Lecture 5
Lecture 5
Lecture- 4
Rudra Kumar
6 March 2023
Email: [email protected]
Topic-2 Heuristics and short cut methods for process equipment design
2.1 Apply heuristic rules and short methods for the sizing of tanks and process vessels.
2.2 Apply heuristic rules and short methods for sizing engines, pipes, pumps, fans, and
compressors.
2.3 Apply heuristic rules and short methods for the sizing of heat exchangers and equipment
for heat transfer.
2.4 Apply heuristic rules and short methods for the sizing of distillation and absorption
towers.
2.5 Apply heuristic rules and short methods for the sizing of chemical reactors.
2.6 Understand the process of identifying and specifying services, particularly those related
to heating and cooling.
2.7 Know and apply the techniques of individual costing of process equipment (CAPCOST)
Heuristic: A heuristic, or heuristic technique, is any approach to problem-solving that uses a
practical method or various shortcuts in order to produce solutions that may not be optimal
but are sufficient given a limited timeframe or deadline.
VESSELS (DRUMS)
1. Drums are relatively small vessels to provide surge capacity or separation of entrained
phases.
9. Gas velocity in gas/liquid separators, V = k (ρL/ρV - 1)1/2 m/sec, with k =0.35 with mesh
deentrainer, k =0.00305 without mesh deentrainer.
10. Entrainment removal of 99% is attained with mesh pads of 4-12 in. thicknesses; 6 in.
thickness is popular.
11. For vertical pads, the value of the coefficient in Step 9 is reduced by a factor of 2/3.
13. Disengaging spaces of 6-8 in. ahead of the pad and 12 in. above the pad are suitable.
14. Cyclone separators can be designed for 95% collection of 5 μm particles, but usually only
droplets greater than 50 μm need be removed.
Solution:
a. V-102 High-Pressure Phase Separator
we use the following heuristics:
Rule 12 → Good performance obtained at 30% – 100% of u from Rule 9; typical value is
75%
From Table 1, we have
Solving for D,
Table 1:
( )
𝑢 ρ𝑉 π 𝐷 2 0.23 ×8 × 3.14 × 𝐷 2 0.5
2.56= =
2.56 × 4
4 4 𝐷= =1.33 𝑚
0.23 × 8 ×3.14
Holdup time is 5 min half full for reflux drums
From Rule 5, we have volume of liquid = 0.5 L πD2/4 = 0.5 x 3.14 x (1.33)2 L/4 = 0.726 L m3
From Table 2, we see that the actual V-102 is a vertical vessel with D = 1.1 m, L = 3.5 m.
Heuristic rules and short methods for the sizing of heat exchangers and equipment for heat
transfer.
1. Take true countercurrent flow in a shell-and-tube exchanger as a basis.
2. Standard tubes are 3/4 in. OD, 1 in. triangular spacing, 16 ft long; a shell 1 ft dia
accommodates 100 sqft; 2 ft dia, 400 sqft, 3 ft dia, 1100 sqft.
3. Tube side is for corrosive, fouling, scaling, and high pressure fluids.
5. Pressure drops are 1.5 psi for boiling and 3-9 psi for other services.
6. Minimum temperature approach is 10 °C (20°F) with normal coolants, 5°C (10°F) or less with
refrigerants.
10. Compact (plate and fin) exchangers have 1150 m2/m3 (350 sqft/cuft), and about 4 times the
heat transfer per cuft of shell-and-tube units.
11. Plate and frame exchangers are suited to high sanitation services, and are 25-40% cheaper in
stainless construction than shell-and-tube units.
12. Air coolers: Tubes are 0.75-1.00 in. OD, total finned Surface 15-20 m2/m2 (sqft/sqft bare
Surface), U = 450–570 W/m2 °C, (80-100 Btu/hr sqft bare Surface °F). Minimum approach
temperature = 22°C (40°F). Fan input power = 1.4–3.6 kW/(MJ/h) [2-5 HP/(MBtu/hr)].
13. Fired heaters: radiant rate, 37.6 kW/m2 (12,000 Btu/ hr sqft); convection rate, 12.5 kW/m2
(4000 Btu/hr ft2); cold oil tube velocity, 1.8 m/s (6 ft/sec); approx equal transfers of heat in the
two sections; thermal efficiency 70-90%; flue gas temperature 140-195 °C (250-350°F) above
feed inlet; stack gas temperature 345–510°C (650-950°F).
b. E-105 Product Cooler
From Table 1 and Figure that Rule 6 has been violated because ΔTmin = 8°C.
Log mean temperature, ΔTlm = [(105 − 40) − (38 − 30)]/ln[(105 − 40)/(38 − 30)] = 27.2°C
2. Normal pump suction head (NPSH) of a pump must be in excess of a certain number,
depending on the kind of pumps and the conditions, if damage is to be avoided. NPSH =
(pressure at the eye of the impeller- vapor pressure)/(density). Common range is 1.2–6.1 m (4-
20 ft).
4. Centrifugal pumps: Single stage for 0.057–18.9 m3/min (15-5000 gpm), 152 m (500 ft) max
head; multistage for 0.076–41.6 m3/min (20-11,000 gpm), 1675 m (5500 ft) max head.
Efficiency 45% at 100 gpm, 70% at 500 gpm, 80% at 10,000 gpm.
5. Axial pumps for 0.076–378 m3/min (20-100,000 gpm), 12 m (40 ft) head, 65-85% efficiency.
6. Rotary pumps for 0.00378–18.9 m3/min (1-5000 gpm), 15,200 m (50,000 ft) head, 50-80%
efficiency.
7. Reciprocating pumps for 0.0378–37.8 m3/min (10-10,000 gpm) , 300 km (1,000,000 ft) head
max. efficiency 70% at 7.46 kW (10 HP), 85 % at 37.3 kW (50 HP), 90 % at 373 kW (500 HP).
c. P-101
We use the following heuristics:
Rule 1: Power(kW) = (1.67)[Flow(m3/min)]ΔP(bar)/ε
4. Exit temperatures should not exceed 167–204°C (350–400 °F); for diatomic gases (C p/Cv =
1.4). This corresponds to a compression ratio of about 4.
5. Compression ratio should be about the same in each stage of a multistage unit,
ratio = (Pn/P1)1/n, with n stages.
6. Efficiencies of reciprocating compressors: 65% at compression ratios of 1.5, 75% at 2.0, and
80–85% at 3–6.
10. In-leakage of air to evacuated equipment depends on the absolute pressure, Torr, and the
volume of the equipment, V in m3 (ft3) according to W = kV2/3 kg/h (lb/hr) with k = 0.98 (0.2)
when P > 90 Torr, k = 0.39 (0.08) between 3 and 20 Torr, and k = 0.12 (0.025) at less than 1 Torr.
d. C-101
From Table 2,
we have mass flow rate = 6770 kg/h,
T1 = 38°C = 311 K,
Molecular weight, MW = 8.45,
k = 1.41 (assume)
a = (k-1)/k= 0.2908 Z1 = 1
Molar flow rate, m = (6770)/(3600 x 8.45) = 0.223 kmol/s
1. Distillation is usually the most economical method for separating liquids, superior to
extraction, absorption crystallization, or others.
2. For ideal mixtures, relative volatility is the ratio of vapor pressures α12= P1*/P2*
3. Tower operating pressure is most often determined by the temperature of the condensing
media, 38–50°C (100–120 °F) if cooling water is used, or by the maximum allowable reboiler
temperature to avoid chemical decomposition/degradation.
a. Perform the easiest separation first, that is, the one least demanding of trays and reflux, and
leave the most difficult to the last.
b. When neither relative volatility nor feed composition varies widely, remove components one
by one as overhead products.
c. When the adjacent ordered components in the feed vary widely in relative volatility,
sequence the splits in order of decreasing volatility.
d. When the concentrations in the feed vary widely but the relative volatilities do not, remove
the components in order of decreasing concentration.
5. Economical optimum reflux ratio is in the range of 1.2 to 1.5 times the minimum reflux ratio,
Rmin.
6. The economically optimum number of theoretical trays is near twice the minimum value
Nmin.
Nmin = ln{[x/(1-x)]ovhd/[x/(1-x)]btms}/ln α.
8. Minimum reflux for binary or pseudo binary mixtures is given by the following when
separation is essentially complete (xD ≈ 1) and D/F is the ratio of overhead product to feed
rate:
RminD/F = 1/(α-1), when feed is at the bubble point
9. A safety factor of 10% of the number of trays calculated by the best means is advisable.
11. The optimum value of the Kremser absorption factor A = (L/mV) is in the range of 1.25 to
2.0.
12. Reflux drums usually are horizontal, with a liquid holdup of 5 min half-full. A takeoff pot for
a second liquid phase, such as water in hydrocarbon systems, is sized for a linear velocity of
that phase of 1.3 m/s (0.5 ft/sec), minimum diameter is 0.4 m (16 in).
13. For towers about 0.9 m (3 ft) dia, add 1.2 m (4 ft) at the top for vapor disengagement, and
1.8 m (6 ft) at bottom for liquid level and reboiler return.
14. Limit the tower height to about 53 m (175 ft) max. because of wind load and foundation
considerations. An additional criterion is that L/D be less than 30 (20 < L/D < 30 often will
require special design).
Heuristics for Tray Towers (Distillation and Gas Absorption)
1. For reasons of accessibility, tray spacings are made 0.5–0.6 m (20–24 in).
2. Peak efficiency of trays is at values of the vapor factor F s = uρ0.5 in the range of 1.2–1.5 m/s
{kg/m3}0.5 [1–1.2 ft/s {lb/ft3}0.5]. This range of Fs establishes the diameter of the tower.
Roughly, linear velocities are 0.6 m/s (2 ft/sec) at moderate pressures, and 1.8 m/s (6 ft/sec) in
vacuum.
3. Pressure drop per tray is on the order of 7.6 cm (3 in) of water or 0.007 bar (0.1 psi).
4. Tray efficiencies for distillation of light hydrocarbons and aqueous solutions are 60–90%; for
gas absorption and stripping, 10–20%.
5. Sieve trays have holes 0.6–0.7 cm (0.25–0.5 in) dia., area being 10% of the active cross
section.
6. Valve trays have holes 3.8 cm (1.5 in) dia. each provided with a liftable cap, 130–150 caps/m2
(12–14 caps/ft2) of active cross section. Valve trays are usually cheaper than sieve trays.
7. Bubblecap trays are used only when a liquid level must be maintained at low turndown ratio;
they can be designed for lower pressure drop than either sieve or valve trays.
8. Weir heights are 5 cm (2 in), weir lengths are about 75% of tray diameter, liquid rate—a
maximum of 1.2 m3/min m of weir (8 gpm/in of weir); multipass arrangements are used at
higher liquid rates.
Heuristics for Packed Towers (Distillation and Gas Absorption)
1. Structured and random packings are suitable for packed towers less than 0.9 m (3 ft) when
low pressure drop is required.
2. Replacing trays with packing allows greater throughput and separation in existing tower shells.
3. For gas rates of 14.2 m3/min (500 ft3/min), use 2.5 cm (1 in) packing; for 56.6 m3/min (2000
ft3/min) or more, use 5 cm (2 in) packing.
4. Ratio of tower diameter to packing diameter should be >15:1.
5. Because of deformability, plastic packing is limited to 3–4 m (10–15 ft) and metal to 6.0–7.6 m
(20–25 ft) unsupported depth.
6. Liquid distributors are required every 5–10 tower diameters with pall rings, and at least every
6.5 m (20 ft) for other types of dumped packing.
7. Number of liquid distributors should be >32–55/m2 (3–5/ft2) in towers greater than 0.9 m (3 ft)
diameter, and more numerous in smaller columns.
8. Packed towers should operate near 70% of flooding (evaluated from Sherwood and Lobo
correlation).
9. Height equivalent to theoretical stage (HETS) for vapor-liquid contacting is 0.4–0.56 m (1.3–1.8
ft) for 2.5 cm (1 in) pall rings, and 0.76–0.9 m. (2.5–3.0 ft) for 5 cm (2 in) pall rings.
10. Generalized pressure drops Design Pressure Drops Design Pressure Drops
(cm of H2O/m of packing) (inches of H2O/ft of packing)
Rule 4: εtray = 60 – 90 %
xovhd = 0.9962, xovhd = 0.0308, αovhd = 2.44, αbot = 2.13, αgeom ave = (αovhdαbot)0.5 = 2.28