution board should be readily accessible
both for meter reading and for replacing fuses. In some cases special
glasses are provided so that meter can be read without entering the
premises.
Entry in the buildings
Domestic Supply
• Domestic electricity supply usually effected through distribution system
and describe as single and three phases. Normally small buildings are
supplied with electricity by two wires, one phase wire and the other neutral.
This is known as single phase supply and gives a voltage for the
premises of 240 volts. The loading of the supply wiring is balanced
between the phases by using the phases in rotation so that each one services
every third building.
• In three phases, four wire bring 420/ 240 volts, 50 cycle per second. The
voltage. The voltage between any two of the phases wires is 415 Volts.
And between any phase wire and the neutral is 240 volts. The balancing of
load is then achieved by serving different areas of the building by different
phases. Electric motor are usually designed for three phase operation.
Single and Three Phases Distribution
Earthing System
• In electricity supply systems, an earthing system or
grounding system is circuitry which connects parts of
the electric circuit with the ground, thus defining the
electric potential of the conductors relative to the
Earth's conductive surface
Earthing System
• Regulations for earthing system vary considerably among countries
and among different parts of electric systems. Most low voltage
systems connect one supply conductor to the earth (ground).
• People use an earthing system mainly for these applications:
• To protect a structure from lightning strike, directing the lightning
through the earthing system and into the ground rod rather than
passing through the structure.
• Part of the safety system of mains electricity, preventing problems
associated with floating ground and sky voltage.
• The most common ground plane for large monopole antenna and some
other kinds of radio antenna.
Applications Of Earthing
Class II protection –
beside of the basic insulation, addition layer of insulation apply to the
enclosure. Therefore no extraneous conductive part. The additional
layer is independent to the basic insulation so that under failure of
basic insulation, it offers additional protection
Two classes of protection
Types of Earthing
• Supply System – Neutral Earth
• System Earth
• Electrical Safety Earth
• Lightning Earth
• Generator Earth
• Protection Earth (i.e. surge arrestor)
• Telecom / Computer Earth
• Shielding Earth
• Integrated Earthling System (Advocated)
• Electrostatic Earth (Clean Room / Hospital)
Earthling Arrangements
• TN System
• TNS System
• TN C S System
• TN C system
• TT System
• IT System
Domestic Supply
Concept of Earthing Systems
All the people living or working in residential,
commercial and industrial installations, particularly
the operators and personnel who are in close
operation and contact with electrical systems and
machineries, should essentially be protected
against possible electrification. To achieve this
protection, earthing system of an installation is
defined, designed and installed according to the
standard requirements..
What Is Earthing
The process of connecting metallic bodies
of all the electrical apparatus and equipment
to huge mass of earth by a wire having
negligible resistance is called Earthing.
What Is Earthing
The term earthing means connecting the neutral point of supply system or the non current
carrying parts of the electrical apparatus to the general mass of earth in such a manner that all
times an immediate discharge of electrical energy takes place without danger.
• Provide an alternative path for the fault current
to flow so that it will not endanger the user
• Ensure that all exposed conductive parts do not
reach a dangerous potential
• Maintain the voltage at any part of an electrical
system at a known value so as to prevent over
current or excessive voltage on the appliances
or equipment.
Good Earthing Means
Good Earthing must have low impedance
enough to ensure that sufficient current can
flow through the safety device so that it
disconnects the supply ( <0.4 sec ). Fault
current is much more than the full load
current of the circuit which melts the fuse.
Hence, the appliance is disconnected
automatically from the supply mains.
Qualities Of Good Earthing
• Must be of low electrical resistance
• Must be of good corrosion resistance
• Must be able to dissipate high fault
current repeatedly
Purpose of Earthing
• To save human life from danger of electrical shock or death by
blowing a fuse i.e. To provide an alternative path for the fault
current to flow so that it will not endanger the user
• To protect buildings, machinery & appliances under fault
conditions ie. To ensure that all exposed conductive parts
do not reach a dangerous potential.
• To provide safe path to dissipate lightning and short
circuit currents.
• To provide stable platform for operation of
sensitive electronic equipments i.e. To maintain the
voltage at any part of an electrical system at a known value
so as to prevent over current or excessive voltage on the
appliances or equipment .
• To provide protection against static electricity from
friction
Electric shock
• An electric shock (electrocution)occurs when two portion of
a person’s body come in contact with electrical conductors of
a circuit which is at different potentials, thus producing a
potential difference across the body.
• The human body does have resistance and when the body
is connected between two conductors at different potential
a circuit is formed through the body and current will flow
• When the human body comes in contact with only one
conductor, a circuit is not formed and nothing happens.
When the human body comes in contact with circuit
conductors, no matter what the voltage is there is potential
for harm.
Electric shock
• The higher the potential difference the more
the damage. The effect of an electric shock is
a function of what parts of body come in
contact with each conductor, the resistance of
each contact point the surface resistance of
the body at the contact as well as other factor.
• When the electrical contact is such that the
circuit path through the body is across the
heart, you have the greatest potential for
death.
Electric shock
• As shown in fig the human body’s resistance varies
from as low as 500 ohms to as high as 600,000
ohms. As the skin become moist the contact
resistance drop. If the skin is moist due to sweat that
contain salt the resistance drop further
• Fig 1 illustrates the amount of current that can flow
through human body at three different potential
differences across the body also shown is the effect of
different current level both AC and DC the ultimate
effect is fibrillation which cause the heart to stop and
result in death.
Electric shock
• When a high voltage such as 13,800V is
involved the body is literally cooked and
at times explodes
Short circuit
• To analyze how an electrical shock occurs and how
grounding is applied you need to look at the
circuit involved.
• Fig 2 illustrates the basic circuit that consist of a
source, a transformer or generator for all AC circuits,
circuit protection, conductors(R1s), and a load (RL).
Short circuit
• A short circuit is any unintended connection Rsc across
the circuit conductors between the power source and the
load
• See the second circuit in fig short circuit are classified as
bolted shorts, momentary shorts,intermittent shorts, or high
impedance shorts. A bolted short which is rare is a very
low resistant connection such as two conductors being
bolted together.
Short circuit
• Most shorts are high resistant or they are
momentary or intermittent. The high resistant
short starts out as a high resistance or
impedance connection but usually progress
to a low impedance connection.
• In electrical system shorts are classified as
phase to phase, phase to neutral , or phase
to ground short.
Short circuit
• Most short are phase to ground and short which start as phase
to phase or phase to neutral progress to a phase to ground
short
• When considering short circuit and protecting against the
damage they can cause one needs to know what is the
maximum amount of short circuit current that can flow in
a given circuit.
Equipment Earthing
• In case of insulation failure, the primary
object of connecting all the above points and
apparatus to earth is to release the charge
accumulated on them immediately to earth so
that the person coming in contact may not
experience electric shock.
Equipment Earthing(Cont.)
• The other object is that a heavy current when flows through the circuit
that operates the protective devices that is fuse or CB, which open the
circuit
Max. Value of Earth Resistance to
be achieved
Equipment to be Earthed Max. Value of Earth Resistance to be
achieved in Ohms
Large Power Stations 0.5
Major Substations 1.0
Small Substations 2.0
Factories Substations 1.0
Lattice Steel Tower 3.0
Industrial Machine and Equipment 0.5
* The Earth Resistance depends upon the moisture content in the soil.
Methods of Earthing
• Conventional Earthing
• Maintenance Free Earthing
Conventional Earthing
• The Conventional system of Earthing calls for
digging of a large pit into which a GI pipe or
a copper plate is positioned in the middle
layers of charcoal and salt.
• It requires maintenance and pouring of
water at regular interval.
FIGURE:.
CONVENTIONAL EARTHING
Maintenance Free Earthing
• It is a new type of earthing system which is
Readymade, standardized and scientifically
developed. Its Benefits are
• MAINTENANCE FREE: No need to pour water at
regular interval- except in sandy soil.
• CONSISTENCY: Maintain stable and consistent earth
resistance around the year.
• MORE SURFACE AREA: The conductive compound
creates a conductive zone, which provides the
increased surface area for peak current dissipation.
And also get stable reference point.
Maintenance Free Earthing(Contd.)
• Design Details :
1. Earthing Pit : Size 1000 X 1000 X 1800 mm
Depth.M.S. / C.I. Plate : 500 X 500 X 8 mm
Thick.
2. Electrode Assembly : 40 mm Ø GI / CI
Perforated pipe duly fitted or welded with base
plate and 50 X 6 mm flat termination taken on
top for equipment earthing as shown in drawing.
Standard Pipe & Plate Type Earthing Design for the 11
Kv. System Equipments, Distribution Transformer
Centers, L.T. Distribution System Equipments
4. Mixture - I : Homogeneous mixture of black
soft soil 0.3 CMT. approx.
5. Mixture - II : Homogeneous mixture of
common salt 25 Kgs. + wood charcoal pieces
25 Kgs. + Black soft soil 1 CMT. Approx.
6. Crushed Rock pieces Gravel Size 50 X 35 mm
0.1 CMT. Approx.
7. Arrangement for earthing lead terminations
from equipment body, and connection for
main earthing Grid.
Typical arrangement for Pipe
electrode earthing pit (Bore Type)
• Design Details :
1. 75 mm thick RCC Cover.
2. 300 mm Ø 6000 mm deep (Approx. 20 ft.)
bore in the earth.
3. 65 mm Ø 6000 mm long (Approx 20 ft.) G.I.
pipe electrode. Forged at the top up to 75 mm
length and 12 mm hole provided for taking
earthing connection.
4. A homogeneous mixture of 50 kgs. wooden
coal pieces + 50 kgs. common salt
5. Water pouring purpose at the time of routine
maintenance
Applications
• Telecommunication
• Transmission
• Substations & Power Generations
• Transformer Neutral earthing
• Lightning Arrestor Earthing
• Equipment Body Earthing
• Water Treatment Plants
• Heavy Industries
• College, Hospitals, Banks
• Residential Building
Distribution Circuits
• In most of the buildings electricity supply is divided into two types of sub
• circuit: Lighting Load sub-circuit and power load Sub Circuit and
• finally for operation purpose into three phases circuit-lighting, socket
outlets and fixed apparatus.
• The sub circuit which gives supply to lighting load points is called lighting
• load sub circuit. This circuit includes lamps, fans, tubes etc. As per Indian
Electricity Rules. The following rating should be assumed
• Filament lamp 60 W
• Ceiling fan 60 W
• Socket for radio, table fan 60
W
• Flurecent tube 40
W
• Mercury Vapour lamp 80
Basic wiring Systems
• Types of wiring
• There is wide choice of wiring; however one must keep in mind the safety
of men & material. The various types of wiring used are discussed below
• Cleat Wiring
• In this system of wiring, V.I.R or PVC Insulated wires are held to the walls
and ceiling by means of porcelain cleats which are fixed at distance of 0.5
m horizontally and 0.75 m vertically above the walls The cleat are made on
two halves, one is known as base and the other is known as cap. The
wirings are drawn in groves and finally tightened. This wiring is cheapest
and require little skill and can be quickly installed.
Cleat Wiring
Basic wiring Systems