CAPA Chapter 3
CAPA Chapter 3
Institute of Technology
Department of Electrical and Computer Engineering
Computer Aided Power System Analysis (CAPA)
Chapter 3 Fault Studies
By Dawit Adane
Fault Analysis
• During normal conditions, a power system operates under balanced conditions with all equipment’s
carrying normal load currents and the bus voltages are within the prescribed limits. This condition
can be disrupted due to a fault occurred in the system. A fault in a circuit is a failure that
interferes with the normal flow of current. A short circuit fault occurs when the insulation of the
system fails resulting in low impedance path either between phases or phase(s) to ground. This
causes excessively high currents to flow in the circuit, requiring the operation of protective
equipment’s to prevent damage to equipment. An open circuit fault occurs when one or two of the
circuit path breaks and interrupts the current flow in that paths. This causes the disruption of the
balanced nature of the system.
Faults in power system can be classified into two based on their balanced ness nature
1. Symmetrical(Balanced) faults
2. Unsymmetrical(Unbalanced) faults
• Majority of the faults occur on transmission lines as they are exposed to external elements.
Lightening strokes may cause line insulators to flashover, high velocity winds may cause tower
failure, ice loading and wind may result in mechanical failure of line or insulator and tree branches
may cause short circuit.
• Fault analysis is necessary for selecting proper circuit breaker rating and for relay settings and
coordination.
Symmetrical Faults:
A simultaneous short circuit across all three phases. It occurs infrequently (about 5%),
but it is the most severe type of fault encountered. Because the network is balanced, it
is solved on a per-phase basis. The other two phases carry identical currents except for
the phase shift of 120 degree.
This fault represents a structural network change equivalent with that caused by the
addition of an impedance (i.e., Zf) at the fault place. If Zf = 0 the fault is called a solid or a
bolted fault (this is usually the most severe fault that can occur in a system). These faults
can be of two types: (a) line to line to line to ground fault (LLLG fault) or (b) line to line
to line fault (LLL fault). The faulted network can be solved conveniently by the
Thevenin’s method and ZBUS impedance method.
Unsymmetrical Faults:
Faults in which the balanced state of the network is disturbed resulting unbalanced
system operation. The types of unbalanced faults are:
a) Single line to ground fault (LG Fault): - the most common type (Almost 60 to 75% of
faults in a system)
b) Line to line faults (LL faults): - about 5 to 15% of system fault
c) Double line to ground faults (LLG faults): - about 15 to 25% of system fault
d) Open Conductor (Single or Double line open)
The unsymmetrical faults are analyzed using symmetrical components.
ZBUS Formation Without Mutual Coupling Between Elements
• For a network with ‘m’ buses and a reference bus, a relation between bus currents and
bus voltages is:
Where,
IBUS is (m× 1) bus current injection vector
VBUS is (m× 1) bus voltage vector
ZBUS is m×m bus impedance matrix and is given by,
Where,
is m×1 bus voltage vector
is m×1 bus current injection vector
is m×m bus impedance matrix of the partial
network
• The four possible element additions to a partial network are:
a. Addition of a branch between a new node and the reference
b. Addition of a branch between a new node and an existing node
c. Addition of a link between an existing node and the reference
d. Addition of a link between two existing nodes
1) Addition of a branch between a new node and the reference node (case 1):
• Figure below shows the addition of a branch between a new node ‘q’ and the reference
‘0’. This increases the size of ZBUS to (m+1)×(m+1). Let the impedance of this branch
be zq0. The new network equation can be written as:
• For finding out Zqi, a current source Ii = 1 p.u. is connected between ith bus and the
reference bus with all other buses open circuited as shown in Figure below. Since V q =
0, then
2) Addition of a branch between a new node and an existing node (Case 2):
• Let a branch with impedance zpq be connected between an existing node ‘p’ and a new
node ‘q’ as shown in figure below. The size of ZBus matrix increases by one to
(m+1)×(m+1). The modified network equations can be written as:
• The original matrix ZmBus remains unchanged.
Figure: Addition of a branch between an existing node ‘p’ and a new node ‘q’
• For calculating Zqq one can write
• For current source of Iq = 1 p.u is connected to the qth bus, with all the others buses
open circuited, and the voltage of qth bus Vq is computed, as shown in figure below.
• The voltages Vp and Vq can be related as Figure: Calculation of Zqq
3) Addition of a link between an existing node and the reference node (Case 3):
• Adding an element between an existing node and the reference creates a loop and the
size of modified ZBus matrix remains unchanged. However, all the elements are
modified.
• Let the added element, with an impedance of z qo, be connected between an existing
node ‘q’ and the reference node ‘0’ as shown in the Figure below.
Figure: Addition of a link between an existing node ‘q’ and the reference
The current Iℓ flowing through the link modifies the current injected into q th bus from Iq to
Iq − Iℓ. The modified network equations can be written as,
also,
Substituting Vq, results,
or
Together with the above equations, the modified network equations can be expressed as:
where,
From the above equation, one can write
or
Substituting Iℓ results,
Hence,
Where,
4) Addition of a link between two existing nodes (Case 4):
Let an element with impedance zpq be connected between two existing nodes ‘p’ and ‘q’
and the current Iℓ flowing through the link changes the injected current at p th node from Ip
to (Ip − Iℓ), while at node qth from Iq to (Iq + Iℓ) as shown in figure below.
Figure: Addition of a link between two existing nodes ‘p’ and ‘q’
The modified network equations can be written as:
And
or
Where,
;
;
For eliminating the link current Iℓ, the above partitioned matrix can be written in compact
form as:
Where,
Hence,
Where,
Example–1
Modify the bus impedance matrix of a 4-bus power system as shown in the figure below
to account for the connection of a capacitor having a reactance of 5.0 per unit between bus
4 and the reference node of the circuit of the figure below.
YBUS =
The terms in the fifth row and column were obtained by repeating the fourth row and
column of Zorig with negative sign added and note that to obtain the value of element in the
fifth row and column as follow:
Zℓℓ = Zqq + zq0 = Z44 + z40 = j0.69890 – j5.0 = – j4.30110
Then, by eliminating the fifth row and column, we obtain for Z bus(new) as:
…
Exercise – 1
Modify the Zbus determined in above for the circuit of the above Figure by adding a new
node connected to bus 3 through an impedance of j0.5 per unit.
Exercise – 2
Modify the Zbus determined in above by adding a link of impedance j0.2 per unit between
buses 1 and 4 of the circuit of the above Figure.
Answer for Exercise–1
Recognizing the system is modified by adding a branch of inductive reactance of j0.5 per
unit element from the existing bus (node) of p = 3 to the new node q = 5 and Z orig = Zbus is
the 4 X 4 matrix;
zpq = z35 = j0.5 per unit
To find the modified network equation as per rule 2:
Z1q = Z15 = Z1p = Z13 = j0.53340; Z2q = Z25 = Z2p = Z23 = j0.64008; Z3q = Z35 = Z3p =
Z33 = j0.71660; Z4q = Z45 = Z4p = Z43 = j0.66951;
Zq1 = Z51 = Zp1 = Z31 = j0.53340; Zq2 = Z52 = Zp2 = Z32 = j0.64008; Zq1 = Z51 = Zp1 =
Z31 = j0.71660; Zq1 = Z51 = Zp1 = Z31 = j0.66951;
Zqq = Z55 = Zpq + zpq = Z35 + z35 = j0.71660 + j0.5 = j1.21660
Answer for Exercise–2
Recognizing the system is modified by adding a link of inductive reactance of j0.2 per
unit element between the existing bus (node) of p = 1 and the existing bus (node) q = 4
and Zorig = Zbus is the 4 X 4 matrix;
zpq = z14 = j0.2 per unit
To find the modified network equation as per rule 4:
to yield Zbus(new) as
Symmetrical or Balanced three phase fault analysis:
– Balanced 3-ϕ fault can be solved using Thevenin’s equivalent network as seen from the
fault point. The bus impedance matrix is convenient to use for fault studies as its
diagonal elements are the Thevenin’s impedance of the network as seen from different
buses.
– The generators are represented by a constant voltage source behind a suitable reactance
which may be sub-transient, transient or normal d-axis reactance. The transmission lines
are represented by their π-models with all impedances referred to a common base.
– A balanced three phase fault, through a fault
impedance Zf is assumed to occur at kth
bus of the n-bus power system network
as shown in the figure below. A pre-fault
load flow provides the information about
the pre-fault bus voltage.
Zi and Zk are the equivalent load impedances at bus i and k respectively, Z ik is the impedance of
line between ith and kth buses. xdi is the appropriate generator reactance, Z f is the fault
impedance, Ik(F) is the fault current and Vk(0) is the prefault voltage at kth bus.
From the superposition theorem, the bus voltages due to a fault can be obtained as the sum
of prefault bus voltages and the change in bus voltages due to fault, i.e.,
Where,
[VBUS(F)] = Vector of bus voltages during fault = [V1(F) . . . Vi(F) . . . Vn(F)]T
[VBUS(0)] = Vector of pre-fault bus voltages = [V1(0) . . . Vi(0) . . . Vn(0)]T
[∆VBUS] = Vector of change in bus voltages due to fault = [∆V1 … ∆Vk ... ∆Vn]T
The bus injected current [IBUS] can be expressed as,
With all the bus currents, except of the faulted bus k, equal to zero, the node equation for
the network can be written as
As the fault current Ik(F) is leaving the bus it is
taken as a negative current entering the bus.
Hence,
[∆VBUS] can be calculated as:
We also know,
Zkk is the Thevenin’s impedance or open circuit impedance of the network as seen from
the faulted bus k.
For a bolted fault Zf = 0 and hence, Vk(F) = 0. Thus the fault current Ik(F) for bolted fault
can be expressed as
For faulty with non-zero fault impedance Zf, the fault current can be calculated as:
The bus voltage after fault for the unfaulty or healthy buses can be written as:
The fault current Iij(F) flowing in the line connecting ith & jth bus can be calculated as:
Except for round-off errors, the sum of these current contributions equals I2(F).
Example–2: Power System Analysis – Hadi Saadat – Page 367
Unsymmetrical or Unbalanced Fault Analysis:
• Unbalanced system operation can result.
• Analysis can be carried out on a three phase basis using symmetrical components
where the three-phase voltages (and currents) which is unbalanced are transformed
into three sets of balanced voltages (and currents) called symmetrical components.
• A transformation of various power system elements (synchronous generators,
transformers and lines) impedances to symmetrical components are decoupled from
each other resulting in independent system networks for each component (balanced
set).
Symmetrical Components
• Any unbalanced set of three phase voltage or current phasors can be replaced by three
balanced sets of three phase voltage or current phasors. These three balanced set of
voltage or current phasors are called symmetrical components of voltages or currents.
• A set of three balanced voltages(phasors) Va, Vb, Vc is characterized by equal
magnitude and interphase differences of 120o.
• A set is said to have a phase sequence abc (positive sequence) if V b lags Va by 120o and
Vc lags Vb by 120o. The three voltage phasors can be expressed in terms of the
reference phasor Va as:
Va = |Va|, Vb = a2|Va| and Vc = a|Va|
• If the phase sequence is acb (negative sequence), then
Va = |Va|, Vb = a|Va| and Vc = a2|Va|
• Where the complex number operator, a, is defined as:
Where,
• By expanding
• Similarly, for current
• where, is the set of phase voltages, and is the set of sequence voltages.
Symmetrical Y and ∆ Circuits
Relationships between the symmetrical components of Y and ∆ currents and voltages can
be established by referring to Figure below, which shows symmetrical impedances
connected in Y and ∆. Let us agree that the reference phase for ∆ quantities is branch a-b.
• Adding all the above three equations together, results zero-sequence line current as:
• Note: Assuming zero value of circulating current Iab0 exists in the ∆ circuit.
• From symmetrical component relation, Ica1 = aIab1 and Ica2 = a2Iab2, we have:
• Adding together all the above three equations, results zero-sequence line voltage as:
• If the voltages to neutral are in per unit referred to the base voltage to neutral and the
line voltages are in per unit referred to the base voltage from line to line, the √3
multipliers must be omitted from the above equations. If both voltages are referred to
the same base, however, the equations are correct as given. Similar analogy works for
line ∆ currents.
• when there are no sources or mutual coupling inside the ∆ circuit:
By substitution,
So that,
• This shows that the ∆-connected impedances is three times the per phase or Y-
connected impedances when both are expressed in ohms or in per unit on the same
kilovolt-ampere and voltage bases.
Power Invariance
The sum of powers of the three symmetrical components equals to the three-phase power.
Total complex power in a three-phase circuit is given by
• If there is impedance in the neutral connection to ground, then the voltages V a, Vb and
Vc must be interpreted as voltages from the line to ground rather than to neutral.
Now,
Therefore,
Sequence Networks and Sequence Impedances of Power System
Sequence Networks of a loaded Synchronous Generator:
• A three-phase synchronous generator, having a synchronous impedance of Z s per
phase, with its neutral grounded through an impedance Z n is shown in Figure below.
The generator is supplying a balanced three phase load. The generator induced
voltages Ea, Eb and Ec are balanced and hence treated as positive sequence set of
voltage phasors and can be expressed as:
And,
Substituting the neutral current, and writing the resulting equation in matrix form, we get:
Where,
is the vector of terminal phase voltages.
is the vector of terminal phase currents.
is the impedance matrix.
Replacing the phase quantities of the above equations by corresponding sequence
quantities, using the transformation equation results,
Pre-multiplying both sides of the above equation by [A] -1 and after simplifications one
gets:
Where,
is Generator Sequence Impedance Matrix and is defined as:
It is evident that the three sequence components are independent of each other. The current
of a particular sequence produces a voltage drop of that sequence only, hence the three
sequences are decoupled from each other. The three sequence networks of a synchronous
generator are shown in Figure below.
Sequence networks of a transmission line:
A fully transposed three-phase line is completely symmetrical and therefore the per phase
impedance offered by it is independent of the phase sequence of a balanced set of currents.
Therefore, for a static device such as a transmission line, the phase sequence of voltages
and currents have no effect on the impedance offered by the line as both positive and
negative phase sequences encounter identical line geometry. Hence, the positive and
negative sequence impedances offered by a line are identical i.e. Z 1 = Z2.
The sequence networks for zero sequence depends on the winding connections and
whether or not the neutrals are grounded. Before considering the zero sequence networks
of various types of transformer connections, three important observations are made:
Figure: The flow of zero sequence currents in a star connection
Figure: The zero-sequence equivalent circuit of a Star-Star transformer with both neutrals
grounded
(b) Star-Star connections with only one neutral grounded:
When the neutral of only one winding is grounded, the phase currents of the ungrounded winding
must add up to zero. This implies that the zero sequence currents cannot exist in the ungrounded
winding and hence the zero sequence currents cannot exist even in the transformer side with
neutral grounded.
Figure: The zero-sequence equivalent circuit of a Star-Star transformer with only one
neutral grounded
(c) Star-Star connections with only no neutral grounded:
The zero sequence currents can not exist on any winding in this case also.
Since all sequence currents are equal and the sum of sequence voltages equal 3Z fIa1, a
series connection of sequence networks through an impedance 3Z f results as shown in
figure below.
Substituting for Va0, Va1, and Va2 and noting Ia0 = Ia1 = Ia2, we get
2. Line-To-Line Fault
Figure below shows a three phase generator with a fault through an impedance Z f between
phases b and c. Assuming the generator is on no-load, the boundary conditions at the fault
point are:
By substituting, the symmetrical components of currents are
From the above equation, we find that
We note that
We have
Substituting for Va1 = Ea – Z1Ia1 and Va2 = – Z2Ia2 and noting Ia2 = –Ia1, we get
Thus,
&
The symmetrical components of voltages under fault condition are
For Ia2
Since Ia1 = -(Ia0 + Ia2) and substituting for Ia0 and Ia2, solving for Ia1;
• Where Z0kk, Z1kk, and Z2kk are the diagonal elements in the k-axis of the corresponding
bus impedance matrix of sequence network and Vk(0) is the pre-fault voltage at bus k.
• The fault phase currents are:
The fault current is:
Where , , and are the zero-, positive-, and negative-sequence components of the actual
line impedance between buses i and j.
The phase fault current in line i to j is:
Example–5
Using the bus impedance matrix formation technique, and are found for positive
sequence network and zero sequence network of corresponding Figures in
Example-4.
If the bus currents are changed to a new value, [I0 + ΔI], the new bus voltage [V] can be
expressed as:
where, [ΔV] represents the change in the values of the original bus voltage [V0].
Figure below represents a power system with buses i and j taken out along with the
reference node. The circuit is not energized so that [V0] and [I0] are zero. Currents [ΔIi]
and [ΔIj] are injected into the ith and jth buses respectively, through current sources
connected between the node and the reference node.
The changes in bus voltage [ΔV] can be calculated as:
The modified voltage at ith bus can be written as:
Calculate the voltage difference ΔVij between ith and jth buses as:
The opening of all the three phases is equivalent to the removal of the line i → j totally
from the network. If zij(0), zij(1) and zij(2) are the the three sequence impedance of the line i
→ j, then the removal of this line from the network can be simulated by adding −z ij(0),
−zij(1) and −zij(2) to the corresponding Thevenin’s equivalent network of the three sequence
networks of the original network as seen from ith and jth buses.
Let x represents the fractional length of the broken line i → j from ith bus to the break point
‘k’, where 0 ≤ x ≤ 1.
Figure below illustrates The positive sequence impedance of the conductor segment
between the ith bus and the point of break k is xZij(1), and the positive sequence impedance of
the remaining conductor from point k to j th bus is (1 − x)Zij(1). These two impedances are
then added to represent the broken conductor.
If Vkk’(a), Vkk’(b) and Vkk’(c) represent the phase component of voltage drops between points k
and k’, then Vkk’(0), Vkk’(1) and Vkk’(2) represent the sequence components of the voltage drops
between points k and k’.
Figure below shows simplification of the circuit by replacing a current source V kk’(1)/Zij(1)
and a parallel impedance Zij(1) from the voltage Vkk’(1) and the total series impedance [xZij(1)
+ (1 −x)Zij(1)] = Zij(1).
The sequence voltage drops Vn(0), Vn(1) and Vn(2) at any bus ‘n’ due to the current injections
at the buses ‘i’ and ‘j’ can be calculates as:
The positive sequence equivalent impedance Z kk’(1) as seen from the buses k and k’ is
found out as:
Similarly, the negative sequence and zero sequence Thevenin’s equivalent impedances can
be expressed as:
Also prior to the occurrence of open-conductor fault on any conductor, the current I ij(1)
flowing in phase a is the positive sequence component and is given by:
The Thevenin’s equivalent network as seen from points k and k’ for the three sequence
networks are shown in figure below.
There are two types of open-circuit fault, i.e.,
a) One phase/conductor open
b) Two phases/conductors open
One Conductor Open
Consider that phase a conductor is open, hence phase a current Ia = 0. As a result:
where, Ia(1), Ia(2) and Ia(0) are the symmetrical components of phase a current. Since phases b
and c are closed, the voltage drops,
The symmetrical components of voltage drop across the fault point can be calculated as:
Hence,
It implies that open conductor in phase a causes equal voltages to appear across points k
and k’ of each sequence network. Hence, the three equivalent sequence networks can be
connected in parallel across points k and k’ as shown in Figure below.
Figure: Connection of Equivalent
sequence networks to
represent open conductor
a between k and k’
Simplifying results;
The sequence voltage drops Vkk’(1), Vkk’(2) and Vkk’(0) can be calculated as:
Remaining calculations are similar to those performed for single conductor open case.