Three Phase Circuits: Chapter Objectives
Three Phase Circuits: Chapter Objectives
Chapter Objectives:
Be familiar with different three-phase configurations and how
to analyze them.
Know the difference between balanced and unbalanced circuits
Learn about power in a balanced three-phase system
Know how to analyze unbalanced three-phase systems
Be able to use PSpice to analyze three-phase circuits
Apply what is learnt to three-phase measurement and
residential wiring
Power in a Balanced System
The total instantaneous power in a balanced three phase system is constant.
From the given equation in taking the RMS we have:
1 T 2 Im2 T 1 I
I Rms
T 0
I m cos 2 tdt
T
0 2
(1 cos 2 t )dt m
2
and then;
v AN 2V p cos(t ) vBN 2V p cos(t 120) vCN 2V p cos(t 120)
ia 2 I p cos(t ) ib 2 I p cos(t 120) ib 2 I p cos(t 120)
1
p pa pb pc v AN ia vBN ib vCN iccos A cos B [cos( A B ) cos( A B)]
2
p 3V p I p cos The instantenous power is not function of time (similar to DC)
where the factor √2 is necessary because Vp has been defined as the rms value of the
phase voltage and Ip is the rms value of the phase current.
If ZY = Z θ, the phase currents lag behind their corresponding phase voltages by θ.
Thus the total instantaneous power in a balanced three-phase system is Constant and it
is true whether the load is Y- or Δ-connected.
Since the total instantaneous power is independent of time, the average power
per phase Pp for either the -connected load or the Y-connected load is p/3, or
where Vp and Ip are the phase voltage and
phase current with magnitudes Vp and Ip,
respectively. The total average power is the sum
of the average powers in the phases:
The complex power per phase is Sp. The total complex power for all phases is S.
Sp Pp jQp Vp I p Complex power for each phase
3Vp 2
S=3Sp 3Vp I p 3I p 2 Z p
Toal complex power
Zp
S P jQ 3VL I L
Vp , I p , VL and I L are all rms values, is the load impedance angle
Power in a Balanced System
3Vp 2
S=3Sp 3Vp I p 3I p 2 Z p
Toal complex power
Zp
S P jQ 3VL I L
Vp , I p , VL and I L are all rms values, is the load impedance angle
Notice the values of Vp, VL, Ip, IL for different load connections.
VL 3 V p IL I p VL V p IL 3 I p
Ip
Vp Vp
Ip Vp VL
VL
VL Ip
VL Ip
Vp Vp
VL Vp
Ip Ip
VL
Y connected load. Δ connected load.
Power in a Balanced System
Single versus Three phase systems
Advantage of 3 phase system over single phase: Three phase systems uses lesser
amount of wire than single phase systems for the same line voltage VL and same
power delivered PL.
=4/3
Example 1: Refer to the circuit in the given Figure. Determine the total
average power, reactive power, and complex power at the source and at the
load.
(ans. Ss = −(2087 + j834.6) VA and SL = (1392 + j1113) VA)
Example 2: A three-phase motor can be regarded as a balanced Y-load. A three-
phase motor draws 5.6 kW when the line voltage is 220 V and the line current is
18.2 A. Determine the power factor of the motor. (ans. pf = 0.8075)
Example 3: Two balanced loads are connected to a 240-kV rms 60-Hz line, as
shown in Fig. 12.22(a). Load 1 draws 30 kW at a power factor of 0.6 lagging,
while load 2 draws 45 kVAR at a power factor of 0.8 lagging. Assuming the abc
sequence, determine: (a) the complex, real, and reactive powers absorbed by the
combined load, (b) the line currents, and (c) the kVAR rating of the three
capacitors -connected in parallel with the load that will raise the power factor to
0.9 lagging and the capacitance of each capacitor. (ans. C = 635.5 pF)
Example 4: (Practice Problem 12.2)A Y-connected balanced three-phase generator
with an impedance of 0.4+j0.3 ohms per phase is connected to a Y-connected
balanced load with an impedance of 24 + j19 ohms per phase. The line joining
the generator and the load has an impedance of 0.6 + j0.7 ohms per phase.
Assuming a positive sequence for the source voltages and that Van = 120 angle
30◦ V, find: (a) the line voltages, (b) the line currents.
VL=840 V (Rms)
IL
Capacitors for pf
Correction
S 73650
IL 50.68A
3 VL 3 840
Without Pf Correction
Unbalanced Three Phase Systems
An unbalanced system is caused by two possible situations: (1) the source
voltages are not equal in magnitude and/or differ in phase by angles that are
unequal, or (2) load impedances are unequal.
An unbalanced system is due to
unbalanced voltage sources or
unbalanced load.
In a unbalanced system the
neutral current is NOT zero.
where P1, P2, and P3 correspond to the readings of wattmeters W 1, W2, and
W3, respectively. Notice that the common or reference point o in Figure is
selected arbitrarily. If the load is wye-connected, point o can be connected to
the neutral point n. For a delta-connected load, point o can be connected to any
point.
Three Phase Power Measurement
The total real power is equal to the algebraic sum of the two wattmeter
readings,
Three Phase Power Measurement
We recall that each line voltage leads
the corresponding phase voltage by 30◦.
Thus, the total phase difference between
the phase current Ia and line voltage Vab
is (θ + 30◦), and the average power read
by wattmeter W1 is:
Similarly, we can show that the average power read by wattmeter 2 is:
Three Phase Power Measurement
Finding the sum and the difference of the two wattmeter readings:
since 2 cos 30◦ = √3. It shows that the sum of the wattmeter readings gives
the total average power:
Similarly;
Three Phase Power Measurement
since 2 sin 30◦ = 1. It shows that the difference of the wattmeter readings
is proportional to the total reactive power, or
Thus, the total apparent power can be obtained using the equation of PT and
QT as:
Dividing QT and PT gives the tangent of the power factor angle as:
from which we can obtain the power factor as pf = cos θ. Thus, the two-
wattmeter method not only provides the total real and reactive powers, it
can also be used to compute the power factor.
Three Phase Power Measurement
From the given Equations we conclude that:
1. If P2 = P1, the load is resistive.
2. If P2 > P1, the load is inductive.
3. If P2 < P1, the load is capacitive.