TOPIC 1: Air-Conditioning Systems: Subtopic: Types of HVAC Systems
TOPIC 1: Air-Conditioning Systems: Subtopic: Types of HVAC Systems
Conditioning Systems
Subtopic: Types of HVAC systems
Chapter 2 - HVAC by Faye_C._McQuiston
Chapter 3 – Principles of HVAC by Nihal E Wijeysundera
1
1.1 The Complete System
2
Schematic of
a Typical
Commercial
HVAC system
3
1.2 SYSTEM SELECTION &
ARRANGEMENT
Equipment normally found in the central mechanical room
includes:
• Fans or air handlers for moving air with associated dampers and
filters
• Pumps for moving heated or chilled water and appropriate
control valves
• Heat exchangers for transferring energy from one fluid stream to
another
• Flow measuring and control devices
• Chillers and furnace or boiler equipment
4
HVAC EQUIPMENTS
System Selection and Arrangement
Read up on all the following terms:
•Energy sink
•Dry condensing unit.
•Zone / separate zone
•Central station or central plant
•Diversity factor
•Direct exchange
•Air & water heat exchanging medium
5
1.3 HVAC COMPONENTS AND
DISTRIBUTION SYSTEMS
Air-Handling Equipment
•A simplified schematic always shows the fans, heating and
cooling coils, filter, humidifier, and controlling dampers.
•Centrifugal pumps are usually used in air-conditioning systems
where liquids must be transported.
Pumps & Piping
•Air-conditioning pipe systems can be made up of independent
or interacting loops with pumps serving the separate systems.
Loops are sometimes referred to as primary, secondary, or
tertiary, depending on their location in the flow of energy.
Piping may be involved in transferring fuel, refrigerants, steam,
or water. 6
1.4 Types of All-Air Systems
Single Zone System
• Single-zone System
7
• Usage of a thermostat/damper/valve/fan
Reheating Systems
1.4 Types of All-Air Systems
10
In the dual-duct (double-duct) system, the central equipment supplies
warm air through one duct run and cold air through the other.
Multizone- System
1.4 Types of All-Air Systems
The multizone central units provide a single supply duct for each zone 11
and obtain zone control by mixing hot and cold air at the central unit in
response to room or zone thermostats.
Class Activity (1.1)
2-1
Consider the small single-story office building in Fig. 2-21. Lay
out an all-air central system using an air handler with two zones.
There is space between the ceiling and roof for ducts. The air
handler is equipped with a direct expansion cooling coil and a 12
hot water heating coil. Show all associated equipment
schematically. Describe how the system might be controlled.
1.5 Air- Water Systems
Generally the cooling water is furnished to carry away most
of the sensible energy from the conditioned space. The air
provides the ventilation required for air quality and carries
away the moisture resulting from the space latent load.
19
1.7 Decentralised Cooling &
Heating
The following list of variations is indicative of the vast number of types of
unitary air conditioners available.
1. Arrangement: single or split (evaporator connected in the field).
2. Heat rejection: air-cooled, evaporative condenser, water-cooled.
3. Unit exterior: decorative for in-space application, functional for
equipment room and ducts, weatherproofed for outdoors.
4. Placement: floor-standing, wall-mounted, ceiling-suspended, roof-
mounted.
5. Indoor air: vertical up-flow, counter flow, horizontal, 90- and 180-degree
turns, with fan, or for use with forced-air furnace.
6. Locations: indoor—exposed with plenums or furred-in ductwork,
concealed in closets, attics, crawl spaces, basements, garages, utility rooms,
or equipment rooms; wall—built-in, window, transom; outdoor—rooftop,
wall-mounted, or on ground.
7. Heat: intended for use with up-flow, horizontal, or counter-flow forced-air
furnace, combined with furnace, combined with electrical heat, combined 20
with hot water or steam coil.
Through-the-wall and window-mounted room air-
conditioning units are common in residences and
in renovations of older buildings. Heavy-duty,
commercial-grade through-the-wall units, usually
capable of providing both heating and cooling, are
sometimes referred to as packaged terminal air
conditioners (PTAC).
21
1.7 Decentralised Cooling &
Heating
Other application/structure of decentralized system
-Retail store
-Gymnasium
-Rooftop
-Floor diffusers
22
1.8 Heat Pump Systems
Heat Pump & Types
•Any refrigeration system is a heat pump in the sense that energy is moved
from a low temperature source to a higher temperature sink.
•The thermal cycle is identical to that of ordinary refrigeration; however, in
most heat pump systems a reversing valve permits flow reversal of refrigerant
leaving the compressor such that the evaporator and condenser roles are
switched.
•As with air conditioners, unitary (packaged) heat pumps (as opposed to
applied heat pumps) are shipped from the factory as a complete pre-
assembled unit including internal wiring, controls, and piping. Only the
ductwork, external power wiring, and piping (for water-source heat pumps)
are required to complete the installation.
•Air-to-air heat pump is a common type, others type for consideration:
• Hybrid or dual-fuel heat pumps.
• Air-to-water heat pumps
• Water-to-air pumps 23
• Waste process water pumps? – specialized.
24
25
1.8 Heat Pump Systems
Closed-Loop & Ground Coupled Systems
•In some cases a building may require cooling in interior zones
while needing heat in exterior zones.
•The earth itself is a near-ideal source or sink for heat pumps.
The advantages and disadvantages of using open-loop systems
with wells, rivers, and lakes were described earlier. Using a
closed-loop system with piping buried in the ground, circulating
water either picks up energy for heating or loses energy for
cooling.
With a variety of schemes have been proposed. The
International Ground Source Heat Pump Association (IGSHPA)
under the direction of Bose (8) has produced a large amount of
useful information, including design documents on ground
(source heat) piping/circulation system. 26
Closed-Loop & Ground Coupled Systems
27
1.9 Heat Recovery Systems
Because of the introduction of outdoor ventilation air it is
necessary to exhaust significant quantities of air from large
buildings. In the heating season considerable savings can be
realized if the heat energy from the exhaust air can be
recovered and used in warming the exterior parts of the
structure. In a similar manner energy can be saved when
outdoor temperatures are high by precooling ventilation air
using the cooler air exhausted from the building.
Recovery of heat energy from exhaust air is accomplished
through the use of rotating (periodic type) heat exchangers.
28
1.9 Heat Recovery Systems
29
1.10 Thermal Energy Storage (TES)
31
Class Activity (1.3)
2-20. It is desirable for the water leaving a cooling coil to be
at a fixed temperature for return to the chiller. Sketch a coil,
control valve, and so on to accomplish this action, and
describe the operation of the system.
Explain how the system will be controlled.
32