ECEN 667 Power System Stability
ECEN 667 Power System Stability
2
Single Phase Induction Motor Loads
• A new load model is one that explicitly represents the
behavior of single phase induction motors, which are
quite small and stall very quickly
– Single phase motors also start slower than an equivalent three
phase machine
• New single phase induction motor model (LD1PAC) is
a static model (with the assumption that the dynamics
are fast), that algebraically transitions between running
and stalled behavior based on the magnitude of the
terminal voltage
3
Single Phase Induction Motor
Loads
Model is mostly
algebraic, but
with stalling
behavior
4
Composite Load Models
• Many aggregate loads are best represented by a
combination of different types of load
– Known as composite load models
– Important to keep in mind tbat the actual load is
continually changing, so any aggregate load is at best an
approximation
– Hard to know load behavior to extreme disturbances
without actually faulting the load
• Early models included a number of loads at the
transmission level buses (with the step-down
transformer), with later models including a simple
distribution system model
5
CLOD Model
• The CLOD model represents the load as a combination
of large induction motors, small induction motors,
constant power, discharge lighting, and other
Transmission Bus
Distribution
Capacitors
Distribution Bus
6
CLOD Model
• Different load classes can be defined
Customer Large Motor Small Motor Discharge Constant Power Remaining (PI,
Class Lighting QZ)
8
Modeling Time Variation in Load
• Different time varying composite model parameters are
now being used
PL BV sin 0
QL BV cos BV 2 0
18
Bifurcations
• In general, bifurcation is the division of something into
two branches or parts
• For a dynamic system, a bifurcation occurs when small
changes in a parameter cause a new quality of motion
of the dynamic system
• Two types of bifurcation are considered for voltage
stability
– Saddle node bifurcation is the disappearance of an equilibrium
point for parameter variation; for voltage stability it is two
power flow solutions coalescing with parameter variation
– Hopf bifurcation is cause by two eigenvalues crossing into the
right-half plane
19
PV and QV Curves
• PV curves can be traced by plotting the voltage as the
real power is increased; QV curves as reactive power is
increased
– At least for the upper portion of the curve
• Two bus example PV and QV curves
20
Small Disturbance Voltage Collapse
• At constant frequency (e.g., 60 Hz) the complex power
transferred down a transmission line is S=VI*
– V is phasor voltage, I is phasor current
– This is the reason for using a high voltage grid
• Line real power losses are given by RI2 and reactive
power losses by XI2
– R is the line’s resistance, and X its reactance; for a high
voltage line X >> R
• Increased reactive power tends to drive down the
voltage, which increases the current, which further
increases the reactive power losses
21
PowerWorld Two Bus Example
x=0.2
x=0.2
Bus 1 Bus 2 0.933 pu
150 MW
slack
50 Mvar
Convergence
regions with
P=100 MW,
Q=0 Mvar
23
Load Parameter Space Representation
• With a constant power model there is a maximum
loadability surface, S
– Defined as point in which the power flow Jacobian is
singular
– For the lossless two bus system it can be determined as
PL2 1
QL B 0
B 4
24
Load Model Impact
• With a static load model regardless of the voltage
dependency the same PV curve is traced
– But whether a point of maximum loadability exists
depends on the assumed load model
• If voltage exponent is > 1 then multiple solutions do not exist
(see B.C. Lesieutre, P.W. Sauer and M.A. Pai “Sufficient
conditions on static load models for network solvability,”NAPS
1992, pp. 262-271)
x=0.2
Change load to
Bus 1
x=0.2
Bus 2 0.943 pu constant impedance;
slack
133 MW hence it becomes a
44 Mvar
linear model
25
ZIP Model Coefficients
• One popular static load model is the ZIP; lots of
papers on the “correct” amount of each type
Table 1 from M. Diaz-Aguilo, et. al., “Field-Validated Load Model for the Analysis of CVR in Distribution Secondary Networks: Energy
Conservation,” IEEE Trans. Power Delivery, Oct. 2013
Table 7 from A, Bokhari, et. al., “Experimental Determination of the ZIP Coefficients for Modern Residential, Commercial, and Industrial
Loads,” IEEE Trans. Power Delivery, June. 2014 26
Application: Conservation Voltage
Reduction (CVR)
• If the “steady-state” load has a true dependence on
voltage, then a change (usually a reduction) in the
voltage should result in a total decrease in energy
consumption
• If an “optimal” voltage could be determined, then this
could result in a net energy savings
• Some challenges are 1) the voltage profile across a
feeder is not constant, 2) the load composition is
constantly changing, 3) a decrease in power
consumption might result in a decrease in useable
output from the load, and 4) loads are dynamic and an
initial decrease might be balanced by a later increase 27