Transformer Energisation

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 14

TRANSFORMER

INRUSH CURRENT
BY: GYANESHWAR KUMAR
CONTENTS
Some Pre-requisites
Transformer Inrush current/Transformer Energization
What causes it?
What affects it?
What it affects?
Sympathetic Inrush
Mitigation Measures
Conclusion
Bibliography
TRANSFORMER BASICS
Ep

Ip

Iw
Io

Im øm

Is

Es
Transformer Magnetism
Some useful equations :

m =BmA
H= Magnetising force = Magnetising
current (Im) x number of runs
WHAT IS TRANSFORMER INRUSH
CURRENT
 A transient phenomenon which leads to increase in current when a transformer is switched
on/energized.
It typically has a value of 4-40 times the nominal current.
It typically lasts for few cycles (4 to 16) cycles depending on the circuit time constant.
It is rich in 2nd and 3rd order harmonics.
PEAKY MAGNETISING CURRENT
Expected magnetising current
Ep

Ip

Iw
Io

Im øm

Is

Es
TRANSFORMER INRUSH CURRENT
At t=0+

Switch
MAXIMUM INRUSH CASE
FACTORS AFFECTING INRUSH
CURRENT
1. Switching on angle
• Inrush current decreases when switching-on angle (on the voltage wave) increases. It is maximum for α=0° and minimum
for α=90°.
• If a transformer is switched exactly at an instant of a voltage wave which corresponds to the actual flux density in the
core at that instant, there would be no transient.

2. Residual flux density


• Inrush current is significantly aggravated by residual flux density, which depends upon core material characteristics and
the power factor of the load at interruption when a transformer was switched off.
• No-load, lagging PF load and unity Power factor load at the time of interruption will result in maximum value of residual
flux density. Leading load at the time of interruption results in lower value of residual flux density.
• Residual flux density also depends on the core material.

3. Series Resistance
• Due to the damping effect, series resistance between the transformer and source not only reduces the maximum initial
inrush current but also hastens its decay rate.

4. Inrush under load


• If a transformer is switched on with load, the inrush peaks are affected to some extent by the load power factor.
• Higher secondary current at unity power factor reduces the peak inrush current.
SYMPATHETIC INRUSH
Transformer already energized.

Resistance

Transformer being energized.

• The DC component of inrush current of the transformer being energized flows through the transmission line
resistance (between source and transformer) producing a DC voltage drop across it.

• The DC voltage drop forces the already energized transformer towards/into saturation in opposite direction of the
transformer which is being switched on, resulting in a build-up of magnetizing current in the already energized
transformer.

• The rate of build-up is same as the rate at which DC component of magnetizing current is decreasing in the
transformer being switched on.
SYMPATHETIC INRUSH
Transformer already energized.

Resistance

Transformer being energized.

• When the two parallel transformers are similar and magnitudes of DC components of currents in both the
transformers become equal, there is no DC component in the line feeding both the transformers.

• However, there is a DC component circulating in the loop circuit between them, whose rate of decay is very slow
due to high inductance and small resistance of windings of the two transformers.
MITIGATION OF INRUSH CURRENT
1. Closing Resistors
• The rated voltage is applied through a large resistor so that the voltage at the transformer terminals is
lower than the rated value.
• The resistor is subsequently by-passed to apply full voltage to the transformer.
2. Controlled Closing methods
• Each winding is closed when the prospective and dynamic (transient) core fluxes are equal resulting in an
optimal energization without core saturation or inrush transients.
3. Harmonic restraint to avoid unnecessary relay operation.
CONCLUSION
• Inrush currents are generally less than the peak short circuit current.
• Since the transformers are designed to withstand mechanical effects of short circuit forces, inrush currents
may not be considered to be dangerous.
• However, they may unnecessarily cause operation of protective equipment like relays and fuses.
• Hence, proper relay coordination and mitigation measures, as required, shall be implemented.
BIBLIOGRAPHY
1. Transformer Engineering _ Design and Practice - S.V Kulkarni.
2. Practical Experience in Setting Transformer Differential Inrush Restraint – Rich Hunt & GE
Multilin.
3. Various internet sources and IEEE Papers.

You might also like