4-Testing Differential Protection
4-Testing Differential Protection
(87)
Motaz Al-Fayomi
Senior Protection Engineer
00962795159787
[email protected]
A- Differential Protection (87) Application
B- Negative Sequence Current Fault Discriminator
C- Charging Current
D- Open CT detection feature
E- 2nd and 5th harmonic analysis
F- Analog signal transfer for line differential protection
A-Differential Protection (87) Application
The ratio of operate coil and restraint coil is 20%
)0.2 , 0.2 * 100 =20%=)10A/50A((= )Iop/Ires(
The pickup setting of this relay is 25% so the restraint coil is applying more force than
the operate coil and the relay will NOT TRIP
Idiff
Unrestrained
Limit
Sum
I Bias
Idiff, A
?P2 )1.9 ,4.0(
0%
=8
-3
op
Sl
?P1
= 40% (
-2 3. 0
Slop-1=0.0% Slo
p
1. 1,
)
Idiff min=0.4
)0.4 ,1.25(
`
Slop -2 =40%=(P1-0.4)/(3.0-1.25)P1=40%(3.0-1.25)+0.4=1.1A
Slop -3 =80%=(P2-1.1)/(4.0-3.00)P2=80%(4.0-3.00)+1.1=1.9A
Main menu/Test/Function status/Differential protection/
LineDifferential6Terminal(PDIF,87L)/L6CPDIF:x
B-Negative Sequence Current Fault Discriminator
The open CT circuit condition creates unexpected operations for Line differential-1
.protection under the normal load conditions
The search for an open CT starts after 60 seconds (50 seconds in 60 Hz systems)-3
since the bias current enters the 10–110% range
E-2nd and 5th harmonic analysis
The excitation current cause high degree of fifth harmonic, if the transformer is inside-2
.the protected zone
If we have internal fault at the same time as the harmonic content is above set level-3
and the differential current is below IdMinHigh, will block a trip
NOMESS : No start and stop flags identified for the incoming message
REMGPSER : Remote terminal indicates problem with GPS synchronization SUBSTITU Link
error, values are substituted
LOWLEVEL : Low signal level on the receive link
! Thank you