This document describes the layout and alarm systems for an open-loop exhaust gas scrubber. It includes diagrams of the scrubber system layout and main screens. It then lists the alarm points for various components, including scrubber pressure and temperature, gas monitoring probes, water quality sensors, and system failures. Thresholds and delay times are provided for alarms and automatic trips. The document also discusses troubleshooting approaches, IMO requirements, and a maintenance schedule.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
178 views21 pages
Egcs
This document describes the layout and alarm systems for an open-loop exhaust gas scrubber. It includes diagrams of the scrubber system layout and main screens. It then lists the alarm points for various components, including scrubber pressure and temperature, gas monitoring probes, water quality sensors, and system failures. Thresholds and delay times are provided for alarms and automatic trips. The document also discusses troubleshooting approaches, IMO requirements, and a maintenance schedule.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 21
U-type (Open-loop) system
Lay out Diagram of Open loop scrubber(U-
Type) System Layout Screen Layout and Main screen Exhaust Line Screen Alarm history panel Exhaust Gas Cleaning System • U-Type open-loop system
NO Alarm Set Delay time Remark
• Alarm list(Exh. Gas sytem) point 1 Scrubber Total 140 25 sec Alarm back pressure High mmAq 2 Scrubber Total 150 30 sec Trip back pressure High mmAq
3 Pre-Absorber Gas 400’C 5 sec Alarm
inlet temp high 4 Pre-Absorber Gas 400’C 10 sec Trip inlet temp high Alarm list (Exh. Gas system) NO Alarm Set point Delay time Remark 5 Absorber gas outlet temp high 55’C 5 sec Alarm 6 Absorber gas outlet temp high 60’C 10 sec Trip high 7 Drain water level high 60 sec Alarm 8 Drain water level high high 5 sec Trip 9 ME intake/by pass damper fail Trip 10 AE intake/by pass damper fail Trip 11 Scrubber v/v mis-operation Trip Alarm list(Panels) No Alarm Set point Delay time Remark
1 GPS communication fail - 5 min Alarm
2 PLC response time out - 5 sec Trip
3 Main control panel power fail - - Trip
4 Em’cy stop - - Trip
5 Control panel inside temp high 50’C Alarm
Alarm list (Gas monitoring system) No Alarm Set point Delay time Remark
1 GMS probe sensor fail - - Alarm
2 GMS hose temp sensor fail - - Alarm
3 GMS analyzer communication fail - - Alarm
4 GMS power fail - - Alarm
5 Scrubber SO2/CO2 ratio high 4.3/21.7 % 300 sec Alarm
Alarm list(Water monitoring system) No Alarm Set point Delay time Remark 1 Inlet/outlet WMS pH and temp - - Alarm sensor fail 2 Inlet/outlet WMS turbidity sensor - - Alarm fail 3 Inlet/Outlet WMS pump flow fail - - Alarm 4 Outlet WMS pH low 2.88 25 sece4x Alarm 5 Differential turbidity High 22FNU 2 sec Alarm 6 Differential turbidity High High 25 FNU 2 sec Trip 7 Outlet water PAH High - 170 sec Alarm Detail view Screen Data setting page SO2/CO2 ratio out ofcompliance Alarm on out of compliance Approach Against alarms and issues
•First follow the primary
troubleshooting way •Follow the secondary troubleshooting way to eliminate root cause Primary troubleshooting way Secondary Troubleshooting way Requirement from IMO System malfunction Maintenance Schedule for each component