Carrier VPF System
Carrier VPF System
Carrier VPF System
in Variable Primary
Systems
Ron Beliveau
Carrier
Commercial
Sales
Middletown,
CT
Phone Topics
19XRV Chillers
in Variable 19XRV chillers in VPF
Primary Systems systems.
Outline 1. Review conventional Primary Secondary
System.
55 slides in 45
minutes – 3. Review the Benefits of “Max Cap” in both P/S
We will be moving and VPF systems.
very quickly! 4. Review the Benefits of VFD driven chillers in
both P/S and VPF systems.
5. Review chiller selection guidelines for VPF
applications.
.
Phone Topics
19XRV Chillers
in Variable Why all the interest in VPF?
Primary Systems
Why VPF? 1. Unlike many items –this isn’t a “sell up” concept
– it is actually a lower installed cost.
- VPF Reduces pumping and piping
complexities and lowers installation costs.
- Less real estate in mechanical and electrical
rooms.
2. Unlike many cost reductions, VPF can offer
lower operational costs.
- VPF reduces low ∆ T, increasing eff.
- Fewer, but larger pumps have better
efficiency.
Phone Topics
Primary
Secondary
Systems.
Phone Topics
Primary
Secondary
Systems.
Phone Topics
Primary
Secondary
Systems.
Phone Topics
Primary
Secondary
Systems.
Chiller (primary)
pumps are constant
speed (flow).
Secondary pump
speed (gpm)
controlled by DP
switch at most
hydraulically remote
coil.
Phone Topics
Primary
Secondary 1200 gpm
Systems.
If primary gpm equals
secondary gpm, there 1200 gpm
3600 gpm
0 gpm 3600 gpm
Phone Topics
Primary
Secondary 1200 gpm
Systems.
If primary gpm is
greater than 1200 gpm
secondary gpm,
chilled water flows
through the decoupler
line, bypassing the 1200 gpm
coils.
Phone Topics
Primary
Secondary 1200 gpm
Systems.
If primary gpm is less
than secondary gpm, 1200 gpm
the coils.
If return temp is too
high, another chiller /
pump set is started.
Phone Topics
EX: 100 ton building load 100 tons
Primary
Secondary 1200 gpm
Systems. 0 tons
Start up.
0 gpm
Primary
Secondary 1200 gpm
Systems. 0 tons
Primary gpm
equals secondary 1200 gpm 0 gpm 1200 gpm
gpm and there is
no flow through 1200 gpm
decoupler line.
Phone Topics
EX: 550 ton building load 500 tons
Primary
Secondary 1200 gpm
Systems. 0 tons
At 550 tons of
0 gpm
building load the
54 F 0 tons 44 F
secondary pumps
require 1320 gpm.
0 gpm
For a brief time,
primary gpm is
less than 1200 gpm
secondary gpm 120 gpm 1320 gpm
Phone Topics
EX: 550 ton building load 275 tons
Primary
Secondary 1200 gpm
49. 5 F 0 tons 44 F
on chiller and
pump set.
0 gpm
Now primary gpm
> secondary gpm
and chilled water 2400 gpm
flows through 1080 gpm 1320 gpm
decoupler line
1320 gpm
bypassing the
load.
Phone Topics
EX: 1000 ton building load 500 tons
Primary
Secondary 1200 gpm
54 F 0 tons 44 F
tons, in theory,
the chillers are
fully utilized and 0 gpm
there is no flow
through the
decoupler line. 2400 gpm
0 gpm 2400 gpm
2400 gpm
Phone Topics
EX: 1500 ton building load 500 tons
Primary
Secondary 1200 gpm
When building is
1200 gpm
at full load, there
54 F 500 tons 44 F
is 1500 tons
required by coils
and 1500 tons 1200 gpm
provided by
chillers.
3600 gpm
System is 0 gpm 3600 gpm
balanced and
3600 gpm
there is no flow
through decoupler
Phone Topics
EX: 1000 ton building load 500 tons
Primary
Secondary 1200 gpm
As we unload, the
1200 gpm
system can shut
54 F 0 tons 44 F
off the 3rd chiller
only if the delta T
is at design. 0 gpm
2400 gpm
0 gpm 2400 gpm
2400 gpm
Phone Topics
EX: 1000 ton building load 333 tons
Secondary
Systems. 333 tons
3 chillers running
at 67% load!
3600 gpm
1200 gpm 2400 gpm
2400 gpm
Phone Topics
EX: 750 ton building load 250 tons
TONS = GPM x DT / 24
Tons = GPM x ∆ T
Primary with Low Delta T syndrome
TONS = 1200 X 5
7 / 24
Secondary 24 1200 gpm
TONS = 250
350 ???
Systems. 250 tons
GPM = Tons x 24
∆ (2)
In perfect world T
chillers operate @ 1200 gpm
2@ .479 IKW/Ton
With low delta T (3) 1200 gpm
chillers operate @
250 tons each.
3600 gpm
3 @ .518 IKW/Ton 2571 gpm
1029 gpm
.
Phone Topics
Variable
Primary
Systems
Phone Topics
Variable
Primary
Systems
Phone Topics
Variable
Primary
Systems
Phone Topics
Variable
Primary
Systems
Variable Primary
∆ T constant, GPM changes as load changes.
Pump only the chilled water necessary to serve the
load.
Phone Topics
Variable
Primary
Systems
Only one set of
pumps.
No decoupler line
All pumps are
Variable speed.
Flow (gpm) is
regulated to
maintain ∆ T.
Tons = GPM x
∆T
24
Phone Topics
EX: 100 ton building load 0 tons
Variable
Primary 0 gpm
Systems 0 gpm
0 tons
Start up.
0 gpm
Phone Topics
EX: 208 ton building load 0 tons
Variable
Primary 0 gpm
Systems 0 gpm
0 tons
54 F 44 F
Phone Topics
EX: 500 ton building load 0 tons
Variable
Primary 0 gpm
Systems 0 gpm
0 tons
0 gpm
54 F 44 F
Phone Topics
EX: 550 ton building load 0 tons
Variable
Primary 0 gpm
Systems 0 gpm
275 tons
24
54 F 44 F
Phone Topics
EX: 750 ton building load 0 tons
Variable
Primary 0 gpm
0 gpm
Flow split equally.
1800 gpm
Phone Topics
EX: 1000 ton building load 0 tons
Variable
Primary 0 gpm
0 gpm
Flow split equally.
2400 gpm
Phone Topics
EX: 1100 ton building load 366 tons
Variable
Primary 880 gpm
24
54 F 44 F
Phone Topics
EX: 1500 ton building load 500 tons
Variable
Primary 1200 gpm
0 gpm
Flow split equally.
3600 gpm
Phone Topics
Primary Secondary Pumping System
Constant Variable
Variable Building Qty of Chiller
Speed
Chiller
Speed
Chiller
Primary Load
100
GPM Chillers % Load ECWT
1200 1 20% 65
IKW/Ton
0.954
IKW/Ton
0.551
Systems 208
500
1200
1200
1
1
42%
100%
65
65
0.619
0.446
0.36
0.384
550 2400 2 55% 65 0.537 0.332
750 2400 2 75% 65 0.479 0.33
When comparing 1000
1100
2400
3600
2
3
100.0% 71.8
73.4% 74.2
0.485
0.527
0.436
0.444
the two systems 1500 3600 3 100% 85 0.59 0.589
we find that
chiller efficiency Variable Primary Pumping System
is basically equal Constant
Speed
Variable
Speed
Building Qty of Chiller Chiller Chiller
Load GPM Chillers % Load ECWT IKW/Ton IKW/Ton
100 500 1 20% 65 0.954 0.548
208 500 1 42% 65 0.619 0.358
500 1200 1 100% 65 0.446 0.384
550 1320 2 55% 65 0.537 0.332
750 1800 2 75% 65 0.479 0.328
1000 2400 2 100% 71.8 0.485 0.436
1100 2640 3 73.4% 74.2 0.527 0.442
1500 3600 3 100% 85 0.59 0.589
Phone Topics
19XRV Chillers
in Variable Why is chiller performance
Primary Systems
identical for both systems?
Mass Flow X Lift
KW = Tons x Lift
Compressor HP ~
Compressor/Cycle
Efficiency
Load
Cooling
Tower
Chiller
Phone Topics
19XRV Chillers
in Variable Lift is equivalent in both
Primary Systems Primary / Secondary and VPF
systems.
Phone Topics
Primary Secondary Pumping System
Constant Variable
Variable Building Qty of Chiller
Speed
Chiller
Speed
Chiller
Primary Load
100
GPM Chillers % Load ECWT
1200 1 20% 65
IKW/Ton
0.954
IKW/Ton
0.551
Systems 208
500
1200
1200
1
1
42%
100%
65
65
0.619
0.446
0.36
0.384
550 2400 2 55% 65 0.537 0.332
750 3600 2 75% 65 0.479 0.33
When comparing 1000
750
1100
3600
3600
3600
2
3
3
100.0% 71.8
50%
73.4% 65
74.2
0.485
0.562
0.527
0.436
0.339
0.444
the two systems 1000
1500 3600
3600 3
3 66.7%
100% 71.8
85 0.533
0.59 0.414
0.589
we find that
chiller efficiency Variable Primary Pumping System
is basically equal Constant
Speed
Variable
Speed
Building Qty of Chiller Chiller Chiller
system.
Phone Topics
19XRV Chillers
in Variable 19XRV chillers in VPF
Primary Systems systems.
Outline 1. Review conventional Primary Secondary
System.
2. Review Variable Primary Flow System.
.
Phone Topics
19XRV Chillers
in Variable The “Max Cap” Advantage
Primary Systems Applied in VPF Systems?
643
Positive
Pressure chillers 630
typically can 630
produce above
rated tons as 600
entering Tons Carrier
condenser water
570
drops.
550
Others
Phone Topics
EX: 550 ton building load 0 tons
Variable
Primary 0 gpm
Systems 0 gpm
0 tons
550 tons
1320 gpm
At 550 tons, the
design ∆ T (of 10F)
1320 gpm 1320 gpm
is achieved with 44 F
1320 gpm of flow. 54 F
0 gpm
(1) Chiller is fully
1320 gpm
loaded.
1320 gpm
550 = 1320 x 10
24 54 F 44 F
Phone Topics
EX: 1100 ton building load 0 tons
Variable
Primary 0 gpm
0 gpm
(2) Chillers are
2640 gpm
now fully loaded.
2640 gpm
1100 = 2640 x 10
24 54 F 44 F
Phone Topics
EX: 1100 ton building load 0 tons
Variable
Primary 0 gpm
550 tons
1200 gpm
At 1100 tons, the
∆ T can be increased
from 10F to 11F by 2400 gpm 1200 gpm
43 F
lowering the LCHWT. 54 F
2400 gpm
1100 = 2400 x 11
24 54 F 43 F
Phone Topics
Primary Secondary Pumping System
Constant Variable
Primary Load
100
GPM
1200
Chillers % Load ECWT
65
IKW/Ton IKW/Ton
208 1200 77
Systems 500
550
1200
2400 2 55%
65
65 0.537 0.332
750 3600 65
900 3600 69
Max Cap 1000
1100
3600
3600 3 73.4%
71.8
74.2 0.527 0.444
advantage – 1500 3600 85
Phone Topics
Primary Secondary Pumping System
Constant Variable
Primary Load
100
GPM
1200
Chillers % Load ECWT
65
IKW/Ton IKW/Ton
208 1200 77
Systems 500
550
1200
2400 2 55%
65
65 0.537 0.332
750 3600 65
900 3600 69
Max Cap 1000
1100
3600
3600 3 73.4%
71.8
74.2 0.527 0.444
advantage 1500 3600 85
lowering Building
Load GPM
Qty of
Chillers
Chiller
% Load ECWT
Chiller
IKW/Ton
Chiller
IKW/Ton
LCHWT. 100
208
500
500
65
77
500 1200 65
550 1320 1 110% 65 0.458 0.443
750 1800 65
efficient than
increasing flow.
Phone Topics
19XRV Chillers
in Variable 19XRV chillers in VPF
Primary Systems systems.
Outline 1. Review conventional Primary Secondary
System.
2. Review Variable Primary Flow System.
.
Phone Topics
19XRV Chillers
in Variable Why Provide Variable
Primary Systems Speed Chillers in VPF?
Same reasons VFD driven chillers take advantage of reduced lift
you would and/or reduced load hours offering annual power
supply 19XRV costs unmatched by any constant speed chiller.
on Primary
Secondary
Systems.
.
Phone Topics
19XRV Chillers
in Variable How 19XRV Chillers save
Primary Systems kW in P/S & VPF Systems
Affinity laws Flow
Area
V
for centrifugal Flow ~ V, A
fans, pumps To increase flow, increase flow
area or rotor speed
and Diameter
compressors. Lift ~V
2
Phone Topics
19XRV Chillers
in Variable How 19XRV Chillers save
Primary Systems
kW in P/S & VPF Systems
Methods to ECWT
Improve Mass Flow X Lift
Efficiency Compressor HP ~
Compressor/Cycle
- Lift Reduction
Efficiency
- Aerodynamics
- Motor efficiency
- Transmission efficiency
Load
Phone Topics
19XRV Chillers
in Variable Efficiency improves dramatically
Primary Systems as ECWT drops.
R e d u c e d L ift a t 1 0 0 % to n s
All points shown are (5 0 0 T o n s )
100% load (500 tons)
0 .6
0 .5 5
19XRV “unlifts” much 0 .5 1 9 XR V
IKW / Ton
0 .4 5
better then constant 1 9 XR
0 .4
speed machine. 0 .3 5
0 .3
85 80 75 70 65 60
E n te r in g C o n d e n s e r W a te r T e m p e r a tu r e
Phone Topics
Three Chiller
Operation
85 ??
100
85F Typical
90 ton-hour
80 profile
70
Operating Hours
75F
Individual 60
Chiller 50 ARI
Load % Condenser
40
Relief
65F
30
20
10
Economizer, if available
#1 Chiller 0
#2 Chiller 4% 12% 20% 28% 36% 44% 52% 60% 68% 76% 84% 92% 100%
#3 Chiller
Total Building Load %
Phone Topics
VFD chiller unloading versus
constant speed chiller
1.05η max
η max N1
N2
0.9η max
N3 Example: (1) 700 ton chiller with 3000 hours/yr at .07 $/KWhr
N4
Constant Vanes
N = Speed Fixed Speed Chiller Annual Operating Cost $79,380
Variable Speed Chiller Annual Operating Cost $55,860
The chiller VSD saves $23,520 Annually
Phone Topics
Primary Secondary Pumping System
Constant Variable
Variable Building Qty of Chiller
Speed
Chiller
Speed
Chiller
Primary Load
100
GPM Chillers % Load ECWT
1200 1 20% 65
IKW/Ton
0.954
IKW/Ton
0.551
Systems 208
500
1200
1200
1
1
42%
100%
65
65
0.619
0.446
0.36
0.384
550 2400 2 55% 65 0.537 0.332
750 2400 2 75% 65 0.479 0.33
VFD column 1000
1100
2400
3600
2
3
100.0% 71.8
73.4% 74.2
0.485
0.527
0.436
0.444
better than 1500 3600 3 100% 85 0.59 0.589
constant speed
column at every Variable Primary Pumping System
point! Constant
Speed
Variable
Speed
Building Qty of Chiller Chiller Chiller
Load GPM Chillers % Load ECWT IKW/Ton IKW/Ton
100 500 1 20% 65 0.954 0.548
* VFD was 208
500
500
1200
1
1
42%
100%
65
65
0.619
0.446
0.358
0.384
selected for 550 1320 2 55% 65 0.537 0.332
750 1800 2 75% 65 0.479 0.328
same FL 1000 2400 2 100% 71.8 0.485 0.436
IKW/Ton – 1100
1500
2640
3600
3
3
73.4%
100%
74.2
85
0.527
0.59
0.442
0.589
therefore a bit
larger and $$$.
Phone Topics
19XRV Chillers
in Variable 19XRV chillers in VPF
Primary Systems systems.
Outline 1. Review conventional Primary Secondary
System.
2. Review Variable Primary Flow System.
.
Phone Topics
19XRV Chillers
in Variable VFD chiller selection guidelines
Primary Systems for VPF applications.
VPF systems save Minimum flow rate is 1.5 feet / second (intermittent) and
pump energy – 3.0 feet / second (extended)
don’t forget to save
Maximum flow rate is 12 feet / second.
on chiller energy
too. Rate of change of flow can be up to 30% per minute.
Remember – you Evaporator should be selected such that design flow rate
can have both! is at least double the minimum flow rate (if equally sized
chillers).
Evaporator flow rate and pressure drops must be
carefully coordinated if unequally sized chillers.