Multiple Loops
Multiple Loops
Feedforwar
Cascade Ratio Split-Range Selective
d Plus
Control Control Control Control
Feedback
Feedforward Plus Feedback
•It is difficult to account for every possible
load disturbance in a feedforward system
•Feedforward systems are often combined
with feedback systems.
•Controllers with summing functions are
used in these combined systems to total
the input from both the feedforward loop
and the feedback loop, and send a unified
signal to the final control element.
• The figure shows a feedforward-plus-
feedback loop in which both a flow
transmitter and a temperature transmitter
provide information for controlling a hot
steam valve.
Cascade
•Cascade control is a control
system in which a secondary
(slave) control loop is set up to
control a variable that is a major
source of load disturbance for
another primary (master) control
loop.
•The controller of the primary
loop determines the setpoint of
the summing contoller in the
secondary loop
Traditional Controller
• The temperature inside the tank is
measured and the steam valve
opening is manipulated to add more
or less heat as inflowing water
disturbs the tank temperature.
• This arrangement works well
enough if the steam supply and the
steam valve are sufficiently
consistent to produce another X%
change in tank temperature every
time the controller calls for another
Y% change in the valve opening.
However, several factors could
alter the ratio of X to Y or the
time required for the tank
temperature to change after a
control effort.
• The pressure in the steam supply
line could drop while other tanks
are drawing down the steam
supply they share, in which case
the controller would have to open
the valve more than Y% in order
to achieve the same X% change
in tank temperature.
• A cascade control system could
solve both of these problems as
shown in Figure where a second
controller has taken over
responsibility for manipulating the
valve opening based on
measurements from a second sensor
monitoring the steam flow rate.
• Instead of dictating how widely the
valve should be opened, the first
controller now tells the second
controller how much heat it wants in
terms of a desired steam flow rate.
• The second controller then
manipulates the valve opening until
the steam is flowing at the requested
rate. If that rate turns out to be
insufficient to produce the desired
tank temperature, the first controller
can call for a higher flow rate,
thereby inducing the second
controller to provide more steam and
more heat (or vice versa).
• In the original single-controller arrangement, a drop in the steam
supply pressure would first have to lower the tank temperature
before the temperature sensor could even notice the disturbance.
• With the second controller and second sensor on the job, the steam
flow rate can be measured and maintained much more quickly and
precisely
Ratio Control
• Ratio Control is a special type of feedforward control where 2
disturbances (loads) are measured and held in a constant ratio to
each other.
• It is mostly used to control the ratio of flow rates
• Two flowrates are measured but only one can be controlled.
• The stream whose flowrate is not under control is usually referred
to as wild stream.
Configuration Configuration
1 2
• We measure both flow rates and take • We measure the flow rate of the wild
their ratio. stream and multiply it by the desired
• Ratio is compared with the desired ratio ratio.
(set point) and the deviation (error) • The result is the flow rate that the
between the measured and desired ratios stream B should have and constitutes
constitutes the actuating signal for the the set point value which is compared to
ratio controller. the measured flow rate of stream B.
• The deviation constitutes the actuating
signal for the controller, which adjusts
appropriately the flow of B.
Ratio control is used extensively in chemical
processes with the following as the most commonly
encountered examples:-
• Hold constant the reflux ratio in a distillation column.
• Control the ratio of 2 reactants entering a reactor at a desired
value.
• Hold the ratio of 2 blended streams constant, in order to
maintain the composition of the blend at the desired value.
• Keep the ratio of fuel/air in a burner at its optimum value
(most efficient combustion).
• Maintain the ratio of the liquid flow rate to vapor flow rate in
an absorber constant, in order to achieve the desired
composition in the exit vapor stream.
Example
• Usually the steam pressure in the boiler is controlled through the use of a
pressure control loop on the discharge line (Loop 1).
• At the same time the water level in the boiler should not fall below a lower
limit necessary to keep the heating coil immersed in water thus preventing its
burning out.
• The figure shows the override control system using an LSS (Low Selector
Switch) . If liquid level falls below the allowable limit, the LSS switches the
control action from pressure control to level control (Loop 2).
• Examples of Override Control
Protection of a Compressor System
• Such systems are not very common in chemical processes but provide added
safety and operational optimality whenever necessary.
• Example of Split Range Control
Split Range Control of Chemical Reactor