Spring 2008: ELEN 3441 Fundamentals of Power Engineering
Spring 2008: ELEN 3441 Fundamentals of Power Engineering
However, this approach is not very practical, since it would require to solve for
voltages and currents at all nodes along the line. We could also solve the exact
differential equations for a line but this is also not very practical for large power
systems with many lines.
Lines longer than 240 km (150 miles) are long transmission lines.
R rd (9.37.1)
X xd (9.37.2)
Y yd (9.37.3)
where r, x, and y are resistance, reactance, and shunt admittance per unit length
and d is the length of the transmission line. The values of r, x, and y can be
computed from the line geometry or found in the reference tables for the specific
transmission line.
VS VR ZI VR RI jX L I (9.38.2)
VR VS RI jX L I (9.38.3)
The ABCD constants can be physically interpreted. Constant A represents the effect
of a change in the receiving end voltage on the sending end voltage; and constant D
models the effect of a change in the receiving end current on the sending end
current. Naturally, both constants A and D are dimensionless.
The constant B represents the effect of a change in the receiving end current on the
sending end voltage. The constant C denotes the effect of a change in the receiving
end voltage on the sending end current.
Transmission lines are 2-port linear networks, and they are often represented by
ABCD models. For the short transmission line model, IS = IR = I, and the ABCD
constants are
A 1
BZ
(9.51.1)
C 0
D 1
ELEN 3441 Fundamentals of Power Engineering Spring 2008
9
Y
I ser VR I R (9.52.2)
2
ELEN 3441 Fundamentals of Power Engineering Spring 2008
10
For long lines, it is not accurate enough to approximate the shunt admittance by two
constant capacitors at either end of the line. Instead, both the shunt capacitance
and the series impedance must be treated as distributed quantities; the voltages
and currents on the line should be found by solving differential equations of the line.
However, it is possible to model a long
transmission line as a model with a
modified series impedance Z’ and a
modified shunt admittance Y’ and to
perform calculations on that model
using ABCD constants. The modified
values of series impedance and shunt
admittance are:
sinh d
Z' Z (9.54.1)
d
tanh d 2
Y 'Y (9.54.2)
d 2
ELEN 3441 Fundamentals of Power Engineering Spring 2008
12
Here Z is the series impedance of the line; Y is the shunt admittance of the line; d is
the length of the line; is the propagation constant of the line:
yz (9.55.1)
where y is the shunt admittance per kilometer and z is the series impedance per km.
As d gets small, the ratios approach 1.0 and the model becomes a medium-length
line model. The ABCD constants for a long transmission line are
Z 'Y '
A 1
2
BZ'
Z 'Y ' (9.55.2)
C Y ' 1
4
Z 'Y '
D 1
2
ELEN 3441 Fundamentals of Power Engineering Spring 2008
13
Assuming that the generator is ideal, an increase of load will increase a real and
(or) reactive power drawn from the generator and, therefore, the line current, while
the voltage and the current will be unchanged.
1) If more load is added with the same lagging power factor, the magnitude of the
line current increases but the current remains at the same angle with respect to
VR as before.
VS VR jX L I (9.41.1)
Therefore, when a lagging load increases, the received voltage decreases sharply.
In a summary:
1. If lagging (inductive) loads are added at the end of a line, the voltage at the end
of the transmission line decreases significantly – large positive VR.
2. If unity-PF (resistive) loads are added at the end of a line, the voltage at the end
of the transmission line decreases slightly – small positive VR.
3. If leading (capacitive) loads are added at the end of a line, the voltage at the end
of the transmission line increases – negative VR.
The voltage regulation of a transmission line is
Vnl V fl
VR 100% (9.42.1)
V fl
where Vnl and Vfl are the no-load and full-load voltages at the line output.
ELEN 3441 Fundamentals of Power Engineering Spring 2008
16
where VS is the magnitude of the source (input) line-to-neutral voltage and VLL,S is
the magnitude of the source (input) line-to-line voltage. Note that Y-connection is
assumed! Similarly, the real output power from the transmission line is
If the resistance R is ignored, the output power of the transmission line can be
simplified…
A simplified phasor diagram of a transmission
line indicating that IS = IR = I.
We further observe that the vertical segment
bc can be expressed as either VS sin or
XLIcos. Therefore:
VS sin
I cos (9.45.1)
XL
Then the output power of the transmission line equals to its input power:
3VSVR sin
P (9.45.2)
XL
Therefore, the power supplied by a transmission line depends on the angle between
the phasors representing the input and output voltages.
ELEN 3441 Fundamentals of Power Engineering Spring 2008
19
The maximum power supplied by the transmission line occurs when = 900:
3VSVR
Pmax (9.46.1)
XL
This maximum power is called the steady-state stability limit of the transmission line.
The real transmission lines have non-zero resistance and, therefore, overheat long
before this point. Full-load angles of 250 are more typical for real transmission lines.
Few interesting observations can be made from the power expressions:
1. The maximum power handling capability of a transmission line is a function of the
square of its voltage. For instance, if all other parameters are equal, a 220 kV
line will have 4 times the power handling capability of a 110 kV transmission line.
Therefore, it is beneficial to increase the voltage… However, very high voltages
produce very strong EM fields (interferences) and may produce a corona –
glowing of ionized air that substantially increases losses.
Pout
100% (9.47.1)
Pin
The greater the current flow, the greater the resistive heating losses.
2. The voltage drop in a practical line should be limited to approximately 5%. In other
words, the ratio of the magnitude of the receiving end voltage to the magnitude of the
sending end voltage should be
VR
0.95 (9.49.1)
VS
This limit prevents excessive voltage variations in a power system.
3. The angle in a transmission line should typically be 300 ensuring that the power
flow in the transmission line is well below the static stability limit and, therefore, the
power system can handle transients.
Any of these limits can be more or less important in different circumstances. In short
lines, where series reactance X is relatively small, the resistive heating usually limits
the power that the line can supply. In longer lines operating at lagging power factors,
the voltage drop across the line is usually the limiting factor. In longer lines operating
at leading power factors, the maximum angle can be the limiting f actor.
SOLUTIONS:
SOLUTIONS: