Control Chapter 7
Control Chapter 7
Control Chapter 7
If transfer functions of all components of the loop are known, the dynamic
parameters and can be analytically determined. This is not usually the case, and we
must often determine them from the actual process by the following procedure:
1. Switch off the integral and derivative modes so as to have a P controller.
2. With the controller in automatic (closed-loop), increase the proportional gain
slowly until the loop goes oscillatory with constant amplitude. Record the value
of the gain that produces sustained oscillations as .
PROCESS CHARACTERIZATION:
ON-LINE (CLOSED LOOP) METHOD:
QUARTER DECAY RATIO (QDR) BY ULTIMATE GAIN
This difficulty can be easily corrected by reducing the controller gain from the value
predicted by the formulas.
Another difficulty of using QDR tuning formulas is that (except for the case of the P
controller) the set of tuning parameters necessary to obtain such behavior is not
unique
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION
The Ziegler-Nichols on-line tuning method introduced before is the only one that
characterizes process by and . Most methods approximate processes to a first order
plus dead time (FOPDT) or a second order plus dead time (SOPDT) transfer function.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION
Where and .
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION
As the controller concerns, is the process, and this is precisely what must be
approximated, if possible, as a FOPDT or SOPDT transfer function.
A FOPDT looks like:
∆𝑐 3
𝑘=
Δ𝑚
, 𝜏=
2
( 𝑡 2 − 𝑡 1 ) , 𝑡 0 =𝑡 2 − 𝜏
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR QDR RESPONSE
In addition to on-line tuning formulas, Ziegler and Nichols developed off-line
formulas based on a FOPDT model fit to the process reaction curve.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR QDR RESPONSE
In using the formulas of Table 7-2.1, we must keep in mind that they are empirical
and apply only to a limited range of ratios of dead time to time constant. They are
most applicable for a range of of around 0.10 to 0.5.
As pointed out in the discussion of on-line tuning, the QDR formulas can be adjusted
to less oscillatory responses by reducing the proportional gain from the value given
by the tuning formula.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR MINIMUM ERROR INTEGRAL CRITERIA
Since QDR tuning parameters are not unique, Paul W. Murrill and Cecil L. Smith
developed new tuning formulas.
They used the FOPDT model parameters. Their specification for closed loop
response was to minimize the error or deviation of the controlled variable from set
point.
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR MINIMUM ERROR INTEGRAL CRITERIA
PROCESS CHARACTERIZATION:
OPEN-LOOP PROCESS CHARACTERIZATION:
TUNING FOR MINIMUM ERROR INTEGRAL CRITERIA
The integral of the error cannot be minimized directly, because a very large negative
error would be the minimum. In order to prevent negative values of the
performance function, the following formulations of the integral can be proposed:
• Integral of the absolute value of the error:
Lopez et al. (1967) developed tuning formulas for minimum error integral criteria.
5% Overshoot 0% Overshoot
P
PI
PID
TUNING: EXCERCISES:
7-15
TUNING: EXCERCISES:
7-15
TUNING: EXCERCISES:
7-15
TUNING: EXCERCISES:
7-15
CASE STUDY 2 (APPENDIX E)
CASE STUDY 2 (APPENDIX E)
CASE STUDY 2 (APPENDIX E)