Earthing System - Maintenance
Earthing System - Maintenance
Earthing System - Maintenance
Maintenance
Er. K.V.SURYA PRAKASA RAO
Earthing Systems:
Electrical earthing is designed primarily to render electrical installation safe. The
purpose of earthing are :
1. Protection to the plant
2. Protection to the personnel and
3. Improvement in service reliability
Non- current carrying parts with conducting surface such as tanks of Power
Transformers, and frame work of circuits breakers, structural steel work in
switch yard instrument transformer cases, lightning arresters and armored
cables armoring should be effectively grounded for protection of equipments
and operating personnel. Earth connections of all equipments should be
made in duplicate.
Connecting lead should have sufficient current carrying capacity.
L A s should have independent earth electrode which should be inter connected
to the station grounding system.
All paints, enamel, seals should be removed from the point off contact of metal
surfaces before earth connections are made.
The resistances of earth system should not exceed 2 ohms for 33/11 KV Sub
Stations.
But in the sub stations of Distribution companies Earth resistance Maximum of 1
Ohm is maintained.
Suitable grounding mat should be provided in the sub station yard.
In a Sub Station the following shall be earthed.
During ground fault conditions, the fault current flows via the
system ground. When the system and safety grounds are inter
connected, the fault current flowing (via) the system ground
rises the potential of the safety ground. Also the flow of
current to safety ground results in hazardous potential gradient
in and around sub station. In view of the above it is some
times suggested that separate system and safety grounds will
avoid the danger arising due to potential gradients. The idea is
that by connecting the system ground to a separate earthing
system situated in a in accessible spot, the ground fault current
does not flow through the safety ground. However, this
separate system of grounds has many disadvantages and can
be more hazardous as mentioned below
With separate grounds we can avoid danger due to potentials
only for faults outside the stations.
Short circuit currents will be more if the fault occurs in the
sub stations.
The resistance may be more and in some cases sufficient
currents may not flow to operate the relays.
For effective separation of the earthing systems, the system
ground shall be installed at a distance of at least twice the
diagonal length of the sub station which is covered by safety
grounding. The neutral of the transformer has to be
connected to this remote earthing by means of insulated
leads. Even with this arrangement one cannot always be
sure about the complete isolation of the two systems and
there is always a chance of inadequate electrical connection
through buried neutral pipes etc., Hence, this is
impracticable, complicated and costly. It is therefore a
common practice to install a common grounding system and
design the same for effective earthing and safer potential
gradients.
System Earthing
Neutral connection earth pipe shall never be used for the equipment
earthing.
A separate earth electrode shall be provided adjacent to the structures
supporting Lightning Arrestors. Earth connection shall be as short and
as straight as practicable. For arrestors mounted near for protecting
transformers earth conductors shall be connected directly to the tank.
An Earthing pad shall be provided under each operating handle of the
isolator and operating mechanism of the circuit breakers. Operating
handle of the isolator and supporting structures shall be bonded together
by a flexible connection and connected to the earthing grid.
All equipment and switchgear etc., erected shall be earthed as per I.E
Rules 1956.