Building Management Systems
Building Management Systems
• Central air conditioner station that handles the air that, usually,
will be supplied into the buildings by the ventilation ductwork
(connected to the AHU). Handling the air means that the air will
be delivered into the building spaces with thermo-hygrometric
and IAQ (Indoor Air Quality) treatment.. This means, the Air
Handling Unit treat the air by filtering, cooling and/or heating,
humidifying and/or dehumidifying.
AHU Components
• A fan converts mechanical, rotational energy into fluid energy. This is basically
accomplished by a wheel or propeller which imparts a forward motion to the air.
• Two main types of fans are used in airflow systems centrifugal and axial.
• The selection of the fan will depend on the air volume and the static pressure
required of the system. Usually, the designer of the system will use a specialized
software to do this selection.
AHU Components - Coils
• Coils are a type of heat exchanger. They are arranged
in rows with different fin spacing. Aluminum fins and
copper tubes are used in the design of the coils.
• Cooling Coil is used to cool and dehumidify the air.
There are two types of cooling coil:
1. DX (Direct Expansion - Refrigerant)
2. Chilled Water (Water/ Water + Glycol)
• During winter, the humidity level of the air can be low. Low humidity can cause problems
such as respiratory discomfort and static electricity.
• Humidifiers can humidify a space either directly or through an air handling system.
• Humidifiers in air handling systems typically inject steam directly into the air stream
(steam injection).
AHU Components - Other
• Mixing box has air inlets that is attached to the dampers. This is the place where
the outside air and the return air are mixed to provide the correct proportion of
air to be distributed to the space that is to be conditioned. (Mixing Box is a
component of “Mixed Air Type AHU” only).
• Dampers are used to balance airflow or to block the passage of air through
ductwork. Dampers installed in Outside Air, Return Air & Exhaust Air ducts are
called as mixing dampers. Dampers are also installed after Supply Fan & Return
Fan for isolation purpose. Fire & Smoke Dampers are also installed in Supply &
Return ducts to prevent Fire & Smoke.
• Control Valves are used to control fluid flow by varying the size of the flow
passage as directed by a signal from a controller. They are used in water/ steam
based coils.
AHU Types
• Single Duct AHU has only one duct leaving the fan & has only
one path to go through.
AHU Types
• Dual Duct AHU has only two ducts leaving the fan & has two
paths to go through.
Hot Deck
Cold Deck
AHU Types
• Mixed Air Single Duct Variable Volume
AHU Types
• Roof Top Units (RTU)
AHU Types