Ton of Refrigeration and Heat Load Calculation

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 16

TON OF REFRIGERATION AND

HEAT LOAD CALCULATION


ARC313

LATENT HEAT
Latent heat, energy absorbed or released by a
substance during a change in its physical state (phase)
that occurs without changing its temperature.

Mostafizur Rahman, email: [email protected] mob: 8556053166


ARC313

Mostafizur Rahman, email: [email protected] mob: 8556053166


ARC313

TON OF REFRIGERATION

Ton of Refrigeration (TR): Ton of Refrigeration


(abbreviated as TR) is an important historical unit of
refrigeration capacity. Originally 1 TR was defined as
the rate of heat transfer required to make 1 ton
(1000KG) of ice per day (24HR) from water at 0oC.

Mostafizur Rahman, email: [email protected] mob: 8556053166


ARC313

LATENT HEAT
1000 KG ICE WATER
0*C 0*C

1 TON OF AC WILL BE
REMOVING 3.876 KW OF
24 HRS HEAT FROM THE ROOM
LATENT HEAT OF ICE = 335 KJ / KG
LATENT HEAT OF 1000 KG ICE = 335 KJ/KG X 1000 KG PRACTICALLY ONE TR IS
1 TON OF REFRIGERATION 335 KJ/KG X 1000 KG EQUAL TO 3.517 KW
24 HRS

335 KJ/KG X 1000 KG


1 TON OF REFRIEGERATION = = 3.87KJ/SEC = 3.87 KW
24 X 3600 SEC

Mostafizur Rahman, email: [email protected] mob: 8556053166


ARC313

BTU OR BRITISH THERMAL UNIT

1 TON OF REFRIGERATION = 12000 BTU = 3.876 KJ/SEC = 3.876 KW

a room with heating load as following


1. 3 people producing heat 0.5KW
2. Walls and windows producing heat 2KW
3. Electrical appliances producing heat 1KW
4. Mataces and linen producing heat 1.37KW

CALCULATE THE TOTAL HEAT LOAD AND TON OF REFRIGERATION

Mostafizur Rahman, email: [email protected] mob: 8556053166


ARC313

HEAT LOAD CALCULATION

1. EXTERNAL HEAT LOAD


Walls
Roof
Partition
Glass
Ventilation

2. INTENAL HEAT LOAD


People
Lighting
electrical

Mostafizur Rahman, email: [email protected] mob: 8556053166


ARC313

WALL HEAT LOAD CALCULATION

Q = UA^T
Q = HEAT FLOW (BTU/HR)
A = SQFT
^T = T ext – T int
U = Overall heat transfer coefficient
= 1/R
R = (Resistance of material)

Mostafizur Rahman, email: [email protected] mob: 8556053166


MATERIAL THICKNESS R-VALUE (F° · SQ.FT. · HR/BTU)
 Air Films
Exterior  0.17
Interior Wall  0.68
Interior Ceiling  0.61
 
Air Space
Minimum 1/2" up to 4" 1.00
 
Building Board
Gypsum Wall Board 1/2" 0.45
Gypsum Wall Board 5/8" 0.5625

Plywood 1/2" 0.62


Plywood 1" 1.25
Fiber board sheathing 1/2" 1.32
Medium Density Particle Board 1/2" 0.53
MATERIAL THICKNESS R-VALUE (F° · SQ.FT. · HR/BTU)
Insulating Materials
R-11 Mineral Fiber with 2x4 5.50
metal studs @ 16" OC
R-11 Mineral Fiber with 2x4 12.44
wood studs @ 16" OC
R-11 Mineral Fiber with 2x4 6.60
metal studs @ 24" OC
R-19 Mineral Fiber with 2x6 7.10
metal studs @ 16" OC
R-19 Mineral Fiber with 2x6 8.55
metal studs @ 24" OC
R-19 Mineral Fiber with 2x6 19.11
wood studs @ 24" OC
Expanded Polystyrene 1" 5.00
(Extruded)
Polyurethane Foam (Foamed 1" 6.25
on site)
Polyisocyanurate (Foil Faced) 1" 7.20
Masonry and Concrete

Common Brick 4" 0.80


Face Brick 4" 0.44
Concrete Masonry Unit (CMU) 4" 0.80
Concrete Masonry Unit (CMU) 8" 1.11
Concrete Masonry Unit (CMU) 12" 1.28
MATERIAL THICKNESS R-VALUE (F° · SQ.FT. · HR/BTU)
 Air Films
Exterior  0.17
Interior Wall  0.68
Interior Ceiling  0.61
 
Air Space
Minimum 1/2" up to 4" 1.00
 
Building Board
Gypsum Wall Board 1/2" 0.45
Gypsum Wall Board 5/8" 0.5625
Plywood 1/2" 0.62
Plywood 1" 1.25
Fiber board sheathing 1/2" 1.32
Medium Density Particle Board 1/2" 0.53
Glazing

Single Pane 1/4" 0.91


Double Pane with 1/4" air 1.69
space
Double Pane with 1/2" air 2.04
space
Double Pane with 3/4" air 2.38
space
Triple Pane with 1/4" air 2.56
spaces
Triple Pane with 1/2" air 3.23
spaces
Doors

Wood, solid core 1 3/4" 2.17


Solid insulated metal door, 1.5" - 2" 6.00 - 7.00
polystyrene insulation
ASTM C518 Calculated
Solid insulated metal door, 1.5" - 2" 2.20 - 2.80
polystyrene insulation
ASTM C1363 Operable
Solid insulated metal door, 1.5" - 2" 10.00 - 11.00
polyurethane insulation
ASTM C518 Calculated
Solid insulated metal door, 1.5" - 2" 2.50 - 3.50
polyurethane insulation
ASTM C1363 Operable
a one brick thick wall having (R value 0.24 *F Hr Sqft /BTU) has length 4m and height
3.5m. Calculate the total heat load of the wall (in BTU/HR) when temperature
difference between external and internal is 30*F. Also recommend the tonnage of AC
required for the same.