TSPL - Generator - Protecction.

The document provides details of generator protection settings, including settings for differential protection, stator earth fault protection, rotor earth fault protection, loss of excitation protection, over/under voltage protection, overall differential protection, over fluxing protection, reverse power protection, pole slipping protection, interturn protection, start up/shut down protection, error power protection, and under/over frequency protection. It lists the protection type, settings, interlocks, and tripping causes for 13 protection schemes on the 660MW generator.

Uploaded by

Amaresh Nayak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
328 views8 pages

TSPL - Generator - Protecction.

The document provides details of generator protection settings, including settings for differential protection, stator earth fault protection, rotor earth fault protection, loss of excitation protection, over/under voltage protection, overall differential protection, over fluxing protection, reverse power protection, pole slipping protection, interturn protection, start up/shut down protection, error power protection, and under/over frequency protection. It lists the protection type, settings, interlocks, and tripping causes for 13 protection schemes on the 660MW generator.

Uploaded by

Amaresh Nayak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 8

Generator Protection

Generator Design Data:

QFSN-C
Model

660MW(776.5MVA)
Rated power

22KV
Rated voltage

20.377KA
Rated current

Rated power factor 0.85(lagging)

Rated excitation current

Rated excitation voltage 468.21V(calculated value)

156.2 V
Rated noload excitation voltage

50HZ
Rated frequency

3000r/min
Rated speed

Connection mode Double star

6
Outlet terminal number
Capability Curve
Types of Generator Faults
1. Internal Faults

Inter-turn Faults Field winding Earth Faults Excitation System Faults

2. External Faults

Transformer Faults Line Faults


S.NO Protection Setting Interlock Tripping Cause
Generator Differential Protection(87G) Initial Setting – 0.25Ie
This offers a selective and high speed Initial Slope – 0.08
Trips both Generator
01 protection for the generator against any Instant Setting – 4Ie and Turbine
internal fault such as winding earth fault, Maximum Slope – 0.5
phase to phase short and inter-turn faults. Instantaneous Tripping

Generator Stator Earth Fault


Protection(51G & 59N)
1. 100% Stator Earth Fault
In this protection, some High freq Zero Seq Voltage
setting Low - 7.5V
Low current signal will be injected
on neutral side and will isolate the Zero Seq Voltage
setting High - 15V Trips both Generator
02 Generator during fault even Time delay - 1sec and Turbine
Generator on stand still condition.
100% of winding will be saved
Third harmonic
2. 95% Stator Earth Fault Protection setting – 0.3
This protection based on Voltage Time delay - 3sec
increase in the Broken Delta
winding during fault, 95% of Stator
wining will be saved

Alarm setting –
Rotor Earth Fault Protection(64F)
Stage-1 20K.Ohm
Tripping setting –
In this stage the relay operates when 10K.Ohm Trips both Generator
the Grounded resistance below the set
03 value. Time Delay – 3.5sec and Turbine
Stage-2
Tripping setting – 1V
In this stage the relay will operate on Time Delay – 1.0sec
voltage injection principle.
S.NO Protection Setting Interlock
1. Rotor under
Zone 1 - Voltage
2.56Ohms/0.3sec 2. Stator under
04 Loss of Excitation Protection(40Z) Zone 2 - voltage Trips only HVCB
Relay will operate on Fault Impedance. 33.97Ohms/0.5sec 3. Reduced power
output
4. VT Failure

Under/Over Voltage
Protection(27&59) OV setting – Secondary side MCB
143V/0.5sec Trips both HVCB and
05 Relay will operate during UV setting – 99V/2.5sec VT Failure Field Breaker
Decrease/Increase in voltage of the
Stator terminal.
Overall & GT:
Generator Over all Diff Initial Slope – 0.4Ie
Protection(87O) Initial Slope – 0.15
The overall differential protection Instant Setting – 4Ie
Maximum Slope – 0.7 Trips both Generator
06 covers Generator transformer, UT: HVCB Close feedback and Turbine
Generator and Unit auxiliary Initial Slope – 0.4Ie
Transformers also. This will act as a Initial Slope – 0.15
back up to generator differential Instant Setting – 8Ie
protection Maximum Slope – 0.7
Instantaneous Tripping
Over Fluxing Protection(24)
Over fluxing relay, which measures the
ratio of voltage to frequency, is used to
protect the transformer under this Stage-1 V/Hz – 1.3/1sec Trips both HVCB and
condition. This relay will have two-step Stage-2 V/Hz –
07 action, first step to initiate lowering the 1.1/20sec Above 100% voltage Field Breaker
excitation and second step to trip the
generator after a time delay if the
condition persists.
S.NO Protection Setting Interlock
Reverse Power Protection(32) 1. HVCB close feedback
The reverse power flow using Power setting – 1% 2. Turbine steam inlet Trips both HVCB, Field
08 breaker and Turbine
directional power relay with a time Time delay – 63sec valve
delay 3. VT Failure
Zone 1 – 3.3Ohms
Zone 2 – 4.29ohms
Generator Pole Slipping Protection(78) Trips only HVCB
09 Relay will operate on Fault impedance Zone 3 – 1.88Ohms VT Failure
Sensitive Angle –
90Deg
Zero Seq Voltage
setting
Low side – 2V
Generator Inter turn Protection High side – 6V VT Failure Trips both Generator
10 This protection is provided for faults Time Delay – 0.2sec and Turbine
between turns of the same phase. Back up Negative
sequence voltage
setting(U2) – 7.7V
Current setting – 5.8A
Start up/Shut down Protection
This Protection will operates when GT Diff setting – 0.7Ie Trips both Generator
11 earth fault or phase-phase faults UT Diff setting – 0.5Ie Frequency and Turbine
during low speed operation of Generator - 0.4Ie
Generator.
Error Power on Protection Current setting – 0.7A Trips both Generator
12 This protection is provided against Error closing delay – Frequency and Turbine
incorrect closing of HVCB Poles. 0.2S
Under frequency –
Under/Over Frequency 48Hz/300min
Protection(81O&U) Trips both Generator
47.5Hz/1min VT Failure
13 Relay will operates when frequency is Over frequency – and Turbine
lower/highger than the its setting for
specified time Interval. 51.5Hz/30sec
51Hz/3min