Ict/Reactor Protection: Mahendra S Hada Powergrid
Ict/Reactor Protection: Mahendra S Hada Powergrid
PROTECTION
Mahendra S Hada
POWERGRID
Transformer Protection
Type of Fault
• Incipient faults
• Internal faults
• External fault
Transformer Protection
Cause of Fault
1. Insulation Breakdown
2. Phase to phase and Phase to Ground Fault
3. Reduced Cooling
4. Over heating due to over-excitation
5. Oil contamination and leakage
6. Aging of Insulation
7. Turn to Turn Fault
8. Overload Protection
Transformer Protection
Insulation Breakdown
• Differential relays
• Restricted Earth Fault relays
• Backup Over current/Earth Fault relays
• Backup Impedance Relays
• Over fluxing relays
• Buchholz
Transformer Protection
Differential Protection
BASIC requirement:
• The Differential Relay must not operate for load (or)
external fault
• The relay must operate for severe enough internal
fault
Transformer Protection
Differential Protection
It compares the current entering the transformer with the
current leaving the transformer
• If they are equal there is no fault inside the zone of
protection
• If they are not equal it means that a fault occurs
between the two ends
Transformer Protection
Differential Protection
Transformer differential relays are subject to several
factors that can cause miss- operation
• Different voltage levels, including taps, that result in
different primary currents in the connecting circuits
• Possible mismatch of ratios among different current
transformers.
For units with ratio-changing taps, mismatch can
also occur on the taps. Current transformer
performance is different, particularly at high
currents
• Magnetizing inrush currents, which the differential
relay sees as internal faults
Transformer Protection
Differential Protection
To prevent miss-
operation percentage
characteristics are
used, with line current
Operating zone
restraint
Transformer Protection
Differential Protection: ALSTOM P643/P645
Id/Iref
fe tic
`
ed
de is
si er
e ct
gl ra
in ha
rs tC
Fo ul
Fa = 0.8
k2
TRIPPING
.2
Is1/Iref= 0.2 k1=0 BLOCKING
Operate Unconditionally
Operate Conditionally
Slope Section3
Section1 Section2 Section3
Restrain
Idmin
Slope Section2
End Section1 Retrain
Current
End Section2
Transformer Protection
Differential Protection: Harmonic Restraint
• Since magnetizing inrush current has a high harmonic
content, particularly the second harmonic, this second
harmonic can be used to restrain and thus desensitize
a relay during energization.
• The method of harmonic restraint is not without its
problems.
• There must be enough restraint to avoid relay
operation on inrush, without making the relay
insensitive to internal faults that may also have some
harmonic content
Transformer Protection
Differential Protection: Zero Sequence Filter
• Zero sequence current will flow in the differential
circuit for external ground faults on the wye side of a
grounded wye-delta bank; if the current transformers
were connected in wye, the relays would miss-
operate.
• With the current transformers connected in delta, the
zero sequence current circulates inside the current
transformers, preventing relay miss- operation
Transformer Protection
Differential Protection: Zero Sequence Filter
Transformer Protection
Over Excitation
• Over-excitation occurs when volts per hertz level rises
(V/Hz) above the rated value
• This may occur from
o Load rejection (generator transformers)
o Malfunctioning of voltage and reactive support
elements
• The voltage rise at nominal frequency causes the V/Hz to
rise
• This causes the transformer core to saturate and thereby
increase the magnetizing current.
• The increased magnetizing current contains 5th harmonic
component
• This magnetizing current causes the differential element to
pickup
Transformer Protection
Over Excitation
U/F % Timer Time Setting
110 T1 9000 secs
118 T2 90 secs
126 T3 49.5 secs
134 T4 18 secs
142 T5 4 secs
150 T6 1 sec
Transformer Protection
Restricted Earth Fault
• A percentage differential relay has a certain minimum
value of pick up for internal faults. Faults with current
below this value are not detected by the relay.
Rs = Vs / Is