Configuring Instrumentation and Control Devices
Configuring Instrumentation and Control Devices
1
1.1 Setting up /Configuring Signal Conditioning
Unit
Most signals found from sensors are too weak which needs
conditioning.
Signal conditioning is the process of modifying the incoming signal as
per the requirement
There are different conditioning techniques some of them are the
following:
1. Amplification is the process of increasing the amplitude or
strength of the sensor output signal without varying it in any other
way.
2. Modulation and demodulation is the process of imposing or
removing a signal (the information) up on another signal (the carrier)
that is used to convey the original information.
3. frequency selection (the process whereby a signal containing a
group of different frequencies is filtered, allowing only certain desired
frequencies to pass while blocking all other frequencies .filtration) is
2
1.2 Operational Amplifier Basics
The operational amplifier is an extremely efficient and versatile
device.
Its applications span the broad electronic industry filling
requirements for signal conditioning, special transfer functions,
analog instrumentation, analog computation, and special systems
design.
They have two inputs and one output.
One is an inverting terminal and the other is a non-inverting
terminal
Thus the amplifier subtracts the value of V1 from V2 and the
output signal is an amplified version of the difference b/n the two
i/p signals.
3
4
5
1.2.1. Kirchhoff’s Current Law applied to
Op-amps
An operational amplifier circuit can be analyzed with the use of a
well-accepted observation known as Kirchhoff’s Current Law
(KCL).
KCL simply states that the currents entering a node are equal in
magnitude to the currents leaving that same node
KCL and node voltage analysis apply to all electrical circuits
including operational amplifiers
The number (1) indicates the main node of significance
At this node, a current is assumed to leave the inverting terminal
(V-) of the op-amp and go through Ri to ground
Another current is assumed to feed from the output back to the
inverting input through resistor Rf
The third current (i-) feeds into the inverting terminal, but i- always
equals zero
6
1.2.1. Kirchhoff’s Current Law…
7
1.2.1. Kirchhoff’s Current Law…
In fact, there are two important assumptions that concern op-
amps when it comes to KCL circuit analysis:
1) i− = i+ = 0
2) V + = V −
8
1.2.1. Kirchhoff’s Current Law…
The voltage source is connected directly to V+, so V+ = Vs =
V- , and Gnd always equals zero
9
1.2.3. Supply voltages
Looking at the op-amp symbol, the V+supply and V-supply
terminals are the dc supply voltages
The output of the op-amp is influenced by these supply voltages
in three ways
1.2.4. Open/Closed Loop Gain
An especially notable characteristic of operational amplifiers is
the very high gain achieved at the output
In general, gain is calculated as Vgain = Vout/Vin, a ratio of the
output voltage to the input voltage
The output is positive if the non-inverting input is more positive
than the inverting input, and negative if the inverting input is
more positive than the non-inverting input
10
1.2.4. Open/Closed…
The gain value of an op-amp can be as high as 200,000 when
there is no physical connection between the output and either of
the inputs. This is called open loop gain
However, if there is a connection between the output and the
input, usually through a resistor, then a feedback network has
been established, and the gain is now a closed loop gain
11
1.2.4. Open/Closed…
The feedback is either negative or positive, but usually negative
feedback is used
Positive feedback occurs when some of the output feeds the
input in a way that boosts the input value
Negative feedback exists when some of the output returns to the
input, but it acts contrary to the input, in that it is of opposite
polarity, and so diminishes the value of the input
When this input value is diminished then the difference between
the inputs is also diminished. So, the voltage gain of a closed
loop op-amp due to negative feedback is less than that of the
open-loop gain
12
1.3. Configuring Basic Op-Amp Circuits
13
Inverting…
14
1.3.2. Non-inverting amplifier ckt
15
Non-inverting…
16
1.3.3. Comparator ckt
17
Comparator…
The inverting terminal of the op-amp is set at the reference
voltage, which is
When the input signal (Vs) at the non-inverting input is greater
than the reference voltage at the inverting input then Vout will
equal the positive supply (V+ supply)
Similarly, when Vs is less than the reference voltage, then Vout
will equal the negative supply (V-supply)
18
2. The Control loop
20
21
2.1 Process control terms
1. process variable
A process variable is a condition of the process fluid (a liquid or gas) that can
change the manufacturing process in some way
In the example of you sitting by the fire, the process variable was temperature
In the example of the tank in the above Figure , the process variable is level
Common process variables include:
◦ Pressure
◦ Flow
◦ Level
◦ Temperature
◦ Density
◦ Ph (acidity or alkalinity)
◦ Mass
◦ Conductivity
22
Process control…
2. Set point
The set point is a value for a process variable that is desired to be
maintained
For example, if a process temperature needs to kept within 5 °C of
100 °C, then the set point is 100 °C.
A temperature sensor can be used to help maintain the temperature
at set point
The sensor is inserted into the process, and a controller compares
the temperature reading from the sensor to the set point
If the temperature reading is 110 °C, then the controller
determines that the process is above set point and signals the fuel
valve of the burner to close slightly until the process cools to 100
°C
23
Process control…
3. measured variables
In the temperature control loop example, the measured variable is
temperature, which must be held close to 100 °C
The measured variable is the condition of the process fluid that
must be kept at the designated set point
4. manipulated variables
The factor that is changed to keep the measured variable at set
point is called the manipulated variable
In the example described, the manipulated variable would also be
flow
24
Process control…
5. Error
Error is the difference between the measured variable and the set
point and can be either positive or negative
In the temperature control loop example, the error is the difference
between the 110 °C measured variable and the 100 °C set point—
that is, the error is +10 °C.
The objective of any control scheme is to minimize or eliminate
error
We have more terms to describe how the PID control system reduces
the error
The settling time is how long it takes the error to reach its final value
The overshoot is the peak value of the error
Finally, the steady state error is the value where the error settles
25
26
2.2 Manual and Automatic control
28
Properties of Controller
Consider the following closed-loop control system:
The actual output is sensed by a sensor and converted to a proper
feedback signal b(t) using a feedback element
1. Error
The error detector compares the feedback signal b(t) with the
reference input r(t) to generate an error
29
Classification of Controllers
The classification of controllers is based on the response of the
controller and mode of operation of the controller
Controllers are basically classified as continuous and discontinuous
controllers
The discontinuous mode controllers are further classified as ON/OFF
controllers and multi position controllers
The continuous mode controllers are further classified as proportional
controllers, integral controllers and derivative controllers
Continuous controller modes
In continuous controller mode, the controller output varies smoothly
proportional to the error
Depending upon which form of the error is used as the input to the
controller to produce the continuous controller output, these
controllers are classified as
30