Design and Analysis For Wind Loads
Design and Analysis For Wind Loads
2
Project Description
The project is located in Salfit
Block
(2)
4
Ground Floor Architectural Plan
Block (3)
Block
Block (1) (2)
5
First Floor Architectural Plan
Block (3)
Block
Block (1) (2)
6
Second Floor Architectural Plan
Block (3)
Block
Block (1) (2)
7
Third ( Roof ) Floor Architectural Plan
Block (3)
Block
Block (1) (2)
8
Objectives of Graduation Project
1) To form a better knowledge about the different engineering
codes such as UBC-97 and IBC-2012 regarding :
Earthquake Loads
Wind Loads
2) To make a preliminary design for the structural members in
each block.
3) To analyze and design Block (1) using a 3D structural model
using the provisions of UBC-97 and IBC-2012.
4) To do a simplified comparison between the results and design
obtained from UBC-97 and IBC-2012
9
The Codes Used in This Project
The Codes used in this project are the following :
10
Seismic Zone Requirements (UBC-97)
Seismic Zone Factor (Z) Map Prepared By An-Najah National
University is used to determine the seismic zone for Salfit
11
Seismic Zone Requirements (IBC-
2012)
Mapped Acceleration parameters (S1 and SS) are shown below :
SS = 0.6
S1 = 0.3
13
Structural Materials
2) Reinforcing Steel
14
Non-Structural Materials
1) Concrete Blocks
16
Non-Structural Materials
3) Plastering:
Three layers of plastering will be used to achieve the
required smoothness with an average thickness of 20mm
for each layer
4) Tiles:
The main two types of tiles that will be used in the building
are Mosaic Tiles for internal rooms and Ceramic Tiles for
kitchens and WCs with an average density of 2500 kg/m3
17
The Philosophy of Design
A 3D Model was constructed and analyzed using SAP2000 program
taking into consideration the effects of dynamic Loads
The connections between the footings and the column necks were
represented as pin connections.
19
Load Types
2. Snow Load:
Site Snow Load (So) = (532 – 400) / 320 = 0.4125 kN/m2
20
Load Types
3. Super Imposed Dead Load:
i. Filling Material: 100mm of crushed gravel mixed with sand is
used having a density of 1800 kg/m3
Filling Material Load = 0.1 X 1800 = 180 kg/m2
21
Load Types
iii. Tiles: an average thickness of tiles were taken as 30mm with a
density of 2500 kg/m3
Tiles Load = 0.03 X 2500 = 75 kg/m2
22
Load Types
iv. Internal Walls: two types were used:
Single Layer (100mm) internal wall load per meter run =
0.1 X 1200 X 3.64 = 436.8 kg/m = 4.25 kN/m
Double Layer (250mm) internal wall load per meter run =
0.2 X 1200 X 3.64 = 873.6 kg/m = 8.5 kN/m
23
Load Combinations
Using IBC 2012:
24
Load Combinations
Using UBC 1997:
25
Preliminary Design of The Project
To do the preliminary design for the blocks the following
procedure is used :
28
Equivalent Lateral Force (IBC-2012)
The Following Parameters are used in the calculations :
(Equation 1-41)
(Equation 1-42)
30
Equivalent Lateral Force (IBC-2012)
The following Table shows the calculations of structural
period according to Equation 1-41 and Equation 1-42 :
34
Equivalent Lateral Force (UBC-97)
The Following Parameters are used in the calculations :
35
Equivalent Lateral Force (UBC-97)
Due to the existence of concrete shear walls the following
formula where used:
Ac = 5.45 m2
Ct = 0.0318
(Equation 1-9)
(Equation 1-11)
(Equation 1-10)
37
Equivalent Lateral Force (UBC-97)
Applying the previous Equations :
39
Calculating Wind Load (UBC-97)
The Following Parameters are used in the calculations :
40
Calculating Wind Load (UBC-97)
41
Wind Load-Block 1 (UBC-97)
Windward Pressure = Ce Cq qs Iw
= 1.06 X 0.8 X 0.7 X 1 = 0.6 kN/m2
42
Wind Load-Block 1
(UBC-97)
43
Calculating Wind Load (IBC-2012)
The Following Parameters are used in the calculations :
45
Wind Load - Block 1 (IBC-2012)
Windward Pressure (P) = qz X G X Cp
= 1063 X 0.85 X 0.8 / 1000 = 0.723kN/m2
46
Wind Load-Block 1
(IBC-2012)
47
Structural 3D Modeling
The structure is modeled using SAP2000 program
All Window Openings were considered
48
Verification of Structural Analysis
1) Compatibility Check :
The following figure proves the compatibility of the model
49
Verification of Structural Analysis
2) Equilibrium Verification
v. Wind Loads
The following table shows the base reactions obtained from the
analysis of SAP2000
51
Verification of Structural Analysis
1. Live Load Verification
Total Live Load from hand calculation = 5484 kN
Total Live Load from SAP2000 program = 5320 kN
Difference Percentage = (5848-5319)/5484 = 3%
52
Verification of Structural Analysis
3. Superimposed Dead Load Verification
Super Imposed Dead Loads = 10924kN
Value from SAP2000 Program =10832kN
Difference Percentage = (10924-10832)/10924 = 0.85%
53
Verification of Internal Forces
1) Check of Slabs Internal Forces
Ultimate Load (Wu) = 14.5 kN/m
Bending Moment According to SAP2000 = 7.81 kN.m
The clear span (ln) = 3.0m
Using the ACI Coefficient Method for analysis :
Bending Moment = Wu ln2/16 = 14.5x32/16 = 8.156 kN.m
Difference Percentage
=(8.156-7.81)/8.156
= 4.24 %
54
Verification of Internal Forces
2) Check of Beams Internal Forces
The following figure shows the beam to be checked
Figure 3-26 The Plan of The Beam Selected for Internal Forces Check 55
Verification of Internal Forces
Bending Moment Diagram Obtained From SAP2000 :
61
Serviceability Check
The Long term deflection = 84mm
Allowable Deflection = L/240 = 12.8/240 = 54mm
The Long term deflection exceeds the allowable limit
Beam Dimensions increased from 400x500mm to 500x700
62
Check of Lateral Forces
The following table shows a comparison between the value of lateral
forces obtained by hand calculation and by SAP2000.
63
Structural Design of Concrete
Members
1) The code used for design and detailing is ACI 318-11 regarding
seismic and gravity loads.
2) The structural system is Building Frame System with Special
Shear Walls ( Intermediate Frames ).
3) Provisions were applied to all structural members including:
Beams
Columns
Shear Walls
Foundations
Tie Beams
64
Structural Design of Concrete
Members
Design and Detailing of Intermediate Beams :
1) Positive moment strength at joints shall be at least one third the
negative moment strength.
2) Negative and positive moment strength at any section shall be at
least one fifth the moment strength at joints.
3) Hoops shall be provided at a distance (2h) from the joints with a
spacing equals the minimum of
65
Structural Design of Concrete Members
66
Structural Design of Concrete
Members
Sample Design for Beams :
1) The beam to be designed is (B2) in GF between gridlines (C&E)
2) Dimensions : B =400mm, h =450mm, d =390mm, Span =5.53m
3) Ultimate Moment (Mu)= 180 kN.m, Ultimate Shear (Vu)= 167 kN
4) Reinforcement ratio
67
Structural Design of Concrete Members
Sample Design for Beams :
1) For Top Steel, 2Ø16 are provided as continuous bars As=402mm2
2) Cut-off bars at a distance of (ln/3) = 2m are used for the remaining
area As= 1301-402 = 900mm2, use 3Ø20.
3) For Bottom Steel, As=611mm2, use 4Ø14.
4) Spacing of Hoops = 100mm (at a distance 2h from joints faces).
5) Spacing of other Hoops = 200mm.
68
Structural Design of Concrete Members
Sample Design for Beams :
Figures below show the longitudinal section and cross sections for B2 :
69
Structural Design of Concrete Members
Design and Detailing of Special Shear Walls :
1) Transverse and Longitudinal rebar ratio (ρt and ρl) shall be at least
0.0025
2) Spacing of reinforcement shall not exceed 450mm
3) Two diagonal bars Ø16 shall be provided at the corners of openings
4) Effective depth = 80% of Shear wall length (lw)
5) Nominal Shear Capacity (Vn) shall not exceed Equation 3-24:
71
Structural Design of Concrete Members
Sample Design for Shear Walls :
1) The shear wall to be designed is (SW7) between gridlines (1&2)
2) Dimensions : L = 3250mm, bw = 200mm, d = 2600mm
3) Mu,major= 1403 kN.m, Mu,minor= 100 kN.m, Pu=1700 kN, Vu=385kN
72
Structural Design of Concrete Members
Sample Design for Shear Walls :
5) To account for minor moment, additional steel is needed:
74
Structural Design of Concrete Members
Design and Detailing of Special Shear Walls :
11) Wall piers reinforcement and Diagonal bars around openings are
also provided as shown :
75
Structural Design of Concrete
Members
Design and Detailing of Columns :
1) Spacing (So) shall be provided at both ends for length (L o):
76
Structural Design of Concrete Members
77
Structural Design of Concrete
Members
Sample Design for Columns :
1) The Column to be designed is (C8)
in GF between gridlines (3&E)
2) Dimensions : Square (500X500)mm
Clear Length = 4.42m
3) Ultimate Moment (Mu)= 12.5 kN.m
Minimum Moment = 36.4 kN.m
Ultimate Axial (Pu)= 1214 kN
Axial Capacity (Ø Pn,max) = 3600 kN
4) Reinforcement Ratio = 1%
As = 2500 mm2 (16 Ø 14)
78
Structural Design of Concrete Members
•Sample
Design for Columns :
Check of Column Slenderness
• Moment of Inertia (I) = 5.2 X 10-3 m4
• Area (A) = 0.25 m2
• Radius of Gyration (r) = 0.144 m
• Effective Length Factor (K) = 1.0
• Unbraced Length (Ln) = 4.25 m
• Slenderness Ratio = = 29.5
• Moment 1 = 0 Moment 2 = 12.5 kN.m
• 34 – 12 = 34 > 29.5 Non-Slender Column
79
Structural Design of Concrete Members
Sample Design for Columns :
1) For Ø 14, Lap Splice = 800mm
2) Distance (Lo) = 700mm
Spacing (So) = 100mm
3) Spacing outside (Lo) = 200mm
80
Structural Design of Concrete
Members
Design and Detailing of Slabs :
1) Flexural Capacity of slabs is given by:
81
Structural Design of Concrete
Members
Sample Design for Slabs :
The GF Slab is going to be designed
Dimensions : Strip width = 1000mm, h = 150mm, d = 120mm
IN X-DIRECTION
1) Ultimate Moment (Mu) = 10 kN.m
2) Reinforcement Ratio
2) Reinforcement Ratio
84
Structural Design of Concrete Members
Sample Design for Slabs :
1) When the longitudinal bar ends
with a beam use 90o hook;
Development (Ldh ) = 180mm
Bent Radius = 40mm
Hook Length = 120mm
85
Structural Design of Concrete
Members
Seismic Requirements For Footings:
1) The development length shall be checked at both ends of the footing using
standard hook depending on the bar size.
2) The hoops of the columns shall be continued in the footing at least 300mm
from the top face of footing.
3) The clear cover below the footing shall be at least 70mm if there is no
blinding layer, and 40mm in the case of having a blinding layer.
4) The longitudinal bars of the columns shall extend in the footing with a
standard hook noticing that the extensions of the standard hook are
pointed towards the center of the column in each direction.
5) Service combinations are used to determine the largest axial service load
considering the earthquake effect in these combinations :
→ 0.6D + 0.7E → 1.0D + 0.75L + 0.75E → 1.0D + 0.70E 86
Structural Design of Concrete Members
87
Structural Design of Concrete
Members
Sample Design for single footings:
1) The footing to be designed is (F1) for Column (9)
2) General information for column (9): cross section= 500x500mm,
PService=1370KN, Pultimate = 2360KN.
3) Calculating the required area :
88
Structural Design of Concrete
Members
Sample Design for single footings:
89
Structural Design of Concrete
Members
Sample Design for single footings:
8) Checking the punching shear which is the minimum of the
following equation:
While the ultimate shear on the footing equals to the ultimate stress
multiplied by the area = 377.6 x 2.5 x 2.5 = 2360KN.
90
Structural Design of Concrete
Members
Sample Design for single footings:
9) The ultimate moment on the footing =
So use minimum steel with 1Ø18/200mm as a bottom steel and half the
shrinkage as top steel 1Ø14/200mm. 91
Structural Design of Concrete
Members
Sample Design for single footings:
92
Structural Design of Concrete Members
•Design
for Tie Beams :
1) Tie Beams shall have an axial design strength for a force not less than:
Pu = 0.1 X SDS X Pcolumn
where Pcolumn is the largest ultimate load between the columns.
As =
2) To take into consideration the positive and negative moments that may
result in the tie beam, 2 layers of minimum Area of steel where
applied, one of them as a top layer and the other as a bottom one.
As,minimum =
93
Structural Design of Concrete Members
•Design
for Tie Beams :
1) Assuming dimensions:
b = 350 mm, h = 700 mm, d = 640 mm
2) Pu = 0.1 X 0.46 X 2364 = 113.5 kN
3) As = = 300.2 mm2 use (4 Ø 12)
94
Comparison between UBC-97 and IBC-
2012
1) Comparison is done between UBC-97 and IBC-2012 codes
regarding the following :
a) Wind and earthquake forces
b) Detailing requirements and provisions
c) Design results ( required reinforcement )
2) Table 3-9 shows a brief comparison between the two codes
95
Comparison between UBC-97 and IBC-
2012
Comparison of Detailing Requirements:
1) IBC-2012 uses ACI 318-11 and UBC97 uses ACI 318-95 for detailing
2) For Intermediate Beams, ACI 318-11 stipulates the following :
a) Positive moment strength at joints shall be at least one third the negative
moment strength.
b) Negative and positive moment strength at any section shall be at least
one fifth the moment strength at joints.
c) Hoops shall be provided at a distance (2h) from the joints with a spacing
equals the minimum of
c) The first hoop shall not be located more than (S o/2) from the joint face
Comparison between UBC-97 and IBC-
2012
Comparison of Detailing Requirements:
4) These Figures are cropped literally from ACI 318-95 for Beams :
Comparison between UBC-97 and IBC-
2012
Comparison of Detailing Requirements:
5) These Figures are cropped literally from ACI 318-95 for Columns :
Comparison between UBC-97 and IBC-
2012
Comparison of Design Results :
1) Two models for UBC-97 and IBC-2012 are designed in order to
compare the design results obtained from SAP2000 Program.
2) These figures show the area of longitudinal bars for Frame 3-3
IBC-2012 UBC-97
Comparison between UBC-97 and IBC-
2012
Discussion and Conclusion:
1) Base shear obtained from IBC-2012 is slightly larger than Base shear
obtained from UBC-97 ( VIBC = 2163 kN > VUBC = 2097 kN ).
2) The minor difference in seismic base shear (V) between both codes
will not yield a considerable difference in the results of design.
3) Detailing requirements of seismic design for both ACI 318-11 and
ACI 318-95 are the same.
4) Both codes are applicable and yield good design results.
5) For PALESTINE, UBC-97 is still good although the probability of
exceedance is 10% compared to IBC-2012 (2%) when using the local
maps ( Israeli Code for SS and S1, Seismic Zone Factor Map for Z )
The End
102