DX-AHU & BMS Integration Guide

AE Biz. Supporting Division

V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 1
■ In case of Single Circuit

⊙ In case of single circuit, connections to be done with Master in case of Master, Slave units

Provided By Contractor
Provided By LG DDC
VRF 0~10VDC Analog Signal
(Condensing Unit)
Dry Contact Control/ Monitoring points
INT A (including RAT & SAT)
INT B
IDU A
IDU B AHU components MCC Panel
power supply (Electrical)

Comm. Kit
Local purchase
Wired Remote
Controller
Local purchase

Towards AHU T Pipe In

Towards Multi V T Pipe Out


TXV Kit

Provided By Contractor
Supplied By LG.
1. DDC / BMS.
1.VRF Condensing Unit.
2. MCC Panel.
2.Y Branches for Outdoor Unit (Multiple Module).
3. Air Temperature sensor return and
3.Communication Kit.
supply.
4.Dry Contact.
4. All Communication Cable.
5.Expansion Valve.
5. All power cables.
6.Wired Remote Controller.
6. Piping
7.Tpipe / Tout sensor
6. Other which not mentioned.
V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 2
■ In case of Multiple Circuit

⊙ In case of Multiple circuits, all the units must be looped and must be connected to
only 1 dry contact
MCC Panel
(Electrical)
Control/ Monitoring points
(including RAT & SAT)
DDC
0~10VDC
Analog Signal

AHU components
INT A
power supply INT B
Dry Contact
Outdoor Unit

INT A
Group AHU Expansion Kit
INT B
Control
Comm. Kit T Pipe In
T Pipe Out

IDU A
IDU B

IDU A
IDU B

IDU A
IDU B

V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 3
■ Demand Control Dry Contact Connection Architecture

DRY CONTACT Outdoor PCB

12V
GND

DDC DC 0~10V GND

BMS Scope LG Scope

V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 4
■ Demand Control Dry Contact Connection Architecture

⊙ Set the SW_STEP switch to ‘E’

V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 5
■ Demand Control Dry Contact Connection Architecture

⊙ Voltage Range & Operation table

V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 6
■ Demand Control Dry Contact Connection Architecture

⊙ Voltage Range & Operation Graph

V-net Product Installation Copyright 2011@LG Electronics / AC Company All Rights Reserved 7