Chapter 2 Transformer
Chapter 2 Transformer
Connect to
AC source Connect to
load
Instrument transformer
- Current transformer (CT)
- Voltage transformer (VT)
• 3-phase transformer:
VA 3.V1( rated ) I1( rated ) 3.V2 ( rated ) I 2 ( rated )
A small AC current Iφ
flows in primary winding
and establishes an
alternate flux in the
magnetic circuit.
max . sin t
The core loss : Pc E1. I . cos c
24/12/2019 401065 - Chapter 2: Transformers 17
2.2. NO-LOAD CONDITION
Example 2.1:
The core loss and exciting volt-ampere for the core at
Bmax=1,5T; f =50Hz; were found to be: Pc=16W;
(V.I)rms=20 (VA). And the induced voltage was 194 V(rms)
when winding had 200 turns. Find : the power factor, the
core-loss current Ic, and the magnetizing current Im
Solution:
Pc 16 0,8 36,87
- Power factor: cos c
(V . I )
20 c
Therefore :
V1
Z1
V2 a 1 V1 1 Z2 2 Z1 a 2 .Z 2
Z2 2 . 2 .Z1 a
I 2 1
I .a a
I 1 a
24/12/2019 401065 - Chapter 2: Transformers 21
2.3. EFFECT OF SECONDARY
CURRENT; IDEAL TRANSFORMER
Summary:
In an ideal transformer, voltages are transformed in the
direct ratio of turns, currents in the inverse ratio, and
impedances in the direct ratio squared; power and volt-
amperes are unchanged.
V1 a.V2 V1
V2
N1 a V1. I 1 V2 . I 2
a I2
N2 I1 I 2 a. I 1
a
Z1 a .Z 2
2 Z1
Z2 2
a
24/12/2019 401065 - Chapter 2: Transformers 22
2.3. EFFECT OF SECONDARY
CURRENT; IDEAL TRANSFORMER
Example
An ideal transformer with an impedance R2+jX2=1+j4() connected
in series with the secondary. The turns ratio N1/N2=5.
a/ Draw an equivalent circuit with the series impedance
referred to the primary side.
b/ For a primary voltage
of 120 Vrms and a short
connected across the
terminals A-B, calculate
the primary current and
the current flowing in the
short.
V '2 a.V2
I2
I '2
a
R '2 a 2 . R2
X '2 a 2 . X 2
Req R1 R'2 R1 a 2 R2
X eq X 1 X '2 X 1 a 2 X 2
Poc
Poc > 0
A W 0 cos
1
0
Ioc Voc I oc
V Xm Rc Qoc Voc I oc sin 0
Voc
Voc2 Voc2
Equivalent circuit of no-load test Rc Xm
Poc Qoc
24/12/2019 401065 - Chapter 2: Transformers 31
2.5. ENGINEERING ASPECTS OF
TRANSFORMER ANALYSIS
2.5.2. Short-circuit test
The secondary terminals (normally the LV
winding) are short circuited, and the primary
terminals are connected to a fairly low-voltage
source.
The input voltage is adjusted until the current
in the short circuited windings is equal to its
rated value
The input voltage, current and power are
measured.
V1 V '2
VR%
V1
V&
1 V2
'
0 I 2 2 (R e q jX eq )
'
& I2
V1 (a.V2 )0 2 (R e q jX eq )
a
V1 V '2 Caution:
So: VR% cos2 lagging (lagging PF) 2 > 0
V1 cos2 leading (leading PF ) 2 < 0
24/12/2019 401065 - Chapter 2: Transformers 37
2.5. ENGINEERING ASPECTS OF
TRANSFORMER ANALYSIS
2.5.3. Voltage Regulation
Phasor diagram:
V1
V’2 I’2Xeq V1
I’2Xeq
2 I’2
I’2Req 2
I’2 PF Lagging V’2
I’2Req
PF Leading
V1
I’2Xeq
2=0 V’2
I’2 I’2Req
Unity PF
24/12/2019 401065 - Chapter 2: Transformers 38
2.5. ENGINEERING ASPECTS OF
TRANSFORMER ANALYSIS
2.5.3. Voltage Regulation
Output characteristic: V2=f(I2)
V2
I2
0 I2
V1 N1 N 2
V2 N2
I1 N2
I 2 N1 N 2
V1 N1
V2 N1 N 2
I1 N1 N 2
I2 N2
A multiwiding transformer
x y z
a b c
X Y Z
(a) (b)
Y/Y-12 Y/-11
Step-down transformer
Reduce power system A X
voltage to lower value for
a
measurement x
V
Provides isolation from
u2
high voltages
The secondary working is
in opened-circuit mode.