Generator complete-ALSTOM
Generator complete-ALSTOM
GENERATOR PROTECTION
PROTECTION
16 th July 2001
Generator Protection
I.P. LAIJU
GENERATOR
GENERATOR PROTECTION
PROTECTION
TYPES
TYPES OF
OF PROTECTION
PROTECTION
TYPE
TYPEOF
OFPRIME
PRIME-- MOVER
MOVERAND
ANDCONSTRUCTION
CONSTRUCTION
MW
MWAND
ANDVOLTAGE
VOLTAGERATINGS
RATINGS
MODE
MODEOF
OFOPERATION
OPERATION
METHOD
METHODOF
OFCONNECTION
CONNECTIONTO
TO POWER
POWERSYSTEMS
SYSTEMS
METHOD
METHODOF
OFEARTHING
EARTHING
GENERATOR
GENERATOR PROTECTION
PROTECTION
PRIME
PRIME MOVERS
MOVERS
STEAM
STEAMTURBINES
TURBINES
GAS
GASTURBINES
TURBINES
HYDRO
HYDRO
DIESEL
DIESEL
GENERATOR
GENERATOR PROTECTION
PROTECTION
CONSTRUCTION
CONSTRUCTION
CYLINDRICAL
CYLINDRICALROTOR
ROTOR
SALIENT
SALIENTPOLE
POLE
MODE
MODE OF
OF OPERATION
OPERATION
BASE
BASELOAD
LOAD
PEAK
PEAKLOAD
LOAD
STAND
STAND--BY
BY
GENERATOR
GENERATOR PROTECTION
PROTECTION
CONNECTION
CONNECTION TO
TO POWER
POWER SYSTEM
SYSTEM
DIRECT
DIRECT
~
GENERATOR
GENERATOR PROTECTION
PROTECTION
CONNECTION
CONNECTION TO
TO POWER
POWER SYSTEM
SYSTEM
DIRECT
DIRECT
VIA
VIATRANSFORMER
TRANSFORMER
~
GENERATOR
GENERATOR PROTECTION
PROTECTION
METHOD
METHOD OF
OF EARTHING
EARTHING
SOLID
SOLID
GENERATOR
GENERATOR PROTECTION
PROTECTION
METHOD
METHOD OF
OF EARTHING
EARTHING
SOLID
SOLID
RESISTANCE
RESISTANCE R
GENERATOR
GENERATOR PROTECTION
PROTECTION
METHOD
METHOD OF
OF EARTHING
EARTHING
SOLID
SOLID
RESISTANCE
RESISTANCE R
HIGH
HIGHIMPEDANCE
IMPEDANCE R
GENERATOR
GENERATOR PROTECTION
PROTECTION
REQUIREMENTS
REQUIREMENTS
DETECT
DETECTFAULTS
FAULTSON
ONTHE
THEGENERATOR
GENERATOR
PROTECT
PROTECTFROM
FROMABNORMAL
ABNORMALOPERATING
OPERATINGCONDITIONS
CONDITIONS
ISOLATE
ISOLATEGENERATOR
GENERATORFROM
FROMUNCLEARED
UNCLEAREDSYSTEM
SYSTEM
FAULTS
FAULTS
ACTIONS
ACTIONS REQUIRED
REQUIRED
URGENT
URGENT
NOT
NOTURGENT
URGENT
ALARM
ALARM
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
PROVIDES
PROVIDESHIGH
HIGHSPEED
SPEEDPROTECTION
PROTECTIONFOR
FORALL
ALL FAULT
FAULT
TYPES
TYPES
MAY
MAYBE
BEHIGH
HIGHIMPEDANCE
IMPEDANCETYPE
TYPE
OR
OR
BIASED
BIASEDDIFFERENTIAL
DIFFERENTIALTYPE
TYPE
GOOD
GOODQUALITY
QUALITYCT’S
CT’SARE
AREREQUIRED
REQUIREDAT
ATLINE
LINEAND
AND
NEUTRAL
NEUTRALENDS
ENDS
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
~
Differential Relay
Stabilising Resistor
ZG9323
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
~
If RCT
V
2RL
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
V = If x { RCT + 2RL }
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
Z = V / IS
RSTAB = Z - RRELAY
~
If RCT
V
2RL
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
STABILISING
STABILISINGRESISTOR
RESISTORCALCULATION
CALCULATION
Rstab
Rstab==IIf fxx((RRCTCT++22RRLL)) ((VA
VA))
Is
Is Is
Is22
WHERE
WHERE
IfIf ==MAXIMUM
MAXIMUMTHROUGH
THROUGHFAULT
FAULTCURRENT
CURRENT
RRCTCT ==RESISTANCE
RESISTANCEOF
OFCT
CTWINDING
WINDING
2R
2RLL ==TWO
TWOWAY
WAYLEAD
LEADRESISTANCE
RESISTANCE
VA
VA ==RELAY
RELAYBURDEN
BURDEN
Is
Is ==RELAY
RELAYSETTING
SETTING
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
EXAMPLE
EXAMPLE
50
50MVA
MVA 11KV
11KV F.
F. L.
L.C.
C. ==2624
2624Amps
Amps
Xd’’
Xd’’==18
18 %
% C.
C.T.
T. RATIO
RATIO ==3000
3000// 11
RRCT = 3 Ohms
CT = 3 Ohms
2R
2RLL ==22Ohms
Ohms
SETTING
SETTING == 0.5A
0.5A
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
FAULT CURRENT ((IIFF)) == 50 x 10 ==14579
14579AA
33
FAULT CURRENT 50 x 10
1.732
1.732xx1111xx0.18
0.18
== 4.86
4.86AA(( Sec
Sec))
R == IIF xx((RRCT ++22RRL )) (( VA
RSTAB
STAB F CT L VA))
Is
Is Is
Is
22
== 4.86
4.86xx(3(3++ 22)) 11
0.5
0.5 0.5
0.52
2
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE
CT
CTREQUIREMENT
REQUIREMENT
ACCURACY
ACCURACYCLASS
CLASS :: PS
PS CLASS
CLASS
KNEE
KNEEPOINT
POINTVOLTAGE
VOLTAGE VVKK >> 22IIFF ((RRCT + 2R )
CT + 2RLL )
MAGNETISING
MAGNETISINGCURRENT
CURRENT IIMAG < 3 % OF In AT V / 2
MAG < 3 % OF In AT VKK / 2
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
LOW
LOW IMPEDANCE
IMPEDANCE TYPE
TYPE
BIAS COIL
BIAS COIL
ZG9323
OPERATING COIL
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
LOW
LOW IMPEDANCE
IMPEDANCE TYPE
TYPE
CURRENT
DIFF. CURRENT
OPERATE
RESTRAIN
DIFF.
BIAS
BIASCURRENT
CURRENT
GENERATOR
GENERATOR PROTECTION
PROTECTION
DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
OVERALL
OVERALL DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION SCHEME
SCHEME
~ G T
UAT
RELAY ICT
GENERATOR
GENERATOR PROTECTION
PROTECTION
OVERALL
OVERALL DIFFERENTIAL
DIFFERENTIAL PROTECTION
PROTECTION
BIASED
BIASEDRELAYS
RELAYSSHOULD
SHOULDONLY
ONLYBE
BEUSED
USED
NO
NOMAG
MAG--INRUSH
INRUSHAS
ASTRANSFORMER
TRANSFORMERVOLTAGE
VOLTAGEIS
IS
GRADUALLY
GRADUALLYDEVELOPED
DEVELOPED
HOWEVER
HOWEVERMAG
MAG--INRUSH
INRUSHCURRENT
CURRENTWILL
WILLFLOW
FLOWFOR
FOR
THE
THEFOLLOWING
FOLLOWINGCONDITION
CONDITION
WHEN
WHENAATHROUGH
THROUGHFAULT
FAULTIS
ISCLEARED
CLEARED
WHEN
WHENAALARGE
LARGESTATION
STATIONTRANSFORMER
TRANSFORMER
CONNECTED
CONNECTEDTO
TO G
GTT BUSBAR
BUSBARIS
ISENERGISED
ENERGISED
GENERATOR
GENERATOR PROTECTION
PROTECTION
INTERTURN
INTERTURN FAULT
FAULT PROTECTION
PROTECTION
LONGITUDINAL
LONGITUDINALDIFFERENTIAL
DIFFERENTIAL SYSTEM
SYSTEMDOES
DOESNOT
NOT
DETECT
DETECT INTERTURN
INTERTURNFAULTS
FAULTS
INTERTURN
INTERTURNFAULT
FAULT PROTECTION
PROTECTIONNOT
NOTCOMMONLY
COMMONLY
PROVIDED
PROVIDEDBECAUSE
BECAUSE
FAULTS
FAULTS ARE
ARERARE
RARE
EVEN
EVENIF
IFTHEY
THEYOCCUR,
OCCUR, THEY
THEYWILL
WILLQUICKLY
QUICKLY
DEVELOP
DEVELOPINTO
INTOSTATOR
STATOREARTH
EARTHFAULTS
FAULTS
GENERATOR
GENERATOR PROTECTION
PROTECTION
INTERTURN
INTERTURN FAULT
FAULT PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE PROTECTION
PROTECTION
DIFFERENTIAL
RELAY R STABILISING RESISTOR
GENERATOR
GENERATOR PROTECTION
PROTECTION
INTERTURN
INTERTURN FAULT
FAULT PROTECTION
PROTECTION
LOW
LOW IMPEDANCE
IMPEDANCE TYPE
TYPE PROTECTION
PROTECTION
DIFFERENTIAL
RELAY R
GENERATOR
GENERATOR PROTECTION
PROTECTION
INTER
INTER TURN
TURN FAULT
FAULT PROTECTION
PROTECTION
HIGH
HIGH IMPEDANCE
IMPEDANCE TYPE
TYPE PROTECTION
PROTECTION
SETTINGS
SETTINGS
RELAY
RELAYPICK
PICK--UP
UP == SHOULD
SHOULDBEBELESS
LESSTHAN
THAN
DIFFERENTIAL
DIFFERENTIALCURRENT
CURRENTDUE
DUETO
TO SINGLE
SINGLETURN
TURNSHORT
SHORT
CIRCUIT
CIRCUIT
Rstab
Rstab == SAME
SAMEAS
ASDIFFERENTIAL
DIFFERENTIAL
PROTECTION
PROTECTION
EXCEPT
EXCEPT
FAULT
FAULTCURRENT
CURRENT((IfIf))
== MVA
MVAxx10
1033
1.732
1.732xxKV
KVxxXd’’
Xd’’xx22
GENERATOR
GENERATOR PROTECTION
PROTECTION
ZERO
ZERO SEQ.
SEQ. VOLTAGE
VOLTAGE MEASUREMENT
MEASUREMENT
SHORT
SHORTCIRCUIT
CIRCUITOF
OFONE
ONEOR
ORMORE
MORETURNS
TURNSWILL
WILLCAUSE
CAUSE
THE
THEGENERATED
GENERATED EEM
MFF TO
TOCONTAIN
CONTAINZERO
ZEROSEQUENCE
SEQUENCE
COMPONENT
COMPONENT
EXTERNAL
EXTERNALEARTHFAULTS
EARTHFAULTSWILL
WILLALSO
ALSOPRODUCE
PRODUCEAA
ZERO
ZEROSEQUENCE
SEQUENCEVOLTAGE
VOLTAGE--MOST
MOSTOFOFTHE
THEVOLTAGE
VOLTAGE
WILL
WILLBE
BEEXPENDED
EXPENDEDON
ONEARTHING
EARTHINGRESISTOR
RESISTOR
HENCE,
HENCE,DROP
DROPACROSS
ACROSSTHE
THEWINDING
WINDINGSHOULD
SHOULDBE
BE
MEASURED
MEASURED
GENERATOR
GENERATOR PROTECTION
PROTECTION
INTERTURN
INTERTURN FAULT
FAULT PROTECTION
PROTECTION
ZERO
ZERO SEQUENCE
SEQUENCE VOLTAGE
VOLTAGE DETECTION
DETECTION
TUNED RELAY
SHOUD BE USED
R VVR =V
=VA ++ VVB ++VVC
GENERATOR
GENERATOR PROTECTION
PROTECTION
STATOR
STATOR EARTH
EARTH FAULT
FAULT PROTECTION
PROTECTION
CAUSED
CAUSEDBY
BYINSULATION
INSULATIONFAILURE
FAILURE
LEADS
LEADSTO
TOBURNING
BURNINGOF
OFMACHINE
MACHINECORE,
CORE,
WELDING
WELDINGOF
OFLAMINATIONS
LAMINATIONS
REBUILDING
REBUILDINGOF
OFMACHINE
MACHINECORE
CORECAN
CANBE
BEAA
VERY
VERYEXPENSIVE
EXPENSIVEPROCESS
PROCESS
HENCE
HENCE
EARTH
EARTHFAULT
FAULTPROTECTION
PROTECTIONIS
ISAAMUST
MUST
GENERATOR
GENERATOR PROTECTION
PROTECTION
STATOR
STATOR EARTH
EARTH FAULT
FAULT PROTECTION
PROTECTION
DEPENDS
DEPENDSON
ONSYSTEM
SYSTEMEARTHING
EARTHING
95
95%
%STATOR
STATOREARTH
EARTHFAULT
FAULTPROTECTION
PROTECTION
100%
100%STATOR
STATOREARTH
EARTHFAULT
FAULTPROTECTION
PROTECTION
RELAYS
RELAYSWITH
WITHINVERSE
INVERSECHARACTERISTICS
CHARACTERISTICS
PREFERRED
PREFERRED
GENERATOR
GENERATOR PROTECTION
PROTECTION
95
95 %
% S.
S. E.
E. F.
F. PROTECTION
PROTECTION --CURRENT
CURRENTOPERATED
OPERATED
R
~
R 10 % - 40 %
SUITABLE
SUITABLEFOR
FORRESISTANCE
RESISTANCEAND
ANDSOLIDLY
SOLIDLY
EARTHED
EARTHED SYSTEMS
SYSTEMS
GENERATOR
GENERATOR PROTECTION
PROTECTION
95
95 %
% S.
S. E.
E. F.
F. PROTECTION
PROTECTION --VOLTAGE
VOLTAGEOPERATED
OPERATED
~
R
64
SUITABLE
SUITABLEFOR
FORHIGH
HIGHIMPEDANCE
IMPEDANCEEARTHED
EARTHEDSYSTEMS
SYSTEMS
SHOULD
SHOULDBE
BEAATUNED
TUNEDRELAY
RELAY
GENERATOR
GENERATOR PROTECTION
PROTECTION
NEED
NEED FOR
FOR 100
100 %
% S.
S. E.
E. F.
F. PROTECTION
PROTECTION
OVERCURRENT
OVERCURRENT AND
ANDOVERVOLTAGE
OVERVOLTAGERELAYS
RELAYSWILL
WILL
NOT
NOTDETECT
DETECT EARTH
EARTHFAULT
FAULT NEAR
NEARNEUTRAL
NEUTRAL
DIFFERENT
DIFFERENT METHODS
METHODS
SUB
SUB-- HARMONIC
HARMONICINJECTION
INJECTION
THIRD
THIRDHARMONIC
HARMONICUNDERVOLTAGE
UNDERVOLTAGE
COMPARISON
COMPARISONOF
OFTHIRD
THIRDHARMONIC
HARMONICVOLTAGE
VOLTAGEAT
AT
NEUTRAL
NEUTRALAND
ANDLINE
LINEENDS
ENDS
GENERATOR
GENERATOR PROTECTION
PROTECTION
SUB
SUB -- HARMONIC
HARMONIC INJECTION
INJECTION METHOD
METHOD
WILL
WILLNOT
NOTDETECT
DETECTOPEN
OPENCIRCUITING
CIRCUITINGOF
OF
GROUND
GROUNDTRANSFORMER
TRANSFORMERPRIMARY
PRIMARYOR
OR
SECONDARY
SECONDARY
CHANGES
CHANGESTHE
THEEARTHING
EARTHING PARAMETERS
PARAMETERS
WHICH
WHICHIS
ISNOT
NOTDESIRABLE
DESIRABLE
OFF
OFF-- LINE
LINESUPERVISION
SUPERVISIONIS
ISREQUIRED
REQUIRED
COST
COSTOF
OFIMPLEMENTAION
IMPLEMENTAIONAND
ANDMAINTENANCE
MAINTENANCE
IS
ISVERY
VERYHIGH
HIGH
GENERATOR
GENERATOR PROTECTION
PROTECTION
THIRD
THIRD HARMONIC
HARMONIC UNDERVOLTAGE
UNDERVOLTAGE
SUFFICIENT
SUFFICIENTNEUTRAL
NEUTRALTHIRD
THIRD
HARMONIC
HARMONICVOLTAGE
VOLTAGESHOULD
SHOULDBE
BE
AVAILABLE
AVAILABLE
IT
ITWILL
WILLALSO
ALSOBE
BEOUT
OUT--OF
OF--SERVICE
SERVICEIF
IF
SUFFICIENT
SUFFICIENTVOLTAGE
VOLTAGEHAS
HASNOT
NOT
DEVELOPED
DEVELOPEDDURING
DURINGLIGHTLY
LIGHTLYLOADED
LOADED
CONDITIONS
CONDITIONS
GENERATOR
GENERATOR PROTECTION
PROTECTION
THIRD
THIRD HARMONIC
HARMONIC VOLTAGE
VOLTAGE COMPARISON
COMPARISON
LINE
LINESIDE
SIDEAND
ANDNEUTRAL
NEUTRALSIDE
SIDETHIRD
THIRD
HARMONIC
HARMONICVOLTAGES
VOLTAGESARE
ARECOMPARED
COMPARED
V L3
V N3 NORMAL
NORMALCONDITION
CONDITION
GENERATOR
GENERATOR PROTECTION
PROTECTION
THIRD
THIRD HARMONIC
HARMONIC VOLTAGE
VOLTAGE COMPARISON
COMPARISON
GROUND
GROUNDFAULT
FAULTAT
AT NEUTRAL
NEUTRALEND
END((VVNN33 ==00))
V L3
V N3
GENERATOR
GENERATOR PROTECTION
PROTECTION
THIRD
THIRD HARMONIC
HARMONIC VOLTAGE
VOLTAGE COMPARISON
COMPARISON
GROUND
GROUNDFAULT
FAULTAT
AT NEUTRAL
NEUTRALEND
END((VVNN33 ==00))
V L3
V N3
GROUND
GROUNDFAULT
FAULTAT
ATLINE
LINEEND
END((VVLL33 ==00))
V L3
V N3
GENERATOR
GENERATOR PROTECTION
PROTECTION
FAULT
FAULTAT
AT 50
50%%OF
OFGENERATOR
GENERATORWINDING
WINDING
V L3
DEAD
DEADZONE
ZONE
V N3
THE
THEVV LL33 ,,VVNN33 BALANCE
BALANCEWILL
WILLBE
BEMAINTAINED
MAINTAINED
THE
THE100
100%
% UNIT
UNITMAY
MAYNOT
NOTDETECT
DETECT
HENCE
HENCE,,USE
USEAA95
95%%UNIT
UNITALSO
ALSO
GENERATOR
GENERATOR PROTECTION
PROTECTION
100
100 %
% STATOR
STATOR EARTH
EARTH FAULT
FAULT
95
95%% MODULE
MODULE
100
100%%MODULE
MODULE
00%
% GENERATOR
GENERATORWINDING
WINDING 100
100 %
%
95
95%%MODULE
MODULESHOULD
SHOULDBE
BECONNECTED
CONNECTEDTO
TO
GROUNDING
GROUNDINGTRANSFORMER
TRANSFORMERSECONDARY
SECONDARY
SHOULD
SHOULDBE
BETUNED
TUNED
GENERATOR
GENERATOR PROTECTION
PROTECTION
100
100 %
% STATOR
STATOR EARTH
EARTH FAULT
FAULT PROTECTION
PROTECTION
PVMM
PVMMRELAY
RELAY
DEFINITE TIME DELAYED 100 % UNIT
DEFINITE TIME DELAYED 100 % UNIT
UNBALANCED
UNBALANCED LOADING
LOADING
GIVES
GIVESRISE
RISETO
TO NEGATIVE
NEGATIVEPHASE
PHASESEQUENCE
SEQUENCESTATOR
STATOR
CURRENT
CURRENTWHICH
WHICHCAUSES
CAUSESCONTRA
CONTRA-- ROTATING
ROTATING
MAGNETIC
MAGNETICFIELDS
FIELDS
STATOR
STATORFLUX
FLUXCUTS
CUTSROTOR
ROTORAT
ATTWICE
TWICESYNCHRONOUS
SYNCHRONOUS
SPEED
SPEEDINDUCING
INDUCINGDOUBLE
DOUBLEFREQUENCY
FREQUENCYCURRENT
CURRENTIN
IN
FIELD
FIELDSYSTEM
SYSTEM AND
ANDROTOR
ROTORBODY
BODY
RESULTING
RESULTING.... .... ..
GENERATOR
GENERATOR PROTECTION
PROTECTION
UNBALANCED
UNBALANCED LOADING
LOADING
MACHINES
MACHINESARE AREASSIGNED
ASSIGNED
II22SS == CONTINUOUS
CONTINUOUS NPS
NPS RATING
RATING
II2222 tt == SHORT
SHORTTIME
TIME NPS
NPS RATING
RATING
IF
IFSYSTEM
SYSTEMUNBALANCE
UNBALANCEAPPROACHES
APPROACHESMACHINE
MACHINE
CONTINUOUS
CONTINUOUSWITHSTAND
WITHSTANDTHEN
THENPROTECTION
PROTECTIONIS
IS
REQUIRED
REQUIRED
GENERATOR
GENERATOR PROTECTION
PROTECTION
TYPICAL
TYPICAL NPS
NPS CURRENT
CURRENT WITHSTAND
WITHSTAND TABLE
TABLE
TYPE
TYPEOF
OFMACHINE
MACHINE TYPE
TYPEOF
OFCOOLING
COOLING II2 S II222 tt
2S 2
TURBO
TURBOALTERNATOR
ALTERNATOR DIRECT
DIRECTHYDROGEN
HYDROGEN 10
10 77
30
30LB
LB//SQ.
SQ.FT
FT
TURBO
TURBOALTERNATOR
ALTERNATOR CONVENTIONAL
CONVENTIONALHYDROGEN
HYDROGEN 15
15 12
12
30
30LB
LB//SQ.
SQ.FT
FT
TURBO
TURBOALTERNATOR
ALTERNATOR CONVENTIONAL
CONVENTIONALHYDROGEN
HYDROGEN 15
15 15
15
15
15LB
LB//SQ.
SQ.FT
FT
TURBO
TURBOALTERNATOR
ALTERNATOR CONVENTIONAL
CONVENTIONALHYDROGEN
HYDROGEN 15
15 20
20
0.5
0.5LB
LB//SQ.
SQ.FT
FT
NEGATIVE
NEGATIVE PHASE
PHASE SEQUENCE
SEQUENCE PROTECTION
PROTECTION
I22 t = K
WHERE
OVERLOAD
OVERLOAD
OVER
OVER--TEMPERATURE
TEMPERATUREIN
INSTATOR
STATORAND
ANDROTOR
ROTOR
INSULATION
INSULATIONFAILURE
FAILURE
OVERLOAD
OVERLOAD PROTECTION
PROTECTION
PICK
PICK--UP
UP ABOVE
ABOVETHE
THEMAX
MAXLOAD
LOADCURRENT
CURRENT
ALTERNATIVELY
ALTERNATIVELY,,
CURRENT
CURRENTOPERATED
OPERATEDTHERMAL
THERMALREPLICA
REPLICARELAYS
RELAYS
GENERATOR
GENERATOR PROTECTION
PROTECTION
VOLTAGE
VOLTAGE RELAYS
RELAYS
FIELD
FIELDEXCITATION
EXCITATIONSYSTEM
SYSTEMUSUALLY
USUALLYPREVENTS
PREVENTS
UNDER-
UNDER- AND
ANDOVER-
OVER-VOLTAGE
VOLTAGECONDITIONS
CONDITIONS
OVER
OVER -- VOLTAGE
VOLTAGE CONDITION
CONDITION OCCURS
OCCURS WHEN
WHEN
11)) PRIME
PRIME--MOVER
MOVEROVERSPEEDS
OVERSPEEDSDUE
DUETO
TOSUDDEN
SUDDEN
LOSS
LOSSOF
OFLOAD
LOAD
22)) VOLTAGE
VOLTAGEREGULATOR
REGULATORIS
ISDEFECTIVE
DEFECTIVE
GENERATOR
GENERATOR PROTECTION
PROTECTION
OVER
OVER VOLTAGE
VOLTAGE
ENDANGERS
ENDANGERSINTEGRITY
INTEGRITYOF
OFINSULATION
INSULATION
OVERFLUXING
OVERFLUXING
DEFINITE
DEFINITETIME
TIMEDELAYED
DELAYED//INVERSE
INVERSETIME
TIMEOVERVOLTAGE
OVERVOLTAGEIS
IS
PROVIDED
PROVIDED
UNDER
UNDERVOLTAGE
VOLTAGE
DEFINITE
DEFINITETIME
TIMEDELAYED
DELAYEDUNDERVOLTAGE
UNDERVOLTAGEPROTECTION
PROTECTIONIS
IS
GENERALLY
GENERALLYPROVIDED
PROVIDED
BACK
BACK--UP
UPFOR
FOROTHER
OTHERMAIN
MAINPROTECTION
PROTECTIONRELAYS
RELAYS
GENERATOR
GENERATOR PROTECTION
PROTECTION
FUSE
FUSE FAILURE
FAILURE PROTECTION
PROTECTION
USED
USEDFOR
FORBLOCKING
BLOCKING PROTECTION
PROTECTION RELAYS
RELAYS
PRIMARY
PRIMARYAND
ANDSECONDARY
SECONDARYFUSES
FUSESSHOULD
SHOULDBE
BE
MONITORED
MONITORED
RECOMMENDED
RECOMMENDEDRELAY
RELAY :: MVAPM
MVAPM32
32
MVAPM
MVAPMWORKS
WORKSBY
BYCOMPARING
COMPARINGTHE
THESECONDARY
SECONDARY
VOLTAGES
VOLTAGESOF
OFTWO
TWOSETS
SETSOF
OF VTs
VTs
GENERATOR
GENERATOR PROTECTION
PROTECTION
VT
VT FUSE
FUSE FAILURE
FAILURE PROTECTION
PROTECTION
PT - 1
MVAPM32
(1)
MVAPM32
(2)
PT - 2
MVAPM32 MVAPM32
(1)
(+) (2)
(-)
C1
C2
MVAPM32 MVAPM32
(1) (2)
C1
C1:: PT
PT--11FAILURE
FAILURE
C2 : PT - 2 FAILURE
GENERATOR
GENERATOR PROTECTION
PROTECTION
Loss of Excitation
Generator Capability Curve
( MVA , Ø ) ( Z, Ø )
Causes
AVR failure
Hydrogenerators : saliency
GENERATOR
GENERATOR PROTECTION
PROTECTION
Loss of Excitation
System instability
“ Voltage collapse ”
GENERATOR
GENERATOR PROTECTION
PROTECTION
Loss of Excitation
Xd’/ 2
Xd
GENERATOR
GENERATOR PROTECTION
PROTECTION
Loss of Excitation
Protection
X
Xd’/ 2
Xd
=
dia
Xd
GENERATOR
GENERATOR PROTECTION
PROTECTION
Loss of Excitation
Protection
Delay on pick-up
Delay on drop-off
Measuring
Element
TDDO
TDPU
GENERATOR
GENERATOR PROTECTION
PROTECTION
Pole Slipping
System considerations
System complexity
Performance criteria
Causes
Underexcited operation
P = ( Vs.Vr / X ) Sin Ø
Consequences
High currents, voltage swings
Pulsating torques
ZA
R
A
GENERATOR
GENERATOR PROTECTION
PROTECTION
Pole Slipping
Protection - Type ZTO
jX
Directional cum blinder
Directional identifies
severe swings Locus of
Pole Slip
Blinder identifies swings
leading to pole - slip
R
l
tiona
er
Timer distinguishes
fault conditions
Blind
Direc
stable
swing
GENERATOR
GENERATOR PROTECTION
PROTECTION
Motoring
Synchronous Synchronous
Generator Motor
Electrical detection
Single-phase detection
CT / PT accuracy
GENERATOR
GENERATOR PROTECTION
PROTECTION
Motoring
Protection Considerations P
Reverse power relay Va
Q
High operating angle range
Time delays
-- Transients
-- Asymmetrical faults
Ia
Disabling
-- Pumped storage schemes
-- Synchronous compensation
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Voltages
AVR failure
Operator Errors
Load rejection
Hydro generators
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Voltages
Overvoltages - Consequences
Damage to insulation
Over fluxing
Overvoltages - Protection
Definite Time relays
100 % - 120 % threshold
1s - 3s delay
Undervoltage Function
A V R failure
Interlocking
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
Basics
Load - frequency link
Underfrequency - Causes
Loss of Generation
Overload Underfrequency
System split
Load shedding
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
Frequency
50
Duration
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
Underfrequency - Consequences
Combustion Turbines
Hydro generators
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
Fault clearing
Over shedding
Loss of Load
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
Overfrequency - Causes
Fault clearing
Loss of Load
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
Overfrequency - Causes
Over frequency
Fault clearing
Loss of Load
GENERATOR
GENERATOR PROTECTION
PROTECTION
Abnormal Frequency
- Hydroturbines
- Time delays
GENERATOR
GENERATOR PROTECTION
PROTECTION
Overfluxing
Causes
Prior to synchronisation
Load rejection
GENERATOR
GENERATOR PROTECTION
PROTECTION
Overfluxing
Saturation of Iron
GENERATOR
GENERATOR PROTECTION
PROTECTION
Overfluxing
Saturation of Iron
Leakage Paths
GENERATOR
GENERATOR PROTECTION
PROTECTION
Overfluxing
Saturation of Iron
Leakage Paths
Eddy Currents
GENERATOR
GENERATOR PROTECTION
PROTECTION
Overfluxing
Saturation of Iron
Leakage Paths
Eddy Currents
Interlaminar voltage
Heat
GENERATOR
GENERATOR PROTECTION
PROTECTION
Overfluxing
Protection
Volts / Hz limiter
Hz
V
Definite - time relays
t
GENERATOR
GENERATOR PROTECTION
PROTECTION
Back-up Protection
Overload
Characteristic
Is
Current Pick - up
t
Fault
Characteristic
Vs
I Voltage
GENERATOR
GENERATOR PROTECTION
PROTECTION
Back-up Protection
GENERATOR
GENERATOR PROTECTION
PROTECTION
Back-up Protection
Current Pick-up
I>
Equivalent to
impedance devices
KI>
VS2 VS1
Voltage
GENERATOR
GENERATOR PROTECTION
PROTECTION
Back-up Protection
fault
GENERATOR
GENERATOR PROTECTION
PROTECTION
Back-up Protection
Basics
Subtransient Period Xd’’ , Td’’
( 0.1 - 0.2 p.u. )
~
21
Z = Z T + n ZL
ZT = Transformer impedance
Considerations
Faults involving low currents
Tripping Modes
Class C HV breaker
GENERATOR
GENERATOR PROTECTION
PROTECTION
System Effects
Concerns
Shaft Torques
Accidental Energizing
Unbalanced Currents
Improper Synchronising
Abnormal Voltages
Transient Instability
GENERATOR
GENERATOR PROTECTION
PROTECTION
System Effects
Accidental Energisation
~
Operating Errors
Induced Currents
Mechanical damage
Distance Relays
Directional I D M T relays
GENERATOR
GENERATOR PROTECTION
PROTECTION
VTUM
VTUM
O R VTT 11 U/V
VAA VTT
CTIG TD DO 11
CTIG
Dead Machine
Tripping
VAA Backup
Tripping
GENERATOR
GENERATOR PROTECTION
PROTECTION
Generator Tripping
32
40
46
21/51V
78
81
GENERATOR
GENERATOR PROTECTION
PROTECTION
Rotor Earth Faults
Considerations