0% found this document useful (0 votes)
177 views12 pages

Magnetizing Current - Winding Temperature - Noise and Vibration - Overheating of Laminations and Metal Parts (Caused by Stray Flux)

Over excitation, or over fluxing, in transformers can occur during events that cause low frequency or high voltage such as faults, load shedding, or geomagnetic disturbances. It leads to increased magnetizing current, temperature, noise, and risk of damage. Protection systems monitor the voltage-to-frequency ratio and initiate timers to isolate transformers if they exceed excitation curves for set periods of time, avoiding instant tripping due to momentary disturbances but ensuring removal from service during prolonged over excitation. Relay settings coordinate with the individual transformer's excitation characteristics.

Uploaded by

Ahmad Tukur
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views12 pages

Magnetizing Current - Winding Temperature - Noise and Vibration - Overheating of Laminations and Metal Parts (Caused by Stray Flux)

Over excitation, or over fluxing, in transformers can occur during events that cause low frequency or high voltage such as faults, load shedding, or geomagnetic disturbances. It leads to increased magnetizing current, temperature, noise, and risk of damage. Protection systems monitor the voltage-to-frequency ratio and initiate timers to isolate transformers if they exceed excitation curves for set periods of time, avoiding instant tripping due to momentary disturbances but ensuring removal from service during prolonged over excitation. Relay settings coordinate with the individual transformer's excitation characteristics.

Uploaded by

Ahmad Tukur
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 12

Over Fluxing Or Over excitation in

Transformers
• Generator transformers and grid transformers
• Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.
• Flux  V/ f
• Effects of over fluxing, increase in,
• Magnetizing current
• Winding temperature
• Noise and vibration
• Overheating of laminations and metal parts (caused by stray flux)
Over Excitation:
Over Excitation can occur under no load and on load conditions.

Over Excitation depends on the flux flow in the transformer core.


As


Flux  Voltage Voltage Volts
Flux 
Flux  (Frequecy)-1 Frequency Hertz

Whenever
Volts (P.U)
transformer’s
Volts
Hertz
(P.U)
> Rated transformer’s
Hertz
Over Excitation

Under Over Excitation condition excessive flux saturates core causing


high Eddy current losses in core and adjacent conducting material.

May result in thermal damage to core due to excessively high flux in


magnetic circuits.

2
Over Excitation protection:

Instantaneous tripping is undesirable for Over Excitation. As system


may get overexcited momentary due to some momentary disturbance.

Momentary system disturbances are those which can be borne safely,


and within a very short specific time system restores its normal
conditions.

Over Excitation protection is time dependent function.

For each transformer there exists an “Over Excitation curve”.

“Over Excitation curve” defines over excitation characteristics of a particular


transformer versus time.

Overfluxing protection relay follow “Over Excitation curve” to protect


transformer from over excitation.

3
Over Excitation protection: (Cont)
Over Excitation curve:
Every transformer possesses its own excitation curve.
It follows Inverse time characteristics and definite time characteristics.

Below is the Over Excitation curve of a typical 230/69kV substation transformer.

Over Excitation Curve

70

60
50

40
Danger zone
(Sec)
Time

30

20
10

0
1 1.1 1.2 1.3 1.4 1.5 1.6
Percentage Over Excitation

Transformer Over Excitation curve

4
Over Excitation: (Cont)
Basic concept:
ip(t) is(t)

+ +
Vp(t)= 132kV Vs(t)= 11kV
f= 50
35 Hz f= 50
35 Hz
- -

Due to some external fault, transformer’s operating frequency falls


Consider
down toIf35Hz.
transformer
Due tothe above
will
which not transformer
be
Flux isolated
inside under
thefrom normal
coresupply
has within
been exceeded.
operation and having rating as follows
A relay connected at the primary side of transformer through VT
one or two minutes
having ratio132/√3 will read the information as follows.
24 MVA
“ A transformer
 132 kV / blast
63.5/√3
 50 Hz
11 kV can occurOver Excitation
”. Over Excitation will occur
Fault
Undercondition
normal Operation
3-phase “ If transformer’s [V/Hz] exceeds
transformer’s
Rated
Volts
FOA
Hertz
=
63.5V
35Hz
50Hz
= 1.81 >Rated
Volts
1.27 V/Hz transformer’s
Hertz
= 1.27[V/Hz]
rated V/Hz ”. i.e;
1.27 V/Hz.

5
Over Excitation Relay:
Over Excitation relay follows the same transformer curve.
Over Excitation relay tripping should be well coordinated with transformer’s
over excitation curve.
Over Excitation Curve

70
tim e ( S e c )

60

50

40

30

20

10

0
1 1.1 1.2 1.3 1.4 1.5 1.6
Percentage Over Excitation

Relay Over Excitation curve

6
Over Excitation
Vp(t)= 132kV Vp(t)= 11kV
Solution: f= 50
35 Hz f= 35
50 Hz
Breaker Breaker

Due to some external fault,


132kV/√3
transformer’s operating
63.5V/√3 frequency falls down to
35Hz. Because of which Flux
Timer inside the core has been
24 OverFluxing Protection
1Sec exceeded.

Overfluxing relay connected


If Fault pursuitsatafter
the primary
the timerside of transformer
through VT having ratio 132kV/√3 will read the information as
expiration.
follows. 63.5V/√3 Based on the %age excitation Relay
Under “ Relay sends tripping signals to the a timer.
initiates
Normalfault condition
Operating condition
associated
Volts breakers causingTimer’s
63.5V transformer
value is selected from relay’s
transformer’s Volts = from
transformer’s isolation 63.5Vthe 1.81 V/Hz
=
= 35Hz = 1.27 V/Hz.over excitation curve.
system”
Hertz
Hertz 50Hz
In case of 1.428 %age excitation, relay
Percentage Excitation= 1.428
initiates a timer for 1.0 seconds.

7
Over Fluxing in Transformers
Theory

2m
V=kf
m
Causes
• Low frequency
• High voltage Im
• Geomagnetic disturbances

Effects
 Tripping of differential element (Transient over fluxing)
 Damage to transformers (Prolonged over fluxing)

17th March 2007


5th Harmonic Restraint

• Blocks differential element for transient over fluxing

25% Overvoltage condition

43% 5th Harmonic content

17th March 2007


Over Flux Protection

• Protective relay responds to V/f ratio


• Measured from voltage input
• Two stage protection
Stage 1 - lower A.V.R. or alarm
Stage 2 - Trip field or transformer
• Definite time of Inverse time

17th March 2007


Over Flux Protection

V/f = k 
Trip and alarm outputs for clearing prolonged over fluxing

Alarm : Definite time characteristic to initiate corrective action

Trip : IDMT or DT characteristic to clear over-fluxing condition

Settings

Pick-up 1.5 to 3.0 i.e. 110V x 1.05 = 2.31


50Hz
DT setting range 0.1 to 60 seconds

17th March 2007


Over Excitation Solution: (Cont)
An Over flux relay tripping should be well coordinated with transformer’s
over excitation characteristics.

Over Excitation

70
60
50
Time from transformer curve
Time(Sec)

40
30 Relay Time to initiate Trip
20
10
0
1 1.1
Danger
1.2 1.3
zone
1.4 1.5 1.6 1.7
Percentage Excitation

12

You might also like