Generator Protection Unit#3 KMPCL
Generator Protection Unit#3 KMPCL
UNIT#3 KMPCL
Generating Transformer 400 KV Switchyard
External DC
Supply for fiel
Flashing
CLASS – D Tripping
CAUSES:-
• Failure of Insulation in stator winding with next turn.
• Stator water pipes hoses leakge.
Effects:-
• It can cause unbalance of current.
• Damage of Stator winding.
Settings:
U> 50V. Balancing Factor :0.50 ,I2/I1>5.9%,time delay =20
sec,k=4.4,I2 =-ve seq current,I1=+ve seq current.
inter-turn fault.
59 N Neutral Voltage :50 V,Residual Volatge:2.50 V,Balancing factor >0.50,time delay :20 sec
Voltage Based
Under Excitation
CAUSES:- Excitation Transformer saturation ,AVR limter mal operation, Carbon brush wornout
Result : Gen goes out of synchronism & run asynchronouslyhigher speed .result in overheating of
stator & rotor wdg.
Protection 1. locus lying zone 3 &zone 4 impedance adjustable reach.impedance lowers as
Produced V&I at Gen Terminal is low.2. check with OC&UV.& Timer.
Xd= 1.9987 pu
Stage 1: 1/Xd >0.39 ,Angle>75 degree,Tchar 10 sec.,V residual>1.30 V
Slow rate of change of impedance in transmission linje due to surge,lighting ,Auto Reclose unsucessful.
Overexcitation
Effect : core heating
Causes : Capacitor action of generator.
U/F >1.1 PU time delay 10 sec
U/F >1.3 PU time delay 1 sec
Under Frequency
Effects:-
1.Turbine blade tip worn out due to cavitation.
2.Commercial loss
Setting: 0.63% of Rated power, Digital input for Turbine stop valve close status<1 sec.
Turbine stop valve open status>15 sec.
Low Forward Power
CAUSES:- when steam flow is interuppted by MSV & Governor valve.Remaining steam
flow through stages of turbine deliver low power due to flow is diminished.so Low
forward trips GCB after some delay to prevent motoring action. Reverse power is
just substitute to Reverse power.
GCB close,primeover power less than permissive value.porvided with turbine trip
interlock.
Setting: 0.60% of Rated power, Power sampled >12.6%
Timedelay: 1.5 sec
In low forward power protection relay trips the generator circuit breaker when
the power delivered to the grid drops below a certain level (typical setting being
0.5% or 1% of full load). In reverse power protection relay operates immediately
after the generator starts drawing power from the grid instead of delivering
power to the grid
Accidental Energisation & inadherent Energisation
CAUSES:-
Excitation breaker close. Field breaker accidental close. No Voltage in stator phase side winding.