Gen. Prot. WOA
Gen. Prot. WOA
PROTECTION
&
INTERLOCK
1
Type of Generator Protection
1. Voltage Controlled Over Current Protection (51V)
2. Dead Machine Protection (50/27)
3. Generator Circuit Breaker Failure (50BF)
4. Over Excitation Protection (24G)
5. Over Voltage Protection (59)
6. Reverse Power Protection (32R)
7. Low Forward Power Protection (32F)
8. Differential Protection (87G)
9. Under Frequency Protection (81G)
10. Over Frequency Protection (81G)
11. Loss of Excitation (40G)
12. 95 % Stator Earth Fault (64G1)
13. 100 % Stator Earth Fault (64G2)
14. Generator Rotor Earth Fault (64F)
15. Exciter Rotor Earth Fault
16. I&C Trip from ETS.
17. Excitation System Fault
18. Generator Pole Slipping (78)
19. Negative Phase Sequence Protection (46)
20. Backup Impedance Protection (21)
21. Generator Cooling Water Loss
22. Conductivity High High
Confidential Slide 2
Classification of generator protection
tripping
1. Class A-I
2. Class A-II
3. Class B
OR
4. Class A
5. Class B
6. Class C
Confidential Slide 3
Objective of classification of protection
tripping
1. Damage is minimum.
Confidential Slide 4
Classification depends on following points
Plant layout
Confidential Slide 5
Without GCB Scheme
Generator synchronizing
done at switchyard.
Classification of generator
protection tripping in this
scheme are
1. Class A
2. Class B
3. Class C
Confidential Slide 6
Class A
Class A trip involves a serious electrical fault like differential, stator earth fault etc
and is considered to be the most dangerous in terms of the shock on the unit. Since it
involves serious electrical faults, connections from both generator and the EHV bus is
immediately switched off to limit the damage at the fault point and also to isolate the
healthy system. Hence the unit (turbine, generator and boiler) has to be tripped.
Class B
Class B primarily relates to mechanical problems. This results in tripping of turbine
followed by generator.
Class C
Class C involves basically external system related problems like frequency, overvoltage
etc. This does not involve instant tripping of the unit. CPP unit operates on house load.
Confidential Slide 7
With GCB Scheme
Generator synchronizing done
at TG building.
Classification of generator
protection tripping in this
scheme are
1. Class AI
2. Class AII
3. Class B
Confidential Slide 8
To GRID
205 BAY
BRK.
GCB
205 BAY
BRK.
GCB
In this class, trip goes to following equipments with out time delay.
Turbine,
EHV breaker,
UAT LV breaker,
Field breaker.
Confidential Slide 11
There are three generator protections come into
Class-AI.
1. Voltage Controlled Over Current Protection (51V).
Confidential Slide 12
To GRID
205 BAY
BRK.
GCB
Turbine,
Field breaker.
Confidential Slide 15
To GRID
Low Forward Power
OR Reverse Power
Class B Protection Operated
Protection will Operate
205 BAY
BRK.
GCB
Confidential Slide 17
Generator Protection Relay
1. 7UM6225 Main
Protection relay
2. 7UM6115 Backup
Protection relay
Confidential Slide 18
Voltage Controlled Over Current Protection (51V)
Relay Setting
Confidential Slide 19
Block Diagram for 51V
Confidential Slide 20
Dead Machine Protection (50/27)
Confidential Slide 21
Relay Setting
Confidential Slide 22
Generator circuit breaker failure (50BF)
DC supply fail
Relay Setting
Confidential Slide 23
Block Diagram for 50BF
Confidential Slide 24
Over Excitation Protection (24G)
Confidential Slide 25
Note - A overvoltage protection can provide partial backup, but will
not be effective at reduced operating frequencies
Relay Setting
Stage -1 Stage-2
V/F Pick up = 1.15 V/F Pick up = 1.25
Time Delay = 10.0 sec Time Delay = 2.0 sec
Confidential Slide 26
Over Voltage Protection (59)
2. Operation under manual control with the voltage regulator out of service. A
sudden variation of the load, in particular the reactive power component,
will give rise to change in voltage.
3. Sudden loss of load (due to tripping of outgoing feeders, feeding a very small
load) may cause a sudden rise in terminal voltage due to the trapped field
flux.
Confidential Slide 27
Relay Setting
Stage-1 Stage-2
59-1 Pick up = 24 kV 59-1 Pick up = 26 kV
59-1 Time delay (T1)= 3.0 sec 59-1 Time delay(T2) = 0.5 sec
Confidential Slide 28
Frequency Protection (81)
Confidential Slide 29
Example For Frequency Protection
Grid - 1 Grid - 2
Xmission
Line 12
Xmission
Xmission
Line 2
Line 1
300 MW 300 MW
GEN.-1 GEN.-2
Confidential Slide 30
Healthy Condition
Grid - 1 Grid - 2
Load Demand 50 MW
Load Demand
350 MW 250 MW
Xmission
Line 12
Xmission
Xmission
Line 2
Line 1
Generation MW Generation MW
300 300
GEN.-1 GEN.-2
Confidential Slide 31
Fault on Xmission line - 12
Grid - 1 Grid - 2
Load Demand 50 MW
Load Demand
350 MW 250 MW
Xmission
Line 12
Xmission
Xmission
Line 2
Line 1
Generation MW Generation MW
300 300
GEN.-1 GEN.-2
Relay Setting
Under Frequency Over Frequency
Stage -1 for Class B Stage -1 for DCS
81 Pick up = 47.50 Hz 81 Pick up = 51.50 Hz
Time Delay = 20 sec Time Delay = 5 sec
Confidential Slide 34
Gen. Differential Protection (87G) SLD
GCB
7UM6225
Relay
Confidential Slide 35
Over All Differential Protection (87OA) SLD
Confidential Slide 36
95 % Stator Earth Fault
Confidential Slide 37
Block Diagram for 95%
V0>
Relay Setting
Confidential Slide 38
100 % Stator Earth Fault
In this method 20Hz voltage signal injects into the sec. of the NGT.
Components
20Hz generator – it generates 20Hz signal
Band pass filter – passes only 20Hz signal and rejects out of band signals.
Confidential Slide 39
Block Diagram for 100%
Relay Setting
R< SEF Alarm = 128 ohm
R<< SEF Trip = 26 ohm
T SEF Alarm = 10 sec
T SEF Trip = 2 sec
SEF I>> = 0.49 A
U20 Min. > 0.5 V
I20 Min > 5mA
Confidential Slide 40
Low Forward Power Protection (32F)
This is to minimize the risk of plant over speeding when the electrical load
is removed from a high-speed generator.
Relay Setting
Confidential Slide 41
Block Diagram for 32F
Confidential Slide 42
Reverse Power Protection (32R)
Relay Setting
Confidential Slide 43
Block Diagram for 32R
Confidential Slide 44
I&C Trip
When we start unit for the first time, we use I&C protection for checking
the Polarity of CT & PT.
Block Diagram
Turbine trip
feedback BI - 15 Class AII
from ETS
Confidential Slide 45
Excitation System Faults
Block Diagram
Trip feedback
from AVR BI - 4 Class AII
panel
Confidential Slide 46
Generator Rotor Earth Fault
The field circuit of a generator, is
an isolated d.c. circuit which is not
normally earthed.
Any unbalanced condition can be resolved into positive, negative and zero
sequence components.
Confidential Slide 48
Effect - Negative sequence component produced a flux which cuts the
rotor at twice the rotational velocity, thereby inducing double
frequency currents in the field system and in the rotor body. The
resulting eddy-currents are very large and cause severe heating of
the rotor.
Confidential Slide 49
Thanks
50