Current and Voltage Transformers New
Current and Voltage Transformers New
Transformers
• THE RIGID interconnectivity existing among modern power systems make
them highly unstable when, faults are not cleared rapidly.
• If a fault in an important transmission line is not identified and removed at the
shortest possible time, it might lead to a widespread damage in the power system.
• The job of the protective relays is to identify and isolate the faults in power system
networks.
• The unpredictable nature of the power system signals during faults, make their
extraction a challenging job.
• In order to prevent the damages from spreading to the healthy parts of the power
system, the protective relaying algorithms need to detect the faults within sub
cycles of the power system frequency.
• .
• Electric power utilities use electromechanical and solid-state relays for protecting
power systems.
• Current transformers (CTs) are the basic interconnection between the power
system and almost all measurement devices such as protective relays.
• CTs step the primary current down to a nominal secondary level for use by
protective relays, meters, and other monitoring devices.
• One of the practical concerns for the protection engineer is the actual ability of a
CT to replicate the primary current With the advent of microprocessor
technology.
• Researchers and designers have made significant progress in designing
microprocessor-based relays that are expected to provide fast and accurate fault
detection.
Introduction
• Practically all electrical measurements and relaying decisions are derived from current
and voltage signals.
• Since relaying hardware works with smaller range of current (in amperes and not kA)
and voltage (volts and not kV), real life signals (feeder or transmission line currents)
and bus voltages have to be scaled to lower levels and then fed to the relays.
• This job is done by current and voltage transformers (CTs and VTs).
• CTs and VTs also electrically isolate the relaying system from the actual power
apparatus.
• The electrical isolation from the primary voltage also provides safety of both human
personnel and the equipment.
• Thus, CT and VTs are the sensors for the relay.
• CT and VT function like ‘ears' and the ‘eyes' of the protection system.
• They listen to and observe all happening in the external world.
• Relay itself is the brain which processes these signals and issues decision commands
implemented by circuit breakers, alarms etc.
current transformer
• Total load in ohms that is introduced by CT in series with the transmission line is insignificant
and hence, the connection of the CT does not alter current in the feeder or the power
apparatus at all.
• Hence from modeling perspectives it is reasonable to assume that CT primary is connected to
a current source.
• Therefore, the CT equivalent circuit will look as shown in fig below.
• The remaining steps in modeling are as follows: As impedance in series with the current
source can be neglected, we can neglect the primary winding resistance and leakage
reactance in CT modeling.
• For the convenience in analysis, we can shift the magnetizing impedance from the primary
side to the secondary side of the ideal transformer.
Equivalent Circuit of CT
•After application of the above steps, the CT equivalent circuit is as shown in the fig
above.
•Note that the secondary winding resistance and leakage reactance is not neglected
as it will affect the performance of CT.
•The total impedance on the secondary side is the sum of relay burden, lead wire
resistance and leakage impedance of secondary winding.
•Therefore, the voltage developed in the secondary winding depends upon these
parameters directly.
•The secondary voltage developed by the CT has to be monitored because as per the
transformer emf equation, the flux level in the core depends upon it. The transformer
emf equation is given by,
• If corresponding to this flux is above the knee point, it is more or less obvious
that the CT will saturate.
• During saturation, CT secondary winding cannot replicate the primary current
accurately and hence, the performance of the CT deteriorates.
• Thus, we conclude that in practice, while selecting a CT we should ascertain that it
should not saturate on the sinusoidal currents that it would be subjected to. Use of
numerical relays due to their very small burden vis-a-vis solid state and
electromechanical relays, improves the CT performance.
• CT is to be operated always in closed condition.
• If the CT is open circuited, all the current Ip/N, would flow through Xm.
• This will lead to the development of dangerously high level of voltage in secondary
winding which can even burn out the CT.
Performance of CT
• The performance of a current transformer used in protective relaying is largely
dependent on the total burden or impedance in the secondary circuit of the current
transformer.
• The current transformer core flux density (and thus the amount of saturation) is
directly proportional to the voltage that the current transformer or secondary must
produce.
• So for a given amount of secondary current, the larger the burden impedance
becomes, the greater is the tendency of the current transformer to saturate.
• Ideally, protective relay systems would ignore current transformer saturation.
• However, that is usually not possible; so it is the task of the relay engineer to
minimize current transformer burden impedance.
• Manufacturers' publications give the burdens of individual relays, meters, and
other equipment.
• Adding the resistance of interconnecting leads and internal resistance of the
current transformer gives the total current transformer burden.
• In modern microprocessor relays with very small burdens, the total relay burden is
often dominated by the lead impedance or internal CT impedance.
Knee Point Voltage of Current Transformer
• But still there is a limit as because, it is impossible to make one magnetic core
with infinitely high saturation level and secondly most important reason is that
although the protection care should have high saturation level but that must be
limited up to certain level otherwise total transformation of primary current
during huge fault may badly damage the protection relays.
• So it is clear from above explanation, rated accuracy limit primary current,
should not be so less, that it will not at all help the relays to be operated on the
other hand this value must not be so high that it can damage the relays.
• for a protection grade CT, linear response is expected up to 20 times the rated
current.
• Its performance has to be accurate in the range of normal currents and up to
fault currents.
• Specifically, for protection grade CT's magnetizing impedance should be
maintained to a large value in the range of the currents of the order of fault
currents.
Classification of CTs
• Suppose you have one CT with current ratio 400/1A and its protection core is
situated at 500A.
• If the primary current of the CT becomes 1000A the secondary current will still be
1.25A as because the secondary current will not increase after 1.25A because of
saturation.
• If actuating current of the relay connected the secondary circuit of the CT is 1.5A,
it will not be operated at all even fault level of the power circuit is 1000A.
• The degree of accuracy of a Protection CT may not be as fine as Metering CT but it
is also expressed by CT Accuracy Class or simply Current Transformer Class or CT
Class as in the case of Metering Current Transformer but in little bit different
manner.
Instrument Security Factor or ISF of Current Transformer
• As the maximum electric current can flow through the instrument connected to the
first CT is 1.5A which is less than the maximum value of electric current can flow
through the instrument connected to the second CT i.e. 2A.
• Hence security or safety of the instruments of first CT is better than later.
• Another significance of ISF is during huge electrical fault, the short circuit current,
flows through primary of the CT does not affect destructively, the measuring
instrument attached to it as because, the secondary current of the CT will not rise
above the value of rated secondary current multiplied by ISF
• Protection class CTs are designed to work in the linear range, with minimal errors
and minimal waveform distortion, only up to 20 times the rated nominal current
with the burden as defined by the relay class (saturation voltage) of the CT per
IEEE Std. C57.13.
Classification of CTs
• ANSI / IEEE classification
• ANSI/IEEE standards classify CTs into two
types:
• Class T CT
• Class C CT
Class T CTs
• Typically, a class T CT is a wound type CT with one or more primary turns wound on a core.
• It is associated with high leakage flux in the core.
• Because of this, the only way to determine it's performance is by test.
• In other words, standardized performance curves cannot be used with this types of CTs.
Answer:
CT ratio = 1200/5
Secondary resistance = 0.61
Relay burden = 2
For 20 times rated secondary current, i.e., 100A
Secondary voltage = 100 x (2 + 0.61) = 261 Volts which is less than knee point of the CT.
• Since this voltage is less than 400V, from electrical perspective, linearity will not be lost at
even higher currents.
• Approximate limit on secondary current is given by .
• Hence maximum symmetrical fault current = 36720A.
Example 2:
• A ,1200/5 C400 CT is connected on the 1000/5 tap. What is the maximum secondary burden
that can be used and we can maintain rated accuracy at 20 times rated symmetrical secondary
current?
The secondary voltage corresponding to the tap 1000/5,
=333 V
333 = 100(0.51+RB)
• To cut down the VT size and cost, a capacitance potential divider is used (fig 8.2).
• Thus, a reduced voltage is fed to primary of the transformer.
• This reduces the size of VT.
• This leads to development of coupling capacitor voltage transformers (CCVT).
CCVT
• It is now obvious that Zth due to the capacitance divider, affects the voltage
received by the relay.
• To achieve high level of accuracy, it is therefore necessary to compensate for this
voltage drop by connecting a tuning inductor.
• Under line fault conditions, when the voltage drops and there is no threat of
exceeding the knee-point of the magnetizing characteristic of the step-down
transformer, a CVT can be represented by the equivalent linear circuit as shown in
Figure.
• A CVT consists of the following components:
• Coupling capacitors (C1 and C2)
• Compensating reactor (L )
• Step-down transformer
• Ferro resonance-suppression circuit
• The coupling capacitors of the CVT function as a voltage divider to step down the
line voltage to an intermediate-Ievel voltage, typically 5 to 15 kV.
CCVT
then voltage drop across C is neutralized and the relay sees the actual voltage to be
measured. (See fig 8.5).
• When a fault suddenly reduces the line voltage, the CVT secondary output does not
instantaneously represent the primary voltage.
• This is because the energy storage elements, such as coupling capacitors and the
compensating reactor, cannot instantaneously change their charge or flux.
• These energy storage elements cause the CVT transients.
• Because these elements take time to change their stored energy , they introduce a transient to
the CVT output following a significant input voltage change.
• As can be seen in the fig 8.5, CCVT equivalent circuit is a R-L-C circuit.
• If transformer is considered ideal, it can be described by integro differential equation of the
type,
1 t di
v(t ) Ri
Ceq
idt L
dt
•
• The corresponding differential equation is given by
Transient Response of CCVT
•
Transient Response of CCVT
Transient Response of CCVT
CVT transients differ depending on the fault point-on-wave (POW) initiation.
The CVT transients for faults occurring at voltage peaks and voltage zeros are quite distinctive
and different.
Two CVT transients for zero-crossing and peak POW fault initiations are shown in the fig.. For
comparison, the ideal CVT voltage output (ratio voltage) is shown in each figure.
Figure 8.7 shows a CVT transient with a fault occurring at a voltage zero.
Also, notice that the CVT output does not follow the ideal output until 1.75 cycles after fault
inception.
Figure 8.8 shows the CVT response to the same fault occurring at a voltage peak. Again, the
CVT output does not follow the ideal output. The CVT transient for this case lasts about 1.25
cycles.
Transient Response of CCVT
• The high capacitance value in a CVT decreases the CVT transient in magnitude.
Transient Response of CCVT
• CVTs provide a cost-efficient way of obtaining secondary voltages for EHV systems.
• They create however, certain problems for distance relays.
• During line faults, when the primary voltage collapses and the energy stored in the stack
capacitors and the tuning reactor of a CVT needs to be dissipated, the CVT generates sever
transients that affect the performance of Protective relays.
• The CVT caused transients are of significant magnitude and comparatively long duration.
• This becomes particularly important for large Source Impedance Ratios (SIR — the ratio of
the system equivalent impedance and the relay reach impedance) when the fault loop
voltage can be as low as a few percent of the nominal voltage for faults at the relay reach
point.
• Such a small signal is buried beneath the CVT transient making it extremely difficult to
distinguish quickly between faults at the reach point and faults within the protection zone.
• Electromechanical relays can cope with unfavourable CVT transients due to their natural
mechanical inertia at the expense of slower operation.
• Digital relays are designed for high-speed tripping and therefore they face certain CVT
related problems.
• CVT transients can affect both the transient overreach (a relay operates during faults
located out of its set reach) and the speed of operation (slow tripping for high SIRs) and
directionality.
Classification of CCVTs
• By an overcompensation,
it is possible to give the CVT an inductive characteristic on the secondary side, in the
same way as for an inductive voltage transformer.
FREQUENCY DEPENDENCE OF A CVT
• The fundamental function of the CVT is resonance between the capacitive and
inductive reactance at rated frequency.
• It can therefore not be expected that the CVT will have the same accuracy for
frequencies deviating from the rated.
• The standards, IEC 60044-5, specifies that for a metering class the accuracy shall
be maintained for a frequency variation between 99-101% of rated frequency and
for protection class between 96-102%.
• The sensitivity for frequency variations is dependent on the equivalent capacitance
and the intermediate voltage.
• High values give a lower sensitivity and smaller variations.
• A purely resistive burden will give error variation only for phase displacement and
an inductive burden gives variation both in ratio and in phase.
ERROR VARIATION FOR TEMPERATURE CHANGES
• The temperature characteristic of a CVT is rather complex and only a few factors
influencing the errors of a CVT will be dealt with here.
• The capacitance of the CVD changes by temperature.
• The size of the change depends on the type of dielectric used in the capacitor
elements.
• The relation between capacitance and temperature can be written:
• Where α Temperature coefficient for the capacitor dielectri,c ∆T Temperature change
• The variation of capacitance means two different kinds of temperature dependence.
• If the two capacitors C1 and C2 in the voltage divider can get different temperature
or if they, due to design, have different values of α, the voltage ratio of the CVT
changes by temperature.
• This will have an influence on the ratio error
• It is therefore essential that the design is such that all capacitor elements have the
same dielectric and have the same operating conditions.
• CVD’s having C1 and C2 enclosed in the same porcelain have shown very good
temperature stability.
ERROR VARIATION FOR TEMPERATURE CHANGES
• This temperature dependence influences the tuning of the CVT and gives additional
errors of the same kind as for frequency variations and is proportional to the connected
burden.
• Low temperature coefficient is essential to keep these variations small.
• A third remaining factor influencing the errors, is the change of winding resistance
• in the tuning inductor due to temperature variations.
LEAKAGE CURRENTS AND STRAY CAPACITANCE
• At altitudes above 3300 feet, the flashover value of air-insulated equipment has
decreased appreciably. To compensate for this decrease, additional insulation may
be provided for the line and for the other terminal equipment.
• This may require the next higher standard voltage rating for the coupling capacitor,
and it is the practice to specify the next higher rating if the altitude is known to be
over 3300 feet.
Standard Withstand Test Voltages for Coupling Capacitors
What is a non-conventional instrument transformer
• Today a number of different sensors and technologies are used which are gathered
under the general umbrella of non-conventional instrument transformers.
• They range from traditional cores and dividers having an output at lower levels
than present day standards, via air core coils to optical units employing electro- or
magneto optical effects.
• Each technology has its advantages and disadvantages.
• The future will probably show that each different technology will be used in the
areas where their specific advantages are useful.
• Another typical feature of modern non-conventional transformers is that the
measured signal in many products is transmitted through an optical fibre from the
high potential level to the instrumentation potential in the substation.
• This significantly reduces the insulation problem associated with traditional
transformers.
•ABB currently have several commercial concepts, DOIT (Digital
Optical Instrument Transformers ), MOCT and FOCS.
•These are potentially applicable to digital metering and protection
when the new IEC 61850 is introduced.
•Currently, the DOIT is only used in HVDC applications.
•The FOCS system are currently available for industrial DC
applications.
•AC applications for metering and protection are being developed.
OPTICAL INSTRUMENT TRANSFORMER
• In recent years, electric utilities have been evaluating optical sensors to measure current and
voltage.
• These devices are proving their value, especially in applications where accurate measurement
over wider dynamic range, ability to retrofit, and improved safety are of main concern.
• They are well suited for the advanced functionality of leading-edge protective relays and
meters and for compatibility with digital communications in modern substations.
• The NxtPhase NXVCT optical voltage and current sensor, for example, combines voltage
and current sensing (protection and metering) in a single instrument for each of several volt-
age classes over the range from 115kV to 765kV.
• Primary advantages of this optical technology over conventional inductive and capacitive
measurement transformers include:
• High accuracy (exceeds IEC Class 0.2 and IEEE Class 0.3 accuracy requirements)
• Wide dynamic range
• High bandwidth
OPTICAL INSTRUMENT TRANSFORMER
• Reduced size and weight
• Safe and environmentally friendly (avoids oil or SF6)
• Low maintenance
• Immunity against electromagnetic interferences (EMI);
• Electrical isolation (the optical sensors are made of dielectric materials);
• Possibility for measuring AC and DC;
• Absence of saturation effects;
• Low power consumption;
• relatively low cost
• During fault conditions a well-known phenomenon called “saturation” occurs in
conventional CTs; the iron core in a transformer “saturates” when high fault
currents induce a large magnetic field.
• In effect, the transformer can no longer accurately represent the primary current in
the current transformer secondary.
• Utilities must therefore select oversized CT ratios in order to avoid false relay
operation.
OPTICAL INSTRUMENT TRANSFORMER
• An optical CT does not face the same saturation challenges. It uses light travelling
through glass (an optical fibre in the case of the NXCT) to measure the magnetic
field around a current-carrying conductor, which gives a measure of the current
flowing in the conductor.
• If configured correctly, the optical voltage and current sensor has the ability to
measure fault currents exceeding 400 kA peak.
• Additionally, using advanced techniques, both AC and DC currents can be
measured accurately throughout this range.
• Furthermore they are usually connected to optical fibers that have large
communication bandwidths, and due to their very low absorption loss allow remote
detection, high multiplexing capability and data transmission over long distances.
• Also, optical current sensors measure the magnetic field generated by the electric
current rather than the current itself, thus avoiding the electric hazards that the high
voltage measurements imply.
Digital Optical Instrument Transformers
• DOIT, Digital Optical Instrument Transformers are used for measurement of
current and voltage in power systems.
• Applications are for protection, metering, control and power quality supervision.
• The Instrument transformers combine traditional measuring techniques with digital
optical signal transmission, allowing a purely non-conducting connection between
the transducer part in the switchyard and the interface part in the control room.
Operating Principles of DOCT
• Conventional high DC current transformers utilize the Hall effect to measure the magnetic field
around the current carrying bus bars.
• Over the years Hall effect based DC current transformers have become very accurate and reliable.
• High precision transducers, working with magnetic flux compensation, are complex systems
incorporating a magnetic core around the current-carrying bus bars, a number of Hall elements
in air gaps of the core, solenoids to nullify the primary magnetic field in the core and at the Hall
elements, and high gain current amplifiers to generate the solenoid currents.
• However, they are rather complex systems and demand intricate installation and commissioning
procedures.
• Often an analysis of the magnetic field distribution is necessary in order to place the transducer
head such that errors due to asymmetries in the field and cross-talk from neighbour currents are
minimized.
• Conventional systems weigh up to 2000 kg and consume up to 10 kW of power.
• Special care must be taken to avoid erroneous output due to asymmetric field distributions and
disturbances from neighbor currents or bus bar corners.
optical sensors
• In the fiber-optic current sensor a simple loop of optical fiber around the bus
bar replaces the sophisticated head of the conventional transformer.
• The sensor perfectly integrates the magnetic field along the closed path
described by the sensing fiber.
• As a result, the signal is independent of the particular magnetic field
distribution and only determined by the enclosed current.
• All currents outside the fiber loop are of no influence.
• Sensor placement is therefore uncritical.
• The simplicity of the system reduces the time required for installation and
commissioning to a few hours.
• The sensor overcomes the drawbacks of the classical transducers and
offers superior performance and functionality.
optical sensors
• There are basically two linear effects by which the magnetic field can be measured
by optical sensors: magneto-optic effect (or Faraday effect) and magnetic force (or
Lorentz force).
• The principle of magneto-optic effects is based on the interaction between magnetic
field and the phenomenon of light refraction and reflection in transparent medium
and on its surface .
• Three basic magneto optic effects are know
• Cotton-Mouton effect,
• Kerr surface effect ,
• Faraday effect.
• The most important for current sensor application is Faraday magneto-optic effect.
• Faraday effect causes the electromagnetic wave polarization rotation due to the
magnetic field intensity in transparent material.
Faraday effect
• The sensor makes use of the Faraday effect in the fiber.
• The Faraday effect is the phenomenon that in a medium such as glass right and left
circularly polarized light waves travel at different speeds if a magnetic field is
applied along the propagation direction .
• As a result the waves accumulate a path difference δL or equivalently a phase
difference δΦf = 2 V L H.
• Here, V is a material constant (Verdet constant), L the length of the rod, and H the
magnetic field.
Faraday effect
• The angle of rotation of linearly polarized light is proportional to the strength of the magnetic
field and the cosine of the angle between the field and the propagation direction of the light
wave.
• This rotation can be expressed mathematically by:
• where, V is the material Verdet constant, which is both dispersive and temperature-dependent.
• B is the magnetic flux density vector .
• dl is the differential vector along the direction of propagation.
• This effect is called the Faraday effect or linear magneto-optic effect and can be used to build
optical current sensors.
• Fig. below illustrates the polarization rotation due to a parallel external magnetic field on a
magneto-optical material, such as, glass.
The sensor head is connected to the sensor electronics via a glass fiber cable.
• The MOCT system satisfies current sensing needs for revenue metering or protective
relaying in a wide variety of applications. (ABB make).
• The Magneto-Optic Current Transformer for Protection (MOCT-P) is a passive optical
current transducer which uses light to accurately measure current on high voltage
systems.
• The MOCT-P system is suitable for outdoor application and has a continuous current
rating up to 3150 A with an accuracy limit factor of 40 x.
• It meets the protection class accuracy 5TPE, according to IEC 60044-8.
• The optical design enables accurate reproduction of fully offset fault currents with
decaying d.c. component without saturation or other source of distortion.
• The MOCT-P system provides a 200 mV voltage output for use with protective relays.
• Three phases of MOCT-P sensors mounted on polymer insulator columns with
predominated fiber optic cable in the insulator.
• Fiber optic cables for transmission of the light signals between the optical sensors
and the MOCT-P electronic module.
• The MOCT is a current measuring device based on the magneto-optical Faraday
• effect.
• This effect explains the rotation of the plane of polarization of a linear beam of
light in certain materials that become optically active under the presence of a
magnetic field.
• If the magnetic field and light propagation directions coincide, the angle of
rotation (q) is proportional to the magnetic flux density (B), the length of the path
(l) and a constant named Verdet constant (V), which is a property of the material.
• In the equation below I is the current flowing through the conductor and m is the
permeability of the material.
MOCT optical sensor system
• Light is emitted by an LED and transmitted through multi mode optical fiber to the rotator
installed at high voltage.
• The light is polarized as it enters the sensor. It then travels around the conductor inserted
through the opening on the rotator and exits through an analyzer.
• The analyzer is oriented 45degree with respect to the polarizer.
• Subsequently, the light is transmitted back through another optical fiber to the electronic
module where it is converted into an electric signal by a photodiode.
• The signal processing module and precision amplifier circuit provide an analog 1.0 A output
current which is proportional to the primary current flowing through the conductor.
Voltage measurement and the Pockels effect
• The voltage sensor operates using a variation of the linear, longitudinal mode
electro-optic Pockels effect referred to as the Quadrature Pockels cell.
• This effect occurs in crystalline materials that exhibit induced birefringence under
applied electric field.
• Linearly polarized light propagating the crystal parallel to the electric field will
experience phase retardation between its components in the slow and fast axis.
• The phase retardation is due to the difference in the velocity of propagation of the
light and is related to different refractive indices between these axes.
• The voltage sensor consists of a crystal placed between high voltage and ground.
• The light emitted by a source is transmitted through multi mode optical fiber to the
sensor.
• The beam of light is polarized as it enters the sensor, then it propagates through the
crystal in the direction of the electric field.
• The sensor depicted in Figure below includes a reflective prism on the high-voltage
side of the crystal.
• This prism reflects the light back towards the grounded side.
• Therefore, all of the connections are on the ground side.
• After exiting the sensor, the light is split into two quadrature components, (phase
shifted 90), which are transmitted back to the electronic module where they are
converted into electric signals.
• These two signals provide sufficient information to reconstruct the waveform and
magnitude of the voltage across the sensor by means of a digital signal processor.
• The voltage is obtained by interpolating information extracted from segments of the
signals and counting their optical fringes.
• The signal is then amplified to provide a 120 V output proportional to the applied
voltage.