Interface Cabling Options

for 9910-P13 & P14 UPS

i5-iSeries and p5-pSeries


and Windows
Selecting Which Interface (Communication)
Option is Best for You

© 2002 Eaton Corporation. All rights reserved.


Receiving the UPS

UPS will be installed on floor

Connections that need to be completed

Power
• UPS to utility (mains)
• UPS to Devices

Interface (communications)
• UPS to server(s)

9910-UPS Training
2 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Getting Acquainted

UPS must installed near devices to be protected
• Communication and power connections made at rear of UPS

What a P13 and P141 UPS looks like from the rear

P14
P13 1
P14 includes three (3) IEC-320-C13 to
IEC-320-C14 1.8 m power cords 9910-UPS Training
3 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Communication Options
Software Suite AS/400 Interface
Application CD & Serial Cable Cable
IBM i5/iSeries
Server - X

IBM p5/pSeries, OpenPower


or xSeries Server with Single
Serial (TTY) connection X -
IBM p5/pSeries, OpenPower
or xSeries Server and/or Network
(WebServer) connection
(UPS as a node) X -
IBM p5/pSeries, OpenPower
with Logical Partitions (LPARs) Not Supported

9910-UPS Training
4 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
i5 Interface Overview

To connect the UPS to an
i5 you need:

A Powerware-supplied
interface cable (labeled
05146792)

An IBM-supplied interface
cable (labeled 1827),
included with the server

Connect the cables as
shown in Figure 1

9910-UPS Training
5 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
iSeries Interface Overview

To connect the UPS to an
iSeries or AS/400 you
need:

A Powerware-supplied
interface cable (labeled
05146792)

Connect the cable as
shown in Figure 2

9910-UPS Training
6 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
UPS Monitoring on the i5, iSeries
and AS/400
1. Set the QUPSDLYTIM system value for the UPS monitoring
feature.
2. UPS monitoring is a standard feature of the i5-iSeries-
AS/400 operating system. QUPSDLYTIM is a time that tells
the system how long to run on UPS power before shutting
down. Each system is initially assigned a default value for
QUPSDLYTIM. A complete description of QUPSDLYTIM is
proved on the AS/400 Information Center Internet Site at:
http://publib.boulder.ibm.com/pubs/html/as400ic2924/info/index.htm
Select System Administration and Maintenance
CAUTION

The *NOMAX value tells the AS/400 to use customized shutdown software, and if
non is available it will begin shutdown immediately when utility power fails.

9910-UPS Training
7 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Serial (TTY) Interface Overview

To serially (TTY) connect the UPS to a p5, pSeries, RS/6000,
OpenPower, or other system you need:

A Powerware-supplied serial interface cable (labeled 60420064-002 or
124102022), included with the UPS

Powerware LanSafe Power Management Software from the Software
Suite CD, included with the UPS
For p5 installations you also need:

An IBM-supplied 2-port Asynchronous EIA adapter (FC 5723) installed
(the pSeries does not require an EIA adapter)

An IBM-supplied maintenance package 5200-05 for AIX 5.2L V5.2
(APAR IY66260); or, the maintenance package 5300-01 for AIX 5.3L
V5.3 (APAR IY62267)
Follow the software installation instructions contained on the Software
Suite CD to install LanSafe Software.

Connect the serial cable as shown in Figure 3
9910-UPS Training
8 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Serial (TTY) Interface Overview

9910-UPS Training
9 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
p5 or pSeries with LPARs

The UPS does not support Logical Partitions.
LPARs are supported on UPS models 9910-P22,
P23, P30, P33, P64 or P65 with the ConnectUPS
X-Slot Web/SNMP Card (FC 2934)

9910-UPS Training
10 Interface Cabling Options for P13 & P14 rev 3 - Barry Gruetzmacher – September 2005
Completing Start-Up

You have finished the power and connectivity
installation process

Continue with Start-up instructions in User’s
Manuals