Generator Principles Generator Construction Excitation System Operational Aspects Generator Protections
Generator Principles Generator Construction Excitation System Operational Aspects Generator Protections
• Generator Construction
• Excitation System
• Operational aspects
• Generator Protections
Alternator:
• Steam Turbines
• Gas Turbines
• Hydraulic Turbines
• Other sources
• This forms the basis for the conversion of
Mechanical Energy into Electrical Energy.
+
_ N N
SHAFT
ROTOR ROTOR
- RECTIFIER
STATOR
STATOR
Powering
11 KV
RESIDUAL MAGNETISM
PT AVR
Feedback
STATOR
STATOR
+ STATOR
ROTOR DIODE ROTOR MAGNET
SHAFT
ROTOR MAGNET
ROTOR
- RECTIFIER
STATOR
STATOR
STATOR
Feed back
11 KV
PT AVR
Powering
AC - DC +
POWERING TO EXCITER
CONVERTER -
FIRING PULSE
Aux. power
GENERATOR
Reference Feedback
REFERENCE FEEDBACK
PROCESSING PROCESSING
• There are two identical AVRs present
• The AVR will not come into line unless the
turbine reaches 85% of full speed
• One of the AVR will be on line and the other
one will remain as standby.
• If the main AVR fails , then the stand by
AVR will automatically come onto line
• A manual excitation control provision also
exists
Parameters List:
• Voltage
• Frequency
• Active power
• Reactive power
• Excitation voltage / current
• Power Factor
Frequency - Real power
f
NL
FSR 3
FL FSR 2
FSR 1
P
FL
Voltage - Reactive Power:
V
NL
IF 3
FL IF 2
IF 1
Q
FL
TURBINE REACHES FULL SPEED
SYNCHRONISATION
6 MW LOADS
Real and Reactive power supplied will be the amount demanded by the Load.
FIELD
GOVERNOR
CURRENT
SETDECIDES
POINT DECIDES
THE TERMINAL
THE FREQUENCY
VOLTAGE
• More load in shared condition.
• Increase in Reliability.
• Flexibility in Maintenance.
GT-A GT-B
LOADS ARE
ARE
ARE THE
THE
THE YES
FREQUENCIES
VOLTAGES
PHASE SAME?
SAME?
SEQUENCES SAME?
37 MW GT-A 4 MW GT-B
7 MW LOAD LOAD
LOAD DEMAND
HAS TO IS BETWEEN
BE SHARED CONSTANT
THEM
f
GT-A GT-B
P 6 MW 3 MW 1MW 4 MW P
TO SUMMARISE:
• Load demand is constant
P Q
WHEN INCOMING FREQUENCY IS GREATER THAN GRID:
f
APTRANSCO GT-A
P PAPTRANSCO PGT P
APTRANSCO f GT-A
P PAPTRANSCO -PGT P
APSEB f GT-A
P 6 MW 4 MW 2 MW 1 MW 3 MW 5 MW P
• Voltage and Frequency are fixed by GRID
Winding Y
Winding B
O/C OCCURS
I > 540 A
I
Winding R
Winding Y
Winding B
I >15.2 A or
20 A CT
RELAY
Relay operates
NGR
• The star point of the Generator is earthed
through a Resistor to limit Earth fault
current
• Typically 8%
• To avoid reverse flow of power i.e power
into the generator
• In this state Generator will act as a motor
• If continues to operate , this will cause
overheating of turbine
• Typically 3% ( 5% ) reverse flow
• To avoid running the machine without excitation
• It works on the principle, Impedance=V/I.
• The terminal voltage falls if a sudden heavy load
demand or AVR failure occurs, this will cause the
current to increase and the impedance falls.
• The relay is an Impedance relay and it operates
when Impedance falls below certain limit.
• UNDER VOLTAGE = 7.4 KV ; 7.5 KV