Lecture 2 BSE2201 Cooling Load Calculation
Lecture 2 BSE2201 Cooling Load Calculation
Lecture 2 BSE2201 Cooling Load Calculation
1
Cooling load components
The air-conditioning system is to maintain the indoor design
conditions which can fulfill the human thermal comfort.
For example, according to the Code of Practice for Energy
Efficiency of Building Services Installation 2018 (
https://www.emsd.gov.hk/beeo/en/pee/BEC_2018.pdf):
2
According to the energy balance, the sensible and/or latent
(moisture) heat should be removed or added into the indoor space,
in order to maintain the temperature and humidity to be within the
design range.
Simply speaking, the cooling load is the sensible and latent
heat which should be removed by the air-conditioning system.
3
Theoretically, the cooling load components
can be classified into several types:
Type 1: The cooling load due to the solar
heat gain through fenestration (such as
window) area.
6
Type 1: The cooling load due to the solar heat gain through fenestration area (Cont.)
CLF is the Cooling Load Factor. It accounts for the fact that due to the
thermal storage capacity of the building thermal mass, part of the radiant
energy that enters the conditioned space at a particular time does not
become the cooling load instantly. Instead, they are first absorbed by the
internal surfaces (ceiling, floor, internal walls, furniture).
8
Followings are one example of the CLF Table for glass with interior
shading and located in the northern latitudes (ASHRAE) (Cont.)
Where
Af is the fenestration area, unit in m2.
U is the U value of the fenestration,
unit in W/m².K.
The U value (Overall heat transfer coefficients) was introduced in the Lecture L1.
Followings are some examples of the U values of the window glass, unit in W/m 2.K:
Summer Winter
(outdoor air velocity = 3.33 m/s) (outdoor air velocity = 6.67 m/s)
Thickness
3 mm 5 mm 6 mm 12 mm 3 mm 5 mm 6 mm 12 mm
For the surfaces which are not sunlit AND have negligible/light thermal
mass, the CLTD is equal or approximated to be Toutdoor,dry bulb - Tindoor,dry bulb
However, for the sunlit envelope or the envelope with medium/heavy thermal
mass, the CLTD can be checked from the handbooks or manuals (such as
ASHRAE handbooks), with respect to different latitudes, orientations, hour of
the day, day of the year, and different types of thermal masses.
One example of the hourly CLTD of one day for the conduction heat gain
through the window glass, unit in K:
Hour 1 2 3 4 5 6 7 8 9 10 11 12
CLTD -1 0 -1 -1 -1 -1 -1 0 1 2 4 5
Hour 13 14 15 16 17 18 19 20 21 22 23 24
CLTD 7 7 8 8 7 7 6 4 3 2 2 1
11
𝑸˙ 𝒔𝒆𝒏𝒔𝑪𝑳=𝑸˙ 𝒔𝒆𝒏𝒔𝒉𝒆𝒂𝒕𝒈𝒂𝒊𝒏∙𝑪𝑳𝑭=( 𝑨𝒔∙𝑴𝑨𝑿𝑺𝑯𝑮𝑭+𝑨𝒔𝒉∙𝑴𝑨𝑿𝑺𝑯𝑮𝑭𝒔𝒉)∙𝑺𝑪∙𝑪𝑳𝑭
Type 1: The cooling load due to the
solar heat gain through fenestration
(such as window) area.
Type 2: The cooling load due to the
equiv. conduction heat gain through
fenestration area 𝑸˙ 𝒔𝒆𝒏𝒔 𝑪𝑳= 𝑨 𝒇 ∙𝑼 ∙𝑪𝑳𝑻𝑫
12
Example Question 1: Dire Top view of the floor plan
ctio
n of s N
A multi-storey office building has a glass u nlig
curtain wall structure for the 4 facades. ht
Calculate the space cooling load of a typical 3.5 m high for
floor at 16:00 hour on 21 July, which each floor
comprises the solar and conduction heat gain
through the fenestration area.
14
Solution of Example 1:
Type 1: The cooling load due to the solar heat gain through fenestration (such
as window) area.
S: 140, 0.35
15
Solution of Example 1 (cont.):
(1) First check the cooling load of the Type 1 (The cooling load due to
the solar heat gain through fenestration area) for the four facades.
(1.1) For the facade facing North
𝑸˙ 𝒔𝒆𝒏𝒔𝑪𝑳,𝑺𝒐𝒍𝒂𝒓 ,𝑵 =( 𝑨 𝒔,𝑵 ∙𝑴𝑨𝑿 𝑺𝑯𝑮 𝑭 𝑵 +𝑨 𝒔𝒉,𝑵 ∙𝑴𝑨𝑿 𝑺𝑯𝑮 𝑭 𝒔𝒉) ∙𝑺𝑪 ∙𝑪𝑳 𝑭 𝑵
17
Solution of Example 1 (cont.):
(1.3) For the facade facing South
W/m2
𝑺𝑪
=𝟎 .𝟑
𝑪𝑳
𝑭 𝑺 =𝟎 .𝟑𝟓
18
Solution of Example 1 (cont.):
𝑨 𝒔 ,𝑾 =𝟑𝟎× 𝟑 .𝟓=𝟏𝟎𝟓 𝒎 𝟐 𝑨 𝒔 𝒉 ,𝑾 =𝟎 𝒎 𝟐
(2) Thereafter, we can check the cooling load of the Type 2 (The cooling load
due to the equiv. conduction heat gain through fenestration area) for the
four facades.
21
Type 3: The cooling load due to the
equivalent conduction heat gain
through external roofs/walls/floors.
𝑸˙ 𝒔𝒆𝒏𝒔 𝑪𝑳= 𝑨 ∙ 𝑼 ∙𝑪𝑳𝑻𝑫
CLTD is the Cooling Load Temperature Difference (Equivalent concept) between
the outdoor and indoor air by taking the heating effects of the solar radiation
and the storage effect of thermal mass into account, unit in or K.
For the external surfaces which are not sunlit AND have negligible/light thermal
mass, the CLTD is equal or approximated to be Toutdoor,dry bulb - Tindoor,dry bulb
However, if the impact of the solar radiation or the thermal mass should be
considered, the CLTD can be checked from the handbooks or manuals (such as
ASHRAE handbooks), with respect to different latitudes, orientations, hour of
the day, day of the year, and different types of thermal masses.
For the floor surface above the ground soils, the CLTD is equal or
approximated to be Tground - Tindoor,dry bulb
22
Type 3: The cooling load due to the equiv. conduction heat
gain through external roofs, walls, and floors (Cont.)
ASHRAE defines a reference case for the calculation of the CLTD for
a flat roof and two external walls.
The basic information of the roof and the external walls.
Roof External wall A External wall B
Asphalt rolling Stucco Stucco
101.6 mm high-weight concrete 101.6 mm h.w. concrete 101.6 mm h.w. concrete
50.8 mm insulation 25.4 mm insulation
19 mm plastering 19 mm plastering
24
Cooling load temperature difference (CLTD) for a flat roof and two
external walls as described in the former slide (Cont.)
25
Type 3: The cooling load due to the equiv. conduction heat
gain through external roofs, walls, and floors (Cont.)
For different latitudes, months, and indoor/outdoor conditions,
corrections for the CLTD are needed:
𝑪𝑳𝑻
𝑫 𝒄𝒐𝒓𝒓 =[ ( 𝑪𝑳𝑻𝑫+ 𝑳𝑴 ) 𝑲 + ( 𝟐𝟓 . 𝟓 −𝒕 𝒓 ) + ( 𝒕 𝒐𝒎 −𝟐𝟗 . 𝟒 ) 𝒇 ]
CLTD can follow the former Tables.
where tr = indoor temperature (°C),
tom = outdoor daily mean temperature (°C)
LM is the latitude-month correction, with respect to different latitudes,
months and envelope orientations. The Table below shows one example of
the LM values for the latitude of 24 N:
26
Type 3: The cooling load due to the equiv. conduction heat
gain through roofs, walls, and floors (Cont.)
27
Type 4: The cooling
load due to the heat
gain from the
adjacent rooms via
the partition
wall/floor/ceiling
is the sensible heat gain of the occupants (Table on next slides).
CLF is the cooling load factor of the people due to the thermal storage effect of the
building thermal mass (Table on next slides). [The decrement and time-lag effect]
Space latent cooling load for people The latent heat gain is considered to
be the instantaneous space latent
𝑸˙ 𝒍𝒂𝒕𝒆𝒏𝒕 𝑪𝑳 =𝑸
˙ 𝒍𝒂𝒕𝒆𝒏𝒕 𝒉𝒆𝒂𝒕 𝒈𝒂𝒊𝒏 load resulting from the water vapour
released from humansNo CLF in
the Equation
29
Type 5: The cooling load due to the heat gain from the occupants (Cont.)
30
Type 5: The cooling load due to the heat gain from the occupants (Cont.)
CLF is the cooling load factor of the people due to the thermal storage effect of
the building thermal mass.
CLF of people is a function with respect to the number of hours since the entry
and the total hours of staying in space.
The
decrement
and time-
lag effect
Time-lag effect:
the CLF can still
be >0 when the
people are no
longer in the
space.
31
Type 5: The cooling load due to the heat gain from the occupants
(Cont.)
Special cases of CLF=1 for the occupants:
(1) Occupation of the space for continuous of 24
hours in each day (not so common)
OR (2) the cooling is off at night or during weekends
OR (3) for auditorium, theater or when people
density is high such as more than 100 people/90 m2
32
Type 6: The cooling load due to the heat gain from the electric lights
Where is the sensible heat gain from the
electric lights, which can be calculated by the
following equation:
𝑸
˙ 𝒔𝒆𝒏𝒔 𝒉𝒆𝒂𝒕 𝒈𝒂𝒊𝒏 ,𝒍𝒊𝒈𝒉𝒕 =𝑾 𝒊𝒏𝒔𝒕𝒂𝒍𝒍 ∙ 𝑭 𝒖𝒔𝒆 ∙ 𝑭 𝒂𝒍 ∙ ( 𝟏 − 𝑭 𝒗𝒆𝒏 )
Winstall is the total installed rated power of the electric lights in the space, unit in W.
Fuse is the usage factor: the ratio of the actual light power in use to the total installed
light power: e.g. 0.4 means 40% of the total installed light is in use (others are not in
use).
Fal is the allowance factor introduced for the fluorescent light which may require
higher power input than the rated power, varying from 1.18 to 1.30.
33
Type 6: The cooling load due to the heat
gain from the electric lights (Cont.)
Fven is the heat removal factor for the electric
lights employing mechanically ventilated systems
to remove part of the heat released from the
electric lights to the outside.
34
Type 6: The cooling load due to the heat gain from
One example of the CLF of the lights: the electric lights (Cont.)
Number of hours after the lights are turned on
the hours of operation of the lights
Where is the sensible heat gain from the
equipment and appliances, which can be
calculated by the following equation:
𝑸
˙ 𝒔𝒆𝒏𝒔 𝒉𝒆𝒂𝒕 𝒈𝒂𝒊𝒏 ,𝒆𝒒𝒖𝒊𝒑 =𝑾 𝒊𝒏𝒔𝒕𝒂𝒍𝒍 ∙ 𝑭 𝒖𝒔𝒆
36
Type 7: The cooling load due to the sensible heat gain from
equipment and appliances (Cont.)
is the volume flow rate of the infiltrated air, unit in m3/s
is the density of air, unit in [kg/m3], around 1.2 kg/m3 under 15-30 ºC and 1 atm . For detailed
value, please check the Engineering Table.
is the specific heat capacity of air, unit in [J/kg.K], 1000 J/kg.K under 25 ºC and 1 atm. For
detailed value, please check the Engineering Table.
is the dry bulb temperature of the outdoor air, unit in ºC
is the dry bulb temperature of the room air, unit in ºC
is the absolute humidity ratio of the outdoor air, unit in kg/kg dry air.
is the absolute humidity ratio of the room air, unit in kg/kg dry air.
is the latent heat of evaporation per unit mass of vapor, h fg = 2400 kJ/kg = 2.4 x 106 J/kg.
The difference between the heat gain, cooling load, and the
heat extraction rate (by the air-conditioning system)
Cooling Cooling
Part of the
load>Heat load<Heat
Delayed load (Time lag) Extraction Extraction
rate rate
Swing of air
temperature
Conduct to the outdoor through the envelopes
39
Example Question 2
An office room has a vertical window and an exposed wall, both of
which are facing west. The gross area of the window is 7 m2, and
the area of the exposed wall is 8 m2. There are 3 office workers in
this room, and the actual electrical power input to the fluorescent
lights has a total magnitude of 800 W. The actual electric power
input to the computers inside the room has a total magnitude of
240 W. Except computers, no other equipment or appliance is in
the room.
The rest 3 walls of the room are all partition walls, each of which
has an area of 15 m2. The areas of the ceiling and floor are both at
15 m2, too. It is assumed that there are negligible heat gains
through the ceilings or floors. Other information and design data
are listed in the following slides.
In this question, the cooling load due to infiltration can be neglected.
Please calculate the sensible and latent space cooling loads at 14:00 on
July 21st for this office room, if the space air temperature is maintained
constant for continuous of 24 hours in each day.
40
Parameters Values
Window
Window U
U value
value 5
5 W/m
W/m2.K
2
.K
Shading
Shading coefficient
coefficient (SC)
(SC) 0.55
0.55
Maximum solar heat gain factor (MAX_SHGF) for the 672 W/m22
Maximum
sunny areasolar heat
of the gain factor
west-facing (MAX_SHGF)
window on July for
21stthe 672 W/m
sunny area of the west-facing window on July 21st
Maximum solar heat gain factor (MAX_SHGFsh) for 140 W/m2
Maximum
the shadedsolar
areaheat gain21factor
on July st (MAX_SHGFsh) for 140 W/m2
External the shaded
Colour area on
of outside July 21st
surface Dark
Wall
External Colour
U valueof outside surface Dark
1.5 W/m2.K
Wall
Occupants U
Heat gain of each office worker
value Sensible:
1.5 W/m265 .K W
Latent: 55 W
Occupants Heat gain of each office worker Sensible: 65 W
Adjacent U value 3 W/m 55
Latent:
2
.K W
Walls Air temperature differences between the two 5
Adjacent U value rooms
adjacent 3 W/m2.K
Walls
41
Tables for sunlit areas of the windows, CLF and CLTD
Time (hr) 12 13 14 15 16 17 18 19
Sunlit area (m2) 0 3 5 6.5 7 7 7 0
Window CLF for window 0.17 0.31 0.53 0.72 0.82 0.81 0.61 0.16
CLTD for
window (K) 5 7 7 8 7 6 6 5
External CLTD for wall
Wall (K) 15 14 14 14 15 17 19 22
CLF for lights
Lights (Note 1) 0.81 0.83 0.84 0.86 0.87 0.89 0.25 0.22
CLF for
occupants (Note
Occupants 1) 0.77 0.80 0.83 0.85 0.87 0.89 0.42 0.34
42
Solution for the example question 2
At 14:00, the cooling load includes the following components:
Type 1: The cooling load due to the solar heat gain through fenestration
(such as window) area
𝑾 𝟐 𝟐 𝑾
( 𝟐
)
𝑸˙ 𝒔𝒆𝒏𝒔𝑪𝑳,𝑻𝒚𝒑𝒆𝟏=𝑸˙ 𝒔𝒆𝒏𝒔𝒉𝒆𝒂𝒕𝒈𝒂𝒊𝒏∙𝑪𝑳𝑭=( 𝑨𝒔∙ 𝑴𝑨𝑿𝑺𝑯𝑮𝑭+𝑨𝒔𝒉∙ 𝑴𝑨𝑿𝑺𝑯𝑮𝑭𝒔𝒉)∙𝑺𝑪∙𝑪𝑳𝑭= 𝟓𝒎 ∙𝟔𝟕𝟐 𝟐 +(𝟕𝒎 −𝟓𝒎 )∙𝟏𝟒𝟎 𝟐 ∙𝟎.𝟓𝟓∙𝟎.𝟓𝟑=𝟏𝟎𝟔𝟏.𝟎𝟔𝑾
𝒎 𝒎
Type 2: The cooling load due to the equiv. conduction heat gain through
fenestration area
˙ 𝟐 𝑾
𝑸 𝒔𝒆𝒏𝒔 𝑪𝑳, 𝑻𝒚𝒑𝒆 𝟐 = 𝑨 𝒇 ∙ 𝑼 ∙ 𝑪𝑳𝑻𝑫= 𝟕 𝒎 ∙𝟓 𝟐
∙ 𝟕 𝑲 = 𝟐𝟒𝟓 𝑾
𝒎 𝑲
43
Type 3: The cooling load due to the equivalent conduction heat gain
through the external wall.
𝟐 𝑾
𝑸 𝒔𝒆𝒏𝒔 𝑪𝑳, 𝑻𝒚𝒑𝒆 𝟑 =𝑨 ∙𝑼 ∙ 𝑪𝑳𝑻𝑫 =𝟖 𝒎 ∙ 𝟏 .𝟓 𝟐 ∙𝟏𝟒 𝑲=𝟏𝟔𝟖𝑾
˙
𝒎 𝑲
Type 4: The cooling load due to the heat gain from the adjacent rooms
via the partition walls
𝟐 𝑾
𝑸˙ 𝒔𝒆𝒏𝒔 𝑪𝑳,𝑻𝒚𝒑𝒆 𝟒=𝑨∙𝑼 ∙ ( 𝒕𝒂𝒅𝒋 −𝒕 𝒓 )=( 𝟑×𝟏𝟓𝒎 ) ×𝟑 𝟐 ×𝟓 𝑲=𝟔𝟕𝟓𝑾
𝒎𝑲
44
Type 5: The cooling load due to the heat gain from the occupants
45
Type 6: The cooling load due to the heat gain from the electric lights
Type 7: The cooling load due to the sensible heat gain from equipment and
appliances
For the equipment such as
46
Therefore, at 14:00, the total sensible and latent cooling
loads can be calculated as follows:
47
Continuous Question of the Example Question 2:
If the infiltration is 0.2 ACH (Air change rate per hour), what is the
total sensible and latent cooling loads at 14:00?
It is assumed that at 14:00, the indoor and outdoor air has the
following conditions:
Indoor Outdoor
Dry bulb air 25.5 30
temperature (C)
Absolute humidity 10.23 18.87
ratio (g/kg dry air)
48
Review for the Type 8: The cooling load due to the infiltration 49
is the volume flow rate of the infiltrated air, unit in m3/s
is the density of air, unit in [kg/m3], around 1.2 kg/m3 under 15-30 ºC and 1 atm . For detailed
value, please check the Engineering Table.
is the specific heat capacity of air, unit in [J/kg.K], 1000 J/kg.K under 25 ºC and 1 atm. For
detailed value, please check the Engineering Table.
is the dry bulb temperature of the outdoor air, unit in ºC
is the dry bulb temperature of the room air, unit in ºC
is the absolute humidity ratio of the outdoor air, unit in kg/kg dry air.
is the absolute humidity ratio of the room air, unit in kg/kg dry air.
is the latent heat of evaporation per unit mass of vapor, h fg = 2400 kJ/kg = 2.4 x 106 J/kg.
Solution
Type 8: The cooling load due to the infiltration
Space sensible cooling load due to the
infiltrated air (W)
𝑸˙ 𝒔 𝒆𝒏𝒔 𝑪𝑳=𝑽˙ 𝒊𝒇 𝝆𝒐 𝒄 𝒑 ( 𝒕 𝒐 − 𝒕 𝒓 )
kg/m3 𝒕 𝒐=𝟑𝟎 ℃
J/kg.K 𝒕 𝒓=𝟐𝟓 . 𝟓 ℃
According to the question statement:
Pay attention
to the SI unit
Space latent cooling load due to the during the
infiltrated air (W) calculation
−𝟑 −𝟑 𝟔
˙𝑸𝒍𝒂𝒕𝒆𝒏𝒕𝑪𝑳=𝑽˙ 𝒊𝒇 𝝆𝒐(𝒘𝒐−𝒘𝒓)𝒉𝒇𝒈,𝒐=𝟎.𝟎 𝟑𝟐 𝟖×𝟏.𝟐×(𝟏𝟖.𝟖𝟕×𝟏𝟎 −𝟏𝟎.𝟐𝟑×𝟏𝟎 )×𝟐.𝟒×𝟏𝟎 =𝟖𝟎.𝟑𝟐𝑾
51
Therefore, at 14:00, the total sensible and latent cooling
loads can be calculated as follows:
52
Tutorial question
53
Based on the Example Question 2 and assume that the
infiltration is negligible, please calculate the following
questions:
54
Parameters Values
Window
Window U
U value
value 5
5 W/m
W/m2.K
2
.K
Shading
Shading coefficient
coefficient (SC)
(SC) 0.55
0.55
Maximum solar heat gain factor (MAX_SHGF) for the 672 W/m22
Maximum
sunny areasolar heat
of the gain factor
west-facing (MAX_SHGF)
window on July for
21stthe 672 W/m
sunny area of the west-facing window on July 21st
Maximum solar heat gain factor (MAX_SHGFsh) for 140 W/m2
Maximum
the shadedsolar
areaheat gain21factor
on July st (MAX_SHGFsh) for 140 W/m2
External the shaded
Colour area on
of outside July 21st
surface Dark
Wall
External Colour
U valueof outside surface Dark
1.5 W/m2.K
Wall
Occupants U
Heat gain of each office worker
value Sensible:
1.5 W/m265 .K W
Latent: 55 W
Occupants Heat gain of each office worker Sensible: 65 W
Adjacent U value 3 W/m 55
Latent:
2
.K W
Walls Air temperature differences between the two 5
Adjacent U value rooms
adjacent 3 W/m2.K
Walls
55
Tables for sunlit areas of the windows, CLF and CLTD
Time (hr) 12 13 14 15 16 17 18 19
Sunlit area (m2) 0 3 5 6.5 7 7 7 0
Window CLF for window 0.17 0.31 0.53 0.72 0.82 0.81 0.61 0.16
CLTD for
window (K) 5 7 7 8 7 6 6 5
External CLTD for wall
Wall (K) 15 14 14 14 15 17 19 22
CLF for lights
Lights (Note 1) 0.81 0.83 0.84 0.86 0.87 0.89 0.25 0.22
CLF for
occupants (Note
Occupants 1) 0.77 0.80 0.83 0.85 0.87 0.89 0.42 0.34
56
Solution for the example question 1, take 16:00 as an example:
At 16:00, the cooling load includes the following components:
Type 1: The cooling load due to the solar heat gain through fenestration
(such as window) area
𝑾 𝟐 𝟐 𝑾
( 𝟐
)
𝑸˙ 𝒔𝒆𝒏𝒔𝑪𝑳,𝑻𝒚𝒑𝒆𝟏=𝑸˙ 𝒔𝒆𝒏𝒔𝒉𝒆𝒂𝒕𝒈𝒂𝒊𝒏∙𝑪𝑳𝑭=( 𝑨𝒔∙ 𝑴𝑨𝑿𝑺𝑯𝑮𝑭+𝑨𝒔𝒉∙ 𝑴𝑨𝑿𝑺𝑯𝑮𝑭𝒔𝒉)∙𝑺𝑪∙𝑪𝑳𝑭= 𝟕𝒎 ∙𝟔𝟕𝟐 𝟐+(𝟕𝒎 −𝟕𝒎 )∙𝟏𝟒𝟎 𝟐 ∙𝟎.𝟓𝟓∙𝟎.𝟖𝟐=𝟐𝟏𝟐𝟏.𝟓𝟎𝟒𝑾
𝒎 𝒎
Type 2: The cooling load due to the equiv. conduction heat gain through
fenestration area
˙ 𝟐 𝑾
𝑸 𝒔𝒆𝒏𝒔 𝑪𝑳, 𝑻𝒚𝒑𝒆 𝟐 = 𝑨 𝒇 ∙ 𝑼 ∙ 𝑪𝑳𝑻𝑫= 𝟕 𝒎 ∙𝟓 𝟐
∙ 𝟕 𝑲 = 𝟐𝟒𝟓 𝑾
𝒎 𝑲
57
Type 3: The cooling load due to the equivalent conduction heat gain
through the external wall.
𝟐 𝑾
𝑸 𝒔𝒆𝒏𝒔 𝑪𝑳, 𝑻𝒚𝒑𝒆 𝟑 =𝑨 ∙𝑼 ∙ 𝑪𝑳𝑻𝑫 =𝟖 𝒎 ∙ 𝟏 .𝟓 𝟐 ∙𝟏 𝟓 𝑲 =𝟏𝟖𝟎 𝑾
˙
𝒎 𝑲
Type 4: The cooling load due to the heat gain from the adjacent rooms
via the partition walls
𝟐 𝑾
𝑸˙ 𝒔𝒆𝒏𝒔 𝑪𝑳,𝑻𝒚𝒑𝒆 𝟒=𝑨∙𝑼 ∙ ( 𝒕𝒂𝒅𝒋 −𝒕 𝒓 )=( 𝟑×𝟏𝟓𝒎 ) ×𝟑 𝟐 ×𝟓 𝑲=𝟔𝟕𝟓𝑾
𝒎𝑲
58
Type 5: The cooling load due to the heat gain from the occupants
59
Type 6: The cooling load due to the heat gain from the electric lights
Type 7: The cooling load due to the sensible heat gain from equipment and
appliances
For the equipment such as
60
Therefore, at 16:00, the total sensible and latent cooling
loads can be calculated as follows:
61
For the cooling load at other hour, the calculation procedure is all the same
expect the factors shown in Slide 56. By calculating the cooling load one by one,
we can get the table in the following slide.
Generally, the cooling load has an increment in the morning and reaches at the
highest level in the afternoon (maybe between 2:00 pm to 6:00 pm). Then, it will
gradually decreases to a low level, which is closely related with the intensity of
solar radiation. As a result, to determine the maximum cooling load, we only
calculate the values from 12:00 to 19:00 rather than the whole day.
62
Solution of the tutorial question:
(1) If the space air temperature is maintained constant during 24 hour period:
The 8 components of the cooling load can be calculated for each hour, as listed in the
following two Tables for the sensible and latent loads:
Table for the Sensible Cooling Load
Time 12 13 14 15 16 17 18 19
Sens CL Sens CL Sens CL Sens CL Sens CL Sens CL Sens CL Sens CL
Type 1: The cooling load due to the
solar heat gain through fenestration
(such as window) area 91.63 439.208 1061.06 1757.448 2121.504 2095.632 1578.192 86.24
Type 2: The cooling load due to the
equiv. conduction heat gain through
fenestration area 175 245 245 280 245 210 210 175
Type 3: The cooling load due to the
equivalent conduction heat gain
through the external wall. 180 168 168 168 180 204 228 264
Type 4: The cooling load due to the
heat gain from the adjacent rooms via
the partition walls 675 675 675 675 675 675 675 675
Type 5: The cooling load due to the
heat gain from the occupants 150.15 156 161.85 165.75 169.65 173.55 81.9 66.3
Type 6: The cooling load due to the
heat gain from the electric lights 648 664 672 688 696 712 200 176
Type 7: The cooling load due to the
sensible heat gain from equipment
and appliances 240 240 240 240 240 240 240 240
Type 8: The cooling load due to the
infiltration 0 0 0 0 0 0 0 0
Sum of Sens CL (W) 2159.78 2587.208 3222.91 3974.198 4327.154 4310.182 3213.092 1682.54
63
Table for the Latent Cooling Load
Time 12 13 14 15 16 17 18 19
Latent Latent Latent Latent Latent Latent Latent
Latent CL CL CL CL CL CL CL CL
Type 1: The cooling load due to
the solar heat gain through
fenestration (such as window)
area
Type 2: The cooling load due to
the equiv. conduction heat gain
through fenestration area
Type 3: The cooling load due to
the equivalent conduction heat
gain through the external wall.
Type 4: The cooling load due to
the heat gain from the adjacent
rooms via the partition walls
Type 5: The cooling load due to
the heat gain from the occupants 165 165 165 165 165 165 165 165
Type 6: The cooling load due to
the heat gain from the electric
lights
Type 7: The cooling load due to
the sensible heat gain from
equipment and appliances
Type 8: The cooling load due to
the infiltration 0 0 0 0 0 0 0 0
Sum of Latent CL (W) 165 165 165 165 165 165 165 165
64
Summary Table for the Sensible, Latent and Total Cooling Load
Time 12 13 14 15 16 17 18 19
Sum of Sens CL (W) 2159.78 2587.208 3222.91 3974.198 4327.154 4310.182 3213.092 1682.54
Sum of Latent CL (W) 165 165 165 165 165 165 165 165
Sum of Cooling Loads (W) 2324.78 2752.208 3387.91 4139.198 4492.154 4475.182 3378.092 1847.54
65
(2) If the air-conditioning plant is shut down during night-time and weekend
The CLF for the heat gains of the occupants, electric lighting, and equipment
will be equal to 1.0 (refer to Slide 32, 35, 37)
67
Type 6: The cooling load due to the heat gain from the electric lights
Type 7: The cooling load due to the sensible heat gain from equipment and
appliances
For the equipment such as
For the cooling load at other hour, the calculation procedure is all the same expect
the factors shown in Slide 66. By calculating the cooling load one by one, we can get
the table in the following slide.
68
Table for the Sensible Cooling Load
Time 12 13 14 15 16 17 18 19
Sens CL Sens CL Sens CL Sens CL Sens CL Sens CL Sens CL Sens CL
Type 1: The cooling load due to the
solar heat gain through fenestration
(such as window) area 91.63 439.208 1061.06 1757.448 2121.504 2095.632 1578.192 86.24
Type 2: The cooling load due to the
equiv. conduction heat gain through
fenestration area 175 245 245 280 245 210 210 175
69
Table for the Latent Cooling Load
Time 12 13 14 15 16 17 18 19
Latent CL Latent CL Latent CL Latent CL Latent CL Latent CL Latent CL Latent CL
Type 1: The cooling load due to the
solar heat gain through fenestration
(such as window) area
Type 2: The cooling load due to the
equiv. conduction heat gain through
fenestration area
70
Summary Table for the Sensible, Latent and Total Cooling Load
Time 12 13 14 15 16 17 18 19
Sum of Sens CL (W) 2356.63 2762.208 3384.06 4115.448 4456.504 4419.632 3926.192 2435.24
Sum of Latent CL (W) 165 165 165 165 165 165 165 165
Sum of Cooling Loads (W) 2521.63 2927.208 3549.06 4280.448 4621.504 4584.632 4091.192 2600.24
71
Thank you very much for your attention
72