Centum CS3000 Tranning
Centum CS3000 Tranning
Centum CS3000 Tranning
1998
CENTUM-XL
CENTUM (2 )
ND
1988 1993
1984
1981
1975
CENTUM
CENTUM V
Equipment Nomenclature
Human Interface Stations (HIS)
The HIS is mainly used for operation and monitoring – it displays process variables,
control parameters, alarm, trend windows, etc.
There are two types of HIS:
• Console Type
Enclosed Display Console Open Display Console
• Desktop Type
SYSTEM CONFIGURATION
Equipment Nomenclature
Field Control Station (FCS)
The FCS is the controller that executes control strategy and computation to control
the plant.
LFCS (with RIO) KFCS (with FIO) FFCS
(Compact FCS for FIO)
FIO
SYSTEM CONFIGURATION
Equipment Nomenclature
Engineering PC (ENG or EWS)
This is the PC with engineering functions used to perform Centum CS3000 system
generation and maintenance management.
It can be the same type of general-purpose PC as the HIS and can even be the same
PC as the HIS. By having HIS operation and monitoring functions on the same PC,
you can use the test (control station emulation) functions to provide an efficient and
easy-to-use engineering environment.
SFC
Logic Chart
Control
Drawing
SYSTEM CONFIGURATION
Equipment Nomenclature
EXAOPC
This provides OPC server functions to enable applications in a supervisory PC to
access Centum CS3000 data. It provides a link between control layer and business
data processing layer.
SYSTEM CONFIGURATION
Vnet Bus
SYSTEM CONFIGURATION
Vnet I/P
ENG/HIS
Bus 2 Bus 1
(Open Communication) (Control Communication)
L2 switch L2 switch
FCS(FFCS-L)
SYSTEM CONFIGURATION
Vnet I/P
ENG
HIS
Foreign system
SYSTEM SPECIFICATION
Scale
256 stations / system
16 domains / system
64 stations / domain
100.000 tags (expandable up to 1.000.000 tags)
Domain Structure
Centum CS3000 to Centum CS3000 (multiple domain)
Centum CS3000 to other Yokogawa legacy system
(Centum CS, Centum XL, µXL)
Inter-domain communication by using Bus Converter
Control Bus
High Speed (10Mbps) real time network (V-net) (10-B-5, 10-B-
2)
High Speed (1Gbps) for Vnet/IP (100-B-T or 1000-B-T))
Maximum length 20 Km (with repeater / optical)
SYSTEM SPECIFICATION
DOMAIN INTEGRATION
L3 switch
1 Gbps
Domain 1
Domain 2
INTEGRATION WITH OTHER PCS
With the use of industry standard OPC interfaces, maximum connectability with other systems
can be established at a minimum engineering cost. There is no need to create specific programs
for the CS 3000 to access data on other systems. The OPC DA 2.0 interface prescribed by the
OPC Foundation is used to access the OPC DA server of other vendors’ systems and acquire
process data. The OPC A&E 1.1 interface is used to access the OPC A&E server and collect event
and alarm messages.
HARDWARE DESCRIPTION - FCS
Battery
Unit
RIO Bus
Coupler Input-Output
Module/Node.
(Cabinet mounting type)
Input-Output Module/Node.
(19” Rack mounting type)
HARDWARE DESCRIPTION - FCS
ESB Bus
Coupler Unit
Power Supply
FIO
Module
ESB Bus
Module
I/O
Modules
HARDWARE DESCRIPTION - FCS
I/O Modules
Node Expansion
Modules (ESB)
Control
Processor Cards
CONTROLLER ARCHITECTURE - FCS
Bus 1 Vnet
FCU / CPU Bus 2
ESB Bus
I/O Racks
Dual redundant
Single or dual redundant Trans. Speed: 128 Mbps
power supplies
Trans. distance :10 meter
Dual redundant I/O bus
8 I/O slots per node/rack
10 nodes/racks per FCS
(expandable to 15)
HKU
19 “ standard panel
Fan/air temperature
Fans speed
CONTROLLER ARCHITECTURE - FIO
DESKTOP
TYPE
DISPLAY #2
CS3000 SOFTWARE – Operation Panel With Intuitive
Navigation
Monitor your process alarm conditions. Filter by tag, process Long-term trend available
area, control station or tag importance is available. Operator definable
CS3000 SOFTWARE - Security
Auxiliary Tag2
(Logging Alarm)
Centum Software – Virtual Test Function
Engineering function