Transformer
Transformer
Transformer
Recommended Books:
1.Stephen J. Chapman : Electric Machinery and Power System Fundamentals
2.J. Rosenblatt & M. H. Friedman : Direct and Alternating Current
Machinery
3.Charles I Hubert : Electric Machines: Theory, Operating Applications, and
Controls
4.B.L. Thereja, A.K. Thereja : A Textbook of Electrical Technology, Volume
II
Transformer
A transformer is a device that converts one AC voltage to another AC voltage at
the same frequency.
It consists of one or more coil(s) of wire wrapped around a common
ferromagnetic core. These coils are usually not connected electrically together.
However, they are connected through the common magnetic flux confined to the
core.
Assuming that the transformer has at least two windings, one of them
(primary) is connected to a source of AC power; the other (secondary) is
connected to the loads.
Types and construction
Power transformers
Core form Shell form
Windings are wrapped around two Windings are wrapped around the
sides of a laminated square core. center leg of a laminated core.
Usually, windings are wrapped on top of each other to decrease flux leakage
and, therefore, increase efficiency.
Types and construction
Types and construction
v p (t ) Np
a (4.8.1)
vs (t ) Ns
The relationship between the primary ip(t) and secondary is(t) currents is
i p (t ) 1
(4.9.1)
is (t ) a
Ip 1
(4.9.3)
Is a
The phase angles of primary and secondary voltages are the same. The phase
angles of primary and secondary currents are the same also. The ideal
transformer changes magnitudes of voltages and currents but not their angles.
Ideal transformer
If the voltage is positive at the dotted end of the primary winding at some
moment of time, the voltage at the dotted end of the secondary winding will also
be positive at the same time instance.
If the primary current flows into the dotted end of the primary winding, the
secondary current will flow out of the dotted end of the secondary winding.
Power in an ideal transformer
Assuming that p and s are the angles between voltages and currents on the
primary and secondary windings respectively, the power supplied to the
transformer by the primary circuit is:
Since ideal transformers do not affect angles between voltages and currents:
p s (4.11.3)
Therefore: Vp
Pout Vs I s cos aI p cos V p I p cos Pin (4.12.2)
a
The output power of an ideal transformer equals to its input power – to be
expected since assumed no loss. Similarly, for reactive and apparent powers:
which is
Vp aVs 2 Vs
ZL ' a a2Z L (4.13.4)
I p Is a Is
It is possible to match magnitudes of impedances (load and a transmission line) by
selecting a transformer with the proper turn ratio.
Analysis of circuits containing
ideal transformers
A simple method to analyze a circuit containing an ideal transformer is by
replacing the portion of the circuit on one side of the transformer by an
equivalent circuit with the same terminal characteristics.
Next, we exclude the transformer from the circuit and solve it for voltages
and currents.
The solutions obtained for the portion of the circuit that was not replaced
will be the correct values of voltages and currents of the original circuit.
Finally, the voltages and currents on the other side of the transformer (in
the original circuit) can be found by considering the transformer’s turn ratio.
400.18 j 300.24
500.336.88
The total impedance is now referred across T1 to the source’s voltage level:
2
1
Z 'eq a12 Zeq 500.336.88 5.00336.88
10
Analysis of circuits containing
ideal transformers: Example
The generator’s current is
V 4800
IG
Z 'eq 5.00336.88
95.94 36.88 A
Knowing transformers’ turn ratios, we
can determine line and load currents:
I line a1I G 0.1 95.94 36.88 9.594 36.88 A
I load a2I line 10 9.594 36.88 95.94 36.88 A
Therefore, the load voltage is:
Vload Iload Zload 95.94 36.88 5 36.87 479.7 0.01V
The losses in the line are: Ploss I line
2
Rline 9.5942 0.18 16.7W
Note: transmission line losses are reduced by a factor nearly 90, the load voltage is
much closer to the generator’s voltage – effects of increasing the line’s voltage.
The current ratio on a transformer
Fs N s is (4.26.2)
Fnet N p i p N s is 0 (4.26.4)
The current ratio on a transformer
Lp P N p i p (4.29.2)
permeance of flux path
Therefore:
d di p
eLp (t ) N p P N p i p N pP
2
(4.29.3)
dt dt
The exact equivalent circuit of a
real transformer
Recognizing that the self-inductance of the primary coil is
Lp N p2P (4.30.1)
di p
Primary coil: eLp (t ) L p (4.30.2)
dt
dis
Secondary coil: eLs (t ) Ls (4.30.3)
dt
The leakage flux can be modeled by primary and secondary inductors.
The magnetization current can be modeled by a reactance XM connected across
the primary voltage source.
The core-loss current can be modeled by a resistance RC connected across the
primary voltage source.
Both currents are nonlinear; therefore, XM and RC are just approximations.
The exact equivalent circuit of a real
transformer
The transformer’s
equivalent circuit
However, the exact circuit is not
very practical.
From this information, the power factor of the input current and the magnitude and
the angle of the excitation impedance can be determined.
To evaluate RC and XM, we determine the conductance of the core-loss resistor is:
1
GC (4.33.1)
RC
The susceptance of the magnetizing inductor is:
1
BM (4.33.2)
XM
Determining the values of components
Since both elements are in parallel, their admittances add. Therefore, the total
excitation admittance is:
1 1
YE GC jBM j (4.34.1)
RC XM
The magnitude of the excitation admittance in the open-circuit test is:
I oc
YE (4.34.2)
Voc
The angle of the admittance in the open-circuit test can be found from the circuit
power factor (PF):
Poc
cos PF (4.34.3)
Voc I oc
Determining the values of components
In real transformers, the power factor is always lagging, so the angle of the current
always lags the angle of the voltage by degrees. The admittance is:
I oc I oc
YE cos 1 PF (4.35.1)
Voc Voc
Therefore:
VSC 0 VSC
Z SE (4.37.1)
I SC I SC
Since the serial impedance ZSE is equal to
Z SE Req jX eq (4.37.2)
Z SE R p a 2 RS j X p a 2 X S (4.37.3)
it is possible to determine the total series impedance referred to the primary side
of the transformer. However, there is no easy way to split the series impedance
into primary and secondary components.
The same tests can be performed on the secondary side of the transformer. The
results will yield the equivalent circuit impedances referred to the secondary side
of the transformer.
Determining the values of components:
Example
Example 4.2: We need to determine the equivalent circuit impedances of a 20
kVA, 8000/240 V, 60 Hz transformer. The open-circuit and short-circuit tests led to
the following data:
VOC = 8000 V VSC = 489 V
IOC = 0.214 A ISC = 2.5 A
POC = 400 W PSC = 240 W
Vs ,nl Vs , fl Vp a Vs , fl
VR 100% 100% (4.52.1)
Vs , fl Vs , fl
In a per-unit system:
V p , pu Vs , fl , pu
VR 100% (4.52.2)
Vs , fl , pu
Where Vs,nl and Vs,fl are the secondary no load and full load voltages.
Note, the VR of an ideal transformer is zero.
The transformer phasor diagram
A transformer operating at
a unity power factor:
It is seen that VR > 0
A transformer operating at a
leading power factor:
If the secondary current is leading,
the secondary voltage can be higher
than the referred primary voltage;
VR < 0.
The transformer efficiency
a. Find the equivalent circuit of this transformer referred to the high-voltage side.
b. Find the equivalent circuit of this transformer referred to the low-voltage side.
c. Calculate the full-load voltage regulation at 0.8 lagging power factor, at 1.0
power factor, and at 0.8 leading power factor.
d. Plot the voltage regulation as load is increased from no load to full load at
power factors of 0.8 lagging, 1.0, and 0.8 leading.
e. What is the efficiency of the transformer at full load with a power factor of 0.8
lagging?
The transformer efficiency: Example
a. The excitation branch values of the equivalent circuit can be determined as:
Poc 50
oc cos 1 cos 1 84
Voc I oc 2300 0.21
The excitation admittance is:
I oc 0.21
YE 84 84 0.0000095 j 0.0000908S
Voc 2300
The elements of the excitation branch referred to the primary side are:
1
Rc 105k
0.0000095
1
XM 11k
0.0000908
The transformer efficiency: Example
b. To find the equivalent circuit referred to the low-voltage side, we need to divide
the impedance by a2. Since a = 10, the values will be:
Pout
100% 98.03%
PCu Pcore Pout
Transformer taps and voltage regulation
We assumed before that the transformer turns ratio is a fixed (constant) for the
given transformer. Frequently, distribution transformers have a series of taps in
the windings to permit small changes in their turns ratio. Typically, transformers
may have 4 taps in addition to the nominal setting with spacing of 2.5 % of full-
load voltage. Therefore, adjustments up to 5 % above or below the nominal
voltage rating of the transformer are possible.
Example 4.6: A 500 kVA, 13 200/480 V transformer has four 2.5 % taps on its primary
winding. What are the transformer’s voltage ratios at each tap setting?
Taps allow adjustment of the transformer in the field to accommodate for local
voltage variations.
Sometimes, transformers are used on a power line, whose voltage varies widely
with the load (due to high line impedance, for instance). Normal loads need fairly
constant input voltage though…
One possible solution to this problem is to use a special transformer called a tap
changing under load (TCUL) transformer or voltage regulator. TCUL is a
transformer with the ability to change taps while power is connected to it. A voltage
regulator is a TCUL with build-in voltage sensing circuitry that automatically
changes taps to keep the system voltage constant.
These “self-adjusting” transformers are very common in modern power systems.
The autotransformer
Series Series
winding winding
Common Common
winding winding
Output (up) or input (down) voltage is a sum of voltages across common and series windings.
The autotransformer
Since the autotransformer’s coils are physically connected, a different terminology
is used for autotransformers:
The voltage across the common winding is called a common voltage VC, and the
current through this coil is called a common current IC. The voltage across the
series winding is called a series voltage VSE, and the current through that coil is
called a series current ISE.
The voltage and current on the low-voltage side are called VL and IL; the voltage
and current on the high-voltage side are called VH and IH.
For the autotransformers: VC N
C (4.68.1)
VSE N SE
N C I C N SE I SE (4.68.2)
VL VC I L I C I SE (4.68.3)
VH VC VSE I H I SE (4.68.4)
Voltage and Current relationships in
an Autotransformer
Combining (4.68.1) through (4.68.4), for the high-side voltage, we arrive at
N SE N SE
VH VC VC VL VL (4.69.1)
NC NC
VL NC
Therefore: (4.69.2)
VH N C N SE
I L N C N SE
Therefore: (4.69.4)
IH NC
The apparent power advantage
Not all the power traveling from the primary to the secondary winding of the
autotransformer goes through the windings. As a result, an autotransformer can
handle much power than the conventional transformer (with the same windings).
Considering a step-up autotransformer, the apparent input and output powers are:
Sin VL I L (4.70.1)
Sout VH I H (4.70.2)
where SIO is the input and output apparent powers of the autotransformer.
However, the apparent power in the autotransformer’s winding is
SW VC I C VSE I SE (4.70.4)
Which is: SW VL I L I H VL I L VL I H
NC N SE
VL I L VL I L S IO (4.70.5)
N SE NC N SE NC
The apparent power advantage
Therefore, the ratio of the apparent power in the primary and secondary of the
autotransformer to the apparent power actually traveling through its windings is
S IO N SE NC
(4.71.1)
SW N SE
N SE 28
SW S IO 5 1.015MVA
N SE N C 28 110
Therefore, the autotransformer would have windings rated at slightly over 1 MVA
instead of 5 MVA, which makes is 5 times smaller and, therefore, considerably less
expensive.
However, the construction of autotransformers is usually slightly different. In
particular, the insulation on the smaller coil (the series winding) of the
autotransformer is made as strong as the insulation on the larger coil to withstand
the full output voltage.
The primary disadvantage of an autotransformer is that there is a direct
physical connection between its primary and secondary circuits. Therefore,
the electrical isolation of two sides is lost.
The apparent power advantage: Ex
Example 4.7: A 100 VA, 120/12 V transformer will be connected to form a step-up
autotransformer with the primary voltage of 120 V.
a.What will be the secondary voltage?
b.What will be the maximum power rating?
c.What will be the power rating advantage?
a. The secondary voltage:
N C N SE 120 12
VH VL 120 132V
NC 120
Smax 100
b. The max series winding current: I SE ,max 8.33 A
VSE 12
1. Y-Y connection:
The primary voltage on each phase of
the transformer is
VLP
V P (4.77.1)
3
The secondary phase voltage is
VLS 3V S (4.77.2)
VLP 3V P
a (4.77.3)
VLS 3V S
3-phase transformer connections
The Y-Y connection has two very serious problems:
1.If loads on one of the transformer circuits are unbalanced, the
voltages on the phases of the transformer can become severely
unbalanced.
2.The third harmonic issue. The voltages in any phase of an Y-Y
transformer are 1200 apart from the voltages in any other phase.
However, the third-harmonic components of each phase will be in
phase with each other. Nonlinearities in the transformer core always
lead to generation of third harmonic! These components will add up
resulting in large (can be even larger than the fundamental component)
third harmonic component.
2. Y- connection:
The primary voltage on each phase of
the transformer is
VLP
V P (4.79.1)
3
The secondary phase voltage is
VLS V S (4.79.2)
VLP 3V P
3a (4.79.3)
VLS V S
3-phase transformer connections
The Y- connection has no problem with third harmonic components due to
circulating currents in . It is also more stable to unbalanced loads since the
partially redistributes any imbalance that occurs.
One problem associated with this connection is that the secondary voltage is
shifted by 300 with respect to the primary voltage. This can cause problems when
paralleling 3-phase transformers since transformers secondary voltages must be
in-phase to be paralleled. Therefore, we must pay attention to these shifts.
In the U.S., it is common to make the secondary voltage to lag the primary voltage.
The connection shown in the previous slide will do it.
3-phase transformer connections
3. -Y connection:
The primary voltage on each phase of
the transformer is
V P VLP (4.81.1)
VLP V P a
(4.81.3)
VLS 3V S 3
4. - connection:
The primary voltage on each phase of
the transformer is
V P VLP (4.82.1)
VLP V P
a (4.82.3)
VLS V S
flux
If a steady-state voltage
v(t ) VM sin t (4.90.1)
Vmax
max (4.91.1)
Np
Therefore, to maintain the same maximum flux, a change in frequency (say, 50
Hz instead of 60 Hz) must be accompanied by the corresponding correction in
the maximum allowed voltage. This reduction in applied voltage with frequency
is called derating. As a result, a 50 Hz transformer may be operated at a 20%
higher voltage on 60 Hz if this would not cause insulation damage.
Transformer ratings: Apparent Power
The apparent power rating sets (together with the voltage rating) the
current through the windings. The current determines the i2R losses and,
therefore, the heating of the coils. Remember, overheating shortens the
life of transformer’s insulation!
In addition to apparent power rating for the transformer itself, additional
(higher) rating(s) may be specified if a forced cooling is used. Under any
circumstances, the temperature of the windings must be limited.
Note, that if the transformer’s voltage is reduced (for instance, the
transformer is working at a lower frequency), the apparent power rating
must be reduced by an equal amount to maintain the constant current.
Transformer ratings: Current inrush
Assuming that the following voltage is applied to the transformer at the moment
it is connected to the line:
v(t ) VM sin t (4.93.1)
The maximum flux reached on the first half-cycle depends on the phase of the
voltage at the instant the voltage is applied. If the initial voltage is
and the initial flux in the core is zero, the maximum flux during the first half-cycle
is equals to the maximum steady-state flux (which is ok):
VM
max (4.93.3)
N p
However, if the voltage’s initial phase is zero, i.e.