Importance of Sub-Station Equipment Maintenance: Presented by MD - Golam Mowla XEN (G&P)
Importance of Sub-Station Equipment Maintenance: Presented by MD - Golam Mowla XEN (G&P)
Equipment Maintenance
Presented By
MD.GOLAM MOWLA
XEN(G&P)
Major Equipments of S/S
Inspection and maintenance of substation components
Isolator
Earth Switch
C.T./P.T.
Lightening Arrester / Surge Diverter
Switchgear / Breaker
Power transformer
Auxiliary Transformer
Bus bar
Battery and Battery Charger
Control Relay Panel
Remote Terminal Unit for SCADA
Importance of Maintenance
Reliable Power supply
Sustainable Energy Drawing
Quality power deliver
Un-Interruption
Durability
Risk free assurance
Importance of Maintenance
Free from Threat or Pressure
Cost Effective for future planning
Free from Electric Hazards
Economically Savings from unwanted or
unknown huge amount of cost for
restoration.
In a broad sense, savings annually 90
million Taka paying 10 million by
properly using.
Maintenance & Inspection of S/S Equipments
Conservator
HT Buchholz
Bushing Relay
LT
Bushing Tap
Changer
Radiator
Silica Gel
Cooling fan
Operation of Power Transformer
Operation of
Operation of cooling breathing system
control system
Operation of
tap changer
Maintenance of A Power Transformer
Test oil sample of transformer main tank & tap changer tank
Check condition of oil gauges and oil level
Check for oil leakage & integrity of gasket joints
Check the tightness of nuts & bolts
Check the insulation resistance of bushing
Check that silica gel crystals are blue
Re-greasing of bearings of cooling fan
Check the performance of oil temperature & winding temperature meter
Change the oil of OLTC
Check the control system and driving mechanism of OLTC
Check insulation resistance between each winding and ground.
Calculate the Dielectric Absorption Ratio-
Measurement of moisture
content in oil: 50-60 ppm
Gas analysis:
Viscosity at 20°C : 40 cst
Pour point maximum: -10°c
Flash point: 140°c
Dissipation factor or
Power Factor/loss tan delta: at 90°c 0.5%
at 20°c 0.1%
Volume resistivity : 5.7×1014 Ω-cm
Interfacial tension at 27°C: minimum 0.04 N/m
Dielectric constant: 2 to 2.5
Power Transformer Maintenance Form (132/33 KV)
Manufacturer:Hawker Siddeley Power Trans Ltd. Cooling type: ONAN/ONAF Winding Repair/Not repaired
Serial no. 901562 Repaired: 2003.
Checklist:
Sl Check point Checked Remarks
01 Test oil sample of main tank √ Yes No Tested from CERS, result satisfactory
02 Test oil sample of tap changer √ Yes No Replaced oil of tap changer
06 Silica gel condition & breather plugs √ Yes No Color degraded & should be changed.
11 Oil leakage and integrity of gasket joint √ Yes No Not good condition
Test-02: LT Winding resistance (Digital Low resistance Ohmmeter, Model: Megger DLRO 200)
Comments:
Transformer main tank oil is to be centrifuged as degraded P.I. ratio.
Protective device:
Switchgear
Fuse
Mesh Network
Dedicated neutral Grounding.
Proper Boring of Copper Grounding Rod.
Proper size and quality ensure for
copper grounding.
Soil resistivity is more important.
Must have proper grounding design &
grounding equipment and connection.
Importance of Circuit Breaker
No maintenance is required before 10
years for GIS (a set of Bus, Isolator
,Earth switch, Circuit Breaker).
But AIS is not maintenance free.
Thank you