230L1E191 - Distributed Control Unit (DCU)

The document describes the evolution of Distributed Control Units (DCUs) introduced by Schlumberger in the 1990s. It discusses three generations of DCUs - DCU I (DIP360), DCU II (CSD363), and DCU III (CSD364). The DCUs replaced older remote data acquisition devices and added distributed control capabilities for various downhole equipment. Each new generation provided additional functionality while maintaining footprint and connector compatibility with previous versions for ease of use.

Uploaded by

yao nestor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
657 views

230L1E191 - Distributed Control Unit (DCU)

The document describes the evolution of Distributed Control Units (DCUs) introduced by Schlumberger in the 1990s. It discusses three generations of DCUs - DCU I (DIP360), DCU II (CSD363), and DCU III (CSD364). The DCUs replaced older remote data acquisition devices and added distributed control capabilities for various downhole equipment. Each new generation provided additional functionality while maintaining footprint and connector compatibility with previous versions for ease of use.

Uploaded by

yao nestor
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 58

Distributed Control Unit

DCU

Schlumberger Private
Ref: 230L1E191

Herman Bruins
Maintenance Senior Instructor- Electronic
Schlumberger

Written by : Herman Bruins Date: Dec 21th, 2007


Reviewed by: Date: mmm ddth, yyyy
Approved by: Date: mmm ddth, yyyy
Distributed Control Unit (DCU)

Introduced in the 1990’s, the DCU


Replaces:
 Well Services RDA Devices:

Schlumberger Private
– Remote Data Acquisition box Rate (RDA-R)
– Remote Data Acquisition box Sensor ( RDA-S)
– Junction Acquisition Box I and II (JAB II)
Adds:
 Distributed Control for SLB sub-systems:
– Sub-Systems on Stimulation Blending Equipment
– Sub-Systems on Cementing Equipment
– Sub-Systems on Fracturing Pumps
– Sub-Systems on Coiled Tubing Equipment
– Sub-Systems on Wireline Equipment

2 JHB
Revision: 1 21-Dec-2007
Distributed Control Unit (DCU)

DCU-I (DIP360)
– First Generation

Schlumberger Private
DCU-II (CSD363)
– Second Generation
– Footprint, Connector Layout and Firmware* compatible with DCU-I

DCU III (CSD364)


– Third Generation
– Footprint, Connector Layout and Firmware compatible with DCU-II

* Firmware: Fixed program on a processor board

3 JHB
Revision: 1 21-Dec-2007
Distributed Control Unit (DCU)

Footprint & Connector Layout

Schlumberger Private
4 JHB
Revision: 1 21-Dec-2007
DCU Hardware

First generation: DCU I (DIP360).


 Input channels:
– 8 Analog, 0-10V/0-20mA, 16-Bit ADC
– 8 Frequency, 4-8mA, 20kHz, 16-Bit Counter

Schlumberger Private
– 2 Digital, 4-8mA

 Output channels:
– 2 Analog, 0-10V and 0-20mA, 12-Bit DAC
– 4 Digital, 4A, (Raw/Dirty Power)

 Communication ports:
– 2 Serial (RS-232),
– 1 CAN-bus.

Note: ADC: Analog Digital Conversion


DAC: Digital Analog Conversion
5 JHB
Revision: 1 21-Dec-2007
DCU Hardware

Second generation: DCU II (CSD363).

 Input channels:
– 8 Analog, Filtered*, 0-10V/0-20mA, 16-Bit ADC
– 8 Frequency, 4-8mA, 20kHz, 16-Bit Counter

Schlumberger Private
– 2 Digital, 4-8mA

 Output channels:
– 2 Analog, 0-10V and 0-20mA, 12-Bit DAC
– 2 Digital, 4A, (Raw/Dirty Power)
– 2 Digital/PWM, 4A, (Raw/Dirty Power)**

 Communication ports:
– 2 Serial (RS-232/RS-485) ***
– 2 CAN-bus channels ****

* Analog inputs filtered


** Processor support for PWM signals
*** Serial port 2 RS-232 / RS 485 configurable
**** Additional CAN-bus
6 JHB
Revision: 1 21-Dec-2007
DCU Hardware

Third generation: DCU III (CSD364).

 Input channels:
– 8 Analog, Filtered, 0-10V/0-20mA, 16-Bit ADC
– 8 Frequency, 4-8mA, 20kHz, 16-Bit Counter

Schlumberger Private
– 2 Digital, 4-8mA

 Output channels:
– 2 Analog, 0-10V and 0-20mA, 12-Bit DAC
– 4 Digital/PWM, 4A, (Raw/Dirty Power)*

 Communication ports:
– 2 Serial (RS-232/RS-485)
– 2 CAN-bus channels
– 1 Sofi-bus (provisional)**
– 1 Processor Control***

* All digital outputs support PWM signals


** Provisions made for Sofibus connectivity
*** Processor Control (Additional connector)
7 JHB
Revision: 1 21-Dec-2007
DCU Hardware

DCU I (DIP360).

 Processor:
– Intel 80C196, Advanced 16-Bit CHMOS Microcontroller, 16MHz, Integrated CAN* V2.0

Schlumberger Private
DCU II (SCD363) and DCU III (SCD364).

 Processor
– Infineon C167CS, 16-bit CMOS Single-Chip Microcontroller, 33MHz, Dual integrated CAN,
4 - Channel PWM**

* CAN: Controller Area Network


** PWM: Pulse Width Modulation

8 JHB
Revision: 1 21-Dec-2007
DCU
Inputs

Analog (P2)
 8 Analog inputs.
– Voltage 0-10VDC
– Current 0-20mA (Jumpers are required to activate 500 current loop resistor)
• Load resistor 500converts 0-20mA to 0-10V
• ie:

Schlumberger Private
– 4mA @ 500  V = 4 x 10-3 x 500 = 2V
– 20mA @ 500  V = 20 x 10-3 x 500 = 10V

Frequency (P4) / Digital (P10)


 8 Frequency inputs.
– Pulse 0-20kHz
– Current 4-8mA (Jumpers are required to limit current)
• Current limiting resistors convert 5, 12 & 24V pulses to 5mA
• ie:
– 5V @ 1k  I = 5 / 1000 = 5mA
– 12V @ 2.4k  12 / 2400 = 5mA
– 24V @ 4.8 k  24 / 4800 = 5mA

 2 Digital inputs.
– Current High/Low (Same specification as frequency inputs)

9 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Analog Input (P2) DCU I

DCU I (DIP360).
V(in)

 8 Unfiltered inputs JP

10.2k, 0.1%
– 0-10V (R(i) = 13.6k)

287, 0.1%

Schlumberger Private
– JP installed 0-20mA (R(i) = 500) V(out)

– 16 bit ADC (Analog Digital Converter)

3.4k, 0.1%
1uF 7.5V

232, 0.1%
AIN1 AIN2 AIN3 AIN4 AIN5 AIN6 AIN7 AIN8
JP6 JP7 JP10 JP11 JP15 JP14 JP18 JP19
+12V

+24V

CURRENT LOOP
JP8 JP9 JP12 JP13 JP16 JP17 JP20 JP21

1 P2

ANALOG INPUTS

10 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Analog Input (P2) DCU II & III

DCU II (SCD363) and DCU III (SCD364).


V(in) 3.3k
+

JP -

 8 Filtered inputs (1.6Hz Low-pass RC filter) OPA4234

10.2k, 0.1%
– 0-10V (R(i) >10M) V(out)

Schlumberger Private
– JP installed 0 - 20mA (R(i) = 500)

3.4k, 0.1%
7.5V

1k, 0.1%

1k, 0.1%
+ +
– 16 Bit ADC (Analog Digital Converter) -
33uF
-
1uF

JP6 JP7 JP10

JP12 JP11 JP15 JP14 JP18 JP19


JP8 JP9 24V

DCU II JP13 JP16 JP17 JP20 JP21


12V

ANALOG
INPUTS 1 P2

JP6 JP7 JP10

DCU III JP8 JP9


JP12 JP11 JP15 JP14 JP18 JP19
24V
JP13 JP16 JP17 JP20 JP21
12V

ANALOG
INPUTS 1 P2

11 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Analog Input / Sensor Power connector (P2) Pin Assignment

DCU I, II and III


Input V(s) Sign Gnd
AD-1 1 2 3

Schlumberger Private
AD-2 4 5 6
AD-3 7 8 9
AD-4 10 11 12
AD-5 13 14 15

Sign in

Gnd
V(s)
AD-6 16 17 18
AD-7 19 20 21
AD-8 22 23 24
GND 25 26
1

V(s)

Sign in
Gnd
1

AIN1 AIN2 AIN3 AIN4 AIN5 AIN6 AIN7 AIN8

12 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Analog Input / Sensor power Jumpers

AIN1 AIN2 AIN3 AIN4 AIN5 AIN6 AIN7 AIN8


JP6 JP7 JP10 JP11 JP15 JP14 JP18 JP19

DCU I, II and III


+12V

+24V

Input V(s) 12/24 * Current JP8 JP9 JP12 JP13 JP16 JP17 JP20 JP21
CURRENT LOOP

Loop
DCU I

Schlumberger Private
1 P2

AD-1 JP6 JP8 ANALOG INPUTS

AD-2 JP7 JP9


JP6 JP7 JP10
AD-3 JP10 JP12
JP12 JP11 JP15 JP14 JP18 JP19
JP8 JP9 24V

AD-4 JP11 JP13 JP13 JP16 JP17 JP20 JP21

DCU II 12V

AD-5 JP15 JP16 ANALOG


INPUTS 1 P2

AD-6 JP14 JP17


AD-7 JP18 JP20 JP6 JP7 JP10

AD-8 JP19 JP21 JP12 JP11 JP15 JP14 JP18 JP19


24V
JP8 JP9
JP13 JP16 JP17 JP20 JP21
12V

DCU III ANALOG


INPUTS 1 P2

* DCU I – V(s): 12 Volt (Top) / 24 Volt (Bottom)


DCU II & DCU III – V(s): 12 Volt (Bottom) / 24 Volt
(Top)
13 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Frequency Input (P4) DCU I

DCU I (DIP360)
DCU I (DIP360) Output to
Input
Counter
Vcc
24V 4.7k
8 Inputs 1.9V

Schlumberger Private
 Input Signal: 4 – 8mA 12V 2.4k

 Frequency max: 20kHz


Frequency 1 & 2
 Optical-Isolation, Common Ground
 16-bit Counter 12V 2.4k
Vcc

 Input 1 & 2: Jumper selectable 12 or 24 1.9V

Volt
 Input 3 to 8: 12 Volt only
Frequency 3 to 8

14 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Frequency Input (P4) DCU II

DCU II (CSD363) Input


DCU II (CSD363) Output to
Counter
Vcc
24V 4.7k

8 Inputs 12V 2.4k 1.9V

Schlumberger Private
5V
 Input Signal: 4-8mA 1.1k

 Frequency max: 20kHz


Frequency 1 & 2
 Optical-Isolation, Common Ground
Vcc
12V 2.4k
 16-bit Counter 1.9V

 Input 1-2: Jumper selectable 5, 12 or 24 Volt


 Input 3-6: 12 Volt only
Frequency 3 to 6
 Input 7-8: Jumper selectable 0-700mVAC* or 12 Vcc
12V 2.4k
Volt 1.9V
0-700mV 499

Frequency 7 & 8

* Support for Magnetic pickup signals

15 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Frequency Input (P4) DCU III
DCU III (CSD364) Output to
Input
Counter
Vcc
DCU III (SCD364) 24V 4.7k

12V 2.4k 1.9V

5V 1.1k
8 Inputs

Schlumberger Private
 Input Signal: 4-8mA Frequency 1 & 2

 Frequency max: 20kHz 12V 2.4k 2.4k


Vcc

1.9V
 Optical-Isolation, Common Ground
 16-bit Counter
 Input 1-2: Jumper selectable 5, 12 or 24 Volt Frequency 3 to 6

 Input 3-6: Jumper selectable 24 or 12 Volt* 24V 4.7k


Vcc

 Input 7- 8: Jumper selectable 0-700mVAC, 5, 12V 2.4k 1.9V

12 or 24 Volt 5V 1.1k

0-700mV 499

Frequency 7 & 8

•Support for 24V pulse signals on FR3, 4, 5 and 6.


For 12V pulse signals Jumpers need to be installed.

16 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Frequency Input / Sensor Power connector (P4) pin assignment

DCU I, II and III

SHTDWN
Sign in
Input V(s) Sign Gnd Shutdown
FRIN1* 2 Switch 1-2 for FR-1
FRIN2** 4 Switch 3-4 for FR-2

Schlumberger Private
FR-1 5 6 7 8
FR-2 9 10 11 12
FR-3 13 14 15 16

V(s)

Gnd
FR-4 17 18 19 20
FR-5 21 22 23 24
FRIN2
FR-6 25 26 27 28 FRIN1 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8
12 VDC LED
24 VDC LED
P4

FR-7 29 30 31 32 1

FR-8 33 34 35 36 FIN1 FIN2 FIN3 FIN4 FIN5 FIN6 FIN7 FIN8

12V - LED 38 37
24V - LED 40 39

* FR1 to Counter via P4-1/2


**FR2 to Counter via P4-3/4

17 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Frequency Input current limiting & Sensor Power jumpers DCU I

DCU I
Input Sensor Power Signal

12V 24V 12V 24V

Schlumberger Private
FR-1 JP22R JP22L JP23R JP23L
FR-2 JP24R JP24L JP25R JP25L
FR-3 X X
DCU I
FR-4 X X
FR-5 X X
FR-6 X X
FR-7 X X
FR-8 X X

•JPxxL (Left), JPxxR (Right)


18 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Frequency Input current limiting & Sensor Power jumpers DCU II & DCU III

DCU II and III


Input Sensor Power Signal
12V 24V 700mVA 5V 12V 24V
C

Schlumberger Private
FR-1 JP22B JP22T JP34 JP23B JP23T
T
FR-2 JP24B JP22T JP35 JP25B JP25T DCU II
T
FR-3 X JP45
FR-4 X JP46
FR-5 X JP47
FR-6 X JP48
FR-7* X JP38L JP38R
FR-8* X JP39L JP39R DCU III
FR-7** X JP38L JP38 JP49R JP49L
* DCU-II R
** DCU-III
FR-8**(Top), JPxxB
•JPxxT X JP39L
(Bottom), JPxxL JP39
(Left), JPxxR JP50R JP50L
(Right) R
19 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Digital Input (P10) DCU I, II and III

DCU I, II, III JP26 JP27


Vcc
24V 4.7k
V(s)
12V 2.4k
2 Inputs DIN-1 JP30

Sign +
 Input Signal: 4-8mA

Schlumberger Private
Sign -
 Optical-Isolated Gnd
JP31

 Supports sinking* or sourcing* sensors

JP31 JP27 JP26 JP28 JP29


1

Vcc
24V 4.7k
DIGITAL INPUTS

JP30
V(s)
JP33 JP29 JP28 12V 2.4k
DIN-2 JP32

JP32
Sign +
Sign -
Gnd
JP33

*Sinking: Sensor pulls signal to ground.


*Sourcing: Sensor supplies power

20 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Jumper configuration Digital Input (P10) DCU I, II and III

Sinking Sensor
Sinking Sensor
 Pressure switch (V(s) = 24V, DIN2) JP28 JP29
Vcc
24V 4.7k
– Jumper: JP28T to JP29T
V(s)
 Pressure switch (V(s) = 12V,DIN2) 12V 2.4k

DIN-2 JP32
Jumper: JP28B to JP29B

Schlumberger Private
Sign +
Sign -

Gnd
JP33

Pressure Activate Switch

Sourcing Sensor
Sourcing Sensor
 Proximity switch 3-wire (V(s) = 24V,DIN1)
– Jumper: JP26 JP27
Vcc
24V 4.7k
• JP26C to JP26T (Vs=24VDC) V(s)
• JP27C to JP27T(Sign 24 V pulse)
12V 2.4k
• JP31 (GND) DIN-1 JP30

Sign +

Sign -
Gnd

JP31

*Sinking: Sensor pulls signal to ground. Prox


*Sourcing: Sensor supplies power Switch

21 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Digital Input / Sensor Power connector (P10) Pin Assignment

DCU I, II and III

Input DIN-1 DIN-2

Schlumberger Private
1
V(s) 1 5
V(s)1 Sig+1
Sig-1 Gnd
Sig+ 2 6 V(s)2 Sig+2
Sig-2 Gnd

Sig- 3 7 Gnd Gnd

Gnd 4 8

Gnd 9 10

22 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Analog Output Connector (P3)

DCU I, II & III


0-10V V I 0-20mA

 2 Dual Analog
– 0-20mA (12 Bit resolution)

Schlumberger Private
IC
– 0-10 Volt (12 Bit resolution) -
x1 0-10V
+

1
0-20mA (1) Gnd
0-10V (1) Gnd
0-20mA (2) Gnd
0-10V (2) Gnd
Gnd Gnd

P3

Analog Output

Note: Power supplied to 12-bit Digital to Analog converter, Volt to


Current converter and Unity Gain Follower is 24VDC regulated

23 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Digital Output Connector (P5)

DCU I
 4 Digital (Solid State switch) V(b) V(b) V(b) V(b)
– Pulse: 12 Volt (Battery/Dirty Power)
– I(max): 4 A

Schlumberger Private
P5
DCU II & III 1

 4 Digital (Solid State switch) Gnd Gnd Gnd Gnd

– Pulse / PWM: 12 Volt (Battery/Dirty Power)


– I(max): 4 A
OUT1 OUT2 OUT3 OUT4

P5
1
DIGITAL OUTPUT

24 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Signal Level – Digital Output

DOUT-1

Signal Digital Output


Solenoid 1

 Switched output DOUT-2


Solenoid 2
– 0 or 12 Volt
– Uses: 100%

Schlumberger Private
• Open 50%

• Close 0%

 PWM Time based pulses


– Frequency 33 Hz
– Pulse width 10 – 90 %
– Uses:
• Proportional valve
• Engine throttle 10% 30% 50% 70% 90% 25%

 Maximum voltage 100%

– DCU I, II and III pre-revision AM 12 50%

Volt 0%

– DCU III revision AM and later 24 Volt PWM – Frequency 33 Hz

25 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Serial Communication (P9)

DCU I 1
 Serial 1: (RS232)
 Serial 2: (RS232) RS232

Schlumberger Private
DCU II & III
1
 Serial 1: (RS232)
 Serial 2: (RS232 or RS485) RS232
JP42
LOAD

JP41

JP44
JP43

JP40
Note: Serial1 is connected to Micro Processor serial I/O communication port

26 JHB
Revision: 1 21-Dec-2007
DCU Serial Communication
Signal Level RS-232

RS232 – Standard
 Defines the voltage levels, referenced to a common
ground, that correspond to logical one and logical
zero.

Schlumberger Private
+15V Space

– Logical one (Mark) = - Voltage (Off) Start


LSB
1 1 0 0 1 0 1
MSB
0 Stop

– Logical zero (Space) = + Voltage (On)


Function: On
– Open circuit max: 25Volt
+3V

– Common signal levels: ±5V, ±10V, ±12V, and ±15V Gnd Start b0 b1 b2 b3 b4 b5 b6 b7 Stop
– Invalid signal level range from +3 to -3V -3V

– DCU uses ±12V Function: Off

 Network - Point-to-Point serial communication


Idle Idle
– Serial 1: -15V
Time
Mark

• DCU to Application LSB: Least Significant Bit Signal levels RS232 Serial Communication
MSB: Most Significant Bit
• DCU to Upstream (Daisy-chained) DCU
• CPU to Application (J1 installed)
– Serial 2:
• DCU to Downstream (Daisy-chained) DCU
• DCU to Application (Troubleshooting using DCU Shell)

27 JHB
Revision: 1 21-Dec-2007
DCU Serial Communication
Signal Level RS-485

RS485 – Standard

Space

Space
 Specifies a differential form of signalling. The dif-

Mark
ference between wires U- and U+ indicates a logic Mark Space Mark
U+ Mark Mark
1 level, the reverse polarity indicates logic 0.

Schlumberger Private
U- Idle Idle
– Logical one (Marking, OFF) = U+ > U- 1 1 0 0 1 0 1 1

Stop
Start
– Logical zero (Spacing, ON) = U+ < U-
– Minimum V: 0.2 Volt T
– V referred to common ground between +12 and -7
Volt.
– Common V signal levels: 5V
– 35 Mbit/s up to 10 mtr
– 100 kbit/s up to 1200 mtr
 Network topology
– Point to Point
– Bus

28 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Serial Communication connector (P9) pin assignment

DCU I, II and III


Input / Output Serial 1 Serial 2
T(x) 1 6

Schlumberger Private
R(x) 3 8

1
T(x)1 Gnd
Gnd 2 7 Shutdown
R(x)1

Shutdown 4 9 Gnd T(x)2 \ Comm A


Gnd R(x)2 / Comm B
Comm A* 6 Shutdown Gnd

Comm B* 8
Gnd 5 10

* DCU II and III:


Serial 2 configured for RS485 communication.

29 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Serial Communication (P9) Jumpers

Serial 2: DCU II and III 5V

Signal RS232 RS485


RS485

1.5k
Pull Up Resistor

Tx JP43 (Bottom) JP40

Schlumberger Private
R(x)2 R(x)2
Rx JP44 (Bottom) JP43 JP44
RS485

120
T(x)2 A
Load Resistor

Comm: A JP43 (Top) T(x)2 B

Comm: B JP44 (Top) JP41


JP42

RS485 T(x)2
Pull up JP40

1.5k
Pull Down Resistor

Pull Down JP41


Load JP42

RS232
JP42
LOAD
JP41
JP43
JP44
JP40

30 JHB
Revision: 1 21-Dec-2007
DCU Hardware
CAN Network Communication (P1/P6)

DCU I
 CAN 1: (P1) Connection to CAN-Bus
CANL CANH GND
P1

Schlumberger Private
DCU II & III 1

 CAN 1: (P1) Connection to CAN-Bus CAN 1


 CAN 2: (P6) Connection to secondary CAN-Bus JP51
DCU III Only

DCU III
CANL CANH GND
 CAN-Bus termination resistor (120 Ohm) selectable via jumper: P6
– CAN 1: JP51
– CAN 2: JP52 1

CAN 2
JP52
DCU III Only

31 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Signal level CAN

CAN – Standard
 Specifies a differential form of signalling. The difference between wires
CAN-HI and CAN-LO indicates a logic 1 level or logic 0.

Schlumberger Private
– CAN-HI: 2.75 to 4.50 Volt
– CAN-LO: 2.25 to 0.50 Volt
– V: 0.5 to 4.0 Volt
– 125 kbit/s up to 1600 ft (500 m) CAN-HI
0.5V 4.0V
CAN-HI

 Network topology
– Bus
CAN differential signals

32 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Power (P8)

DCU I, II & III


 12VDC regulated
– Supplies 12VDC Sensor Power via Input connectors
– Supplies power to most DCU components via an on-board

Schlumberger Private
12V GND 24V GND
12VDC to 5VDC step down chip

P8
 24VDC regulated DC/DC INPUT

– Supplies 24VDC Sensor Power via Input connectors


– Supplies power to the analog output related components

33 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Power distribution (P7, P11)

DCU I, II & III (Pre-Rev AM)


P11 P7

+ OUT -
V(out)

 12VDC Un-regulated/Dirty

POWER
{

+ IN -
– Protected by: 1,500V transient zener diodes (D8,D9) that

Schlumberger Private
V(in)

break-down at 19VDC. (1.5KE20A)

1
– Input 12VDC distribution.
– Supplies 12VDC Unregulated/Dirty power to digital
outputs.

P11-2 P11-4
P7-1 P7-3
+V UNREG to Digital outputs
D8 D9
EGND
P7-2 P7-4

0.1F 1M

34 JHB
Revision: 1 21-Dec-2007
DCU Hardware
Power distribution (P7, P11)

DCU III (Revision AM or later) P11 P7

+ OUT -
V(out)

POWER
 12-24VDC Un-regulated/Dirty {

+ IN -
V(in)

– Protected by 1,500V transient zener diodes (D8,D9) that

Schlumberger Private
1

1
break-down at 25.7VDC. (1.5KE27A)
– Input 12-24VDC for distribution
– 12 or 24VDC Unregulated/Dirty power to digital outputs.

P11-2 P11-4
P7-1 P7-3
+V UNREG to Digital outputs
D8 D9
EGND
P7-2 P7-4

0.1F 1M

35 JHB
Revision: 1 21-Dec-2007
DCU
Control Jumpers

Control Jumpers
 JP1
– JP1 is the BootStrap Jumper, when installed the MicroProccessor expects
the startup commands from the serial communication port. This jumper
is used to load firmware into memory.
 Unit Type JP2 (RDA S), JP3 (RDA R), JP4 (JAB II) and JP5 (DCU)

Schlumberger Private
– Unit type jumpers are used by the firmware to indicate which sub-
routines of the control program needs to be executed. (See firmware for
function)
 Memory selection (JP36 and JP37)
– Memory selector jumpers are used to select Memory (JP36 Flash, JP37
RAM)
 JP34 DOUBLER (DCU I only)
– JP34 is used on the DCU I in combination with the unit type jumpers.
(See firmware for function)

36 JHB
Revision: 1 21-Dec-2007
DCU
Status BAR

The status BAR LEDs are controlled by the firmware.


 Process status:
– SER 1 (LED0 and LED1)
• LED0 (SER 1 TX) indicates transmission of data on Serial port 1
• LED1 (SER 1 RX) indicates reception of data on Serial port 1
– SER 2 (LED2 and LED3)

Schlumberger Private
• LED2 (SER 2 TX) indicates transmission of data on Serial port 2
• LED3 (SER 2 RX) indicates reception of data on Serial port 2
– CAN 1 (LED4 and LED5)
• LED4 (CAN 1 TX) indicates transmission of data on CAN port 1
• LED5 (CAN 1 RX) indicates reception of data on CAN port 1
– SER 2 (LED6 and LED7)
• LED6 (UNIT STS1) / Hart beat 1/second, indicates firmware routine executing.
• LED7 (UNIT STS2) Not used.
– CAN 2 (LED8 and LED9), DCU II & DCU III
• LED8 (CAN 2 TX) indicates transmission of data on CAN port 2
• LED9 (CAN 2 RX) indicates reception of data on CAN port 2

37 JHB
Revision: 1 21-Dec-2007
DCU
Status BAR

The status BAR LEDs are controlled by the firmware.


 Error status:
– Sequential LED0, LED1,…, LED9 indicates firmware incorrectly
configured.

Schlumberger Private
38 JHB
Revision: 1 21-Dec-2007
DCU
Filter board (DCU I)

Filter board

 DCU filter board


– Mounted below DCU-I

Schlumberger Private
 Function
– Provides analog input filtering for DCU-I
– Analog input signals conditioning
– Configuration jumpers to select Voltage
or Current sensors.

39 JHB
Revision: 1 21-Dec-2007
DCU
Support boards (I-O)

DCU I-O
 CSD362
– 16 Digital outputs to control additional
valves, solenoids etc…

Schlumberger Private
 CSD362-B
– 16 Digital outputs to control additional
valves, solenoids etc…
– 16 Digital inputs to provide feedback for
valves.

40 JHB
Revision: 1 21-Dec-2007
DCU
EtherNET CAN GateWay

Ethernet CAN GateWay (ECGW)


 Configuration
– Master
– Slave

Schlumberger Private
 Function
CAN to EtherNET converter

41 JHB
Revision: 1 21-Dec-2007
DCU
Break-out board

Break-out board

 DCU Break-out board


– Installed on top of a DCU

Schlumberger Private
– 110 Screw terminals for Input and
Outputs
– 5, 12 and 24Volt power for DCU and
sensors
– Signals conditioning
– Diagnostic leds
– Configuration jumpers
– Input power 24VDC

42 JHB
Revision: 1 21-Dec-2007
DCU
Programmable Logic Controller

DCU performs the same function as a Programmable


Logic Controller (PLC) would.
 Firmware controls Inputs and Outputs.

Schlumberger Private
 One board performs most functions
 Consistent foot print and I-O connector positions for
different generations DCU’s
 Better control of firmware

43 JHB
Revision: 1 21-Dec-2007
DCU Firmware
Download/Configuration Hardware

DCU I
 Not supported

Schlumberger Private
DCU II & III
 Required:
– Computer
– CAN adapter (Softing)
– Serial cable (DB9 – 10-pin AMP)
– CAN network cable (DB9F – 4-pin Phoenix)
– CAN Terminator (2 * 120 Ohm)
– DCUWizard (InTouch)
– Firmware (InTouch)

44 JHB
Revision: 1 21-Dec-2007
DCU Firmware
Communication Hardware

CAN communication
 Computer
– Win2000, WinXP
– Serial port

Schlumberger Private
 CAN adapter
– Softing adapters
• CANusb
• CANcard2
• CANpci
• CAN104
 CAN adapter drivers
– CAN Layer 2 V4.11 drivers

45 JHB
Revision: 1 21-Dec-2007
DCU Firmware
Communication Cables Serial

DCU Communication Cables


 Serial cable (DB9 – 10-pin AMPMODU Mod IV)
 Serial cable (DB-9F – 7-pin Jupiter (WS-Standard))

Schlumberger Private
Serial DB- AMPMOD Jupiter
Cable 9F U Mod IV

Tx 2 3 3

Rx 3 1 1

Gnd 5 2 2

46 JHB
Revision: 1 21-Dec-2007
DCU Firmware
Communication Cables CAN

CAN Communication Cables


 CAN network cable (DB9 – 4-pin Phoenix)
 Terminator

Schlumberger Private
CAN DB-9F Phoeni Jupiter
x
CAN-HI 7 2 3
CAN-LO 2 3 1
GND 3/6 1 2
POWER 4
Function DB-9M DB- Function DB-9M DB-
9F 9F
Reserved 1 1 GND 6 6
CAN-LO 2 2 CAN-HI 7 7
GND 3 3 Reserved 8 8
Reserved 4 4 CAN-V+ 9 9

47 JHB Shield 5 5 120Ohm 2 7


Revision: 1 21-Dec-2007
DCU Firmware
DCU I

Required:
 DCUWizard (InTouch)
 HMI (Human Machine Interface)
 CAN Adapter
 Serial and CAN Communication Cable and Terminator

Schlumberger Private
Acquisition (Schlumberger RDA Protocol):
 Firmware: JAB 3.x
 Jumper JP34 (DOUBLER) and.
– DCU Type: RDA-S (JP2), Acquires data from: 4 Frequency + 8 Analog inputs
– DCU Type: RDA-R (JP3), Acquires data from: 8 Frequency + 4 Analog inputs
– DCU Type: JAB II (JP4), Acquires data from: 8 Frequency + 4 Analog inputs
and Simulates a SIM for CTSI via CAN.

Control:
 Firmware: DCU 5.3
 Jumper: JP5 (DCU)
 Configuration via DCUWizard or HMI as per maintenance
manual

48 JHB
Revision: 1 21-Dec-2007
DCU Firmware
DCU II & DCU III

Firmware download:
Required:
– DCUWizard CAN Adapter
– Serial and CAN Communication Cable and Terminator

Schlumberger Private
– Jumper (JP1 for serial download)
Acquisition Firmware:
– DCU2_CMTxxx / DCU3_CMTxxx (Cementing Blending/Pumping Equipment)
– DCU2_FRCxxx / DCU3_FRCxxx (Stimulation Blending Equipment)
Control Firmware:
– DCU2_CMTxxx / DCU3_CMTxxx (Cementing Blending/Pumping Equipment)
– DCU2_FRCxxx / DCU3_FRCxxx (Stimulation Blending Equipment)
– FPC (Fracturing Pumping Units)
– Shutdown
– X11 (Coiled Tubing Unit)
– ??? (Wireline)

49 JHB
Revision: 1 21-Dec-2007
DCU Firmware
DCU II & III Acquisition

Supported Protocol:
– Schlumberger RDA Protocol (12-bit) via RS232
– Schlumberger Extended RDA Protocol (16-bit) via RS232
– CTSI CAN protocol (SDS)

Schlumberger Private
Required:
– XxxCAT (FracCAT, CATMonitor)
– Serial Communication cable.
– Firmware:
• DCU II
– DCU2FRCxxx (preferred)
– DCU2CMTxxx
• DCU III
– DCU3FRCxxx (preferred)
– DCU3CMTxxx

Configuration:
– Jumper:
• JP2 (RDA-S): 12-bit / 16-Bit - 6 Frequency + 6 Analog
• JP3 (RDA-R): 12-bit - 8 Frequency + 4 Analog
• JP4 (JAB II): 12-bit – 4 Frequency + 8 Analog and CTSI via CAN

50 JHB
Revision: 1 21-Dec-2007
DCU Firmware
DCU II & III Stimulation Blending Equipment

Supported Protocol:
– CAN protocol (SDS)
Required:
– DCU Wizard
– HMI for Stimulation Blending Equipment (POD, PCM, LTM)

Schlumberger Private
– CAN Adapter (CANusb, CANcard2,CANpci, CAN104)
– CAN Communication cable.
– Firmware:
• DCU II
– DCU2FRCxxx
• DCU III
– DCU3FRCxxx

Configuration:
– Jumper:
• JP5 (DCU)
– Firmware (As per Equipment manual):
• Address
• Attribute
• Serial Number

51 JHB
Revision: 1 21-Dec-2007
DCU Firmware
DCU II & III Cement Blending Equipment

Supported Protocol:
– CAN protocol (SDS)
Required:
– DCU Wizard
– HMI for Cement Blending Equipment (Truck, TruckLite, Skid, SkidLite)

Schlumberger Private
– CAN Adapter (CANusb, CANcard2,CANpci, CAN104)
– CAN Communication cable.
– Firmware:
• DCU II
– DCU2CMTxxx
• DCU III
– DCU3CMTxxx

Configuration:
– Jumper:
• JP5 (DCU)
– Firmware (As per Equipment manual):
• Address
• Attribute
• Serial Number

52 JHB
Revision: 1 21-Dec-2007
DCU Firmware
DCU III Fracturing Pumping Units

Supported Protocol:
– CAN protocol (SDS)
– J1939 Protocol over CAN. (ECM communication)
Required:
– DCU Wizard

Schlumberger Private
– HMI for Fracturing Pumping Units (FPC)
– CAN Adapter (CANusb, CANcard2,CANpci,
CAN104)
– CAN Communication cable.
– Firmware:
• DCU III
– DCU3_Fpc364R_xxx

Configuration:
– Jumper:
• JP5 (FPC Master DCU)
• JP4 (FPC Slave DCU)
– Firmware (As per Equipment manual):
• Address
• Attribute
• Serial Number Configuration / Download

53 JHB
Revision: 1 21-Dec-2007
DCU Firmware
DCU III Coiled Tubing Units

Supported Protocol:
– CAN protocol (SDS)
Required:
– HMI for X-11 Units (OpsCAB)
– CAN Adapter (CANusb, CANcard2,CANpci, CAN104)

Schlumberger Private
– CAN Communication cable.
– Firmware:
• X11
– DCU3_X11x_xxxx

Configuration:
– Jumper:
• JP2 (X-11 BOP)
• JP3 (X-11 Injector)
• JP4 (X-11 HPU)
• JP5 (X-Reel)
• JP1, JP2, JP3, JP4, JP5 (X-11 Control panel)

54 JHB
Revision: 1 21-Dec-2007
DCU
DCU Standard enclosures

DCU enclosures:
– ROSE Part#: 02162609.00
– Dimension: 10.24 x 6.30 x 3.58” (260 x 160 x 91mm)
– Equipped with:

Schlumberger Private
• DCU Board with Power supply (SLB Part#: 564735000)
• 12 / 24 VDC LED indicators
• Jupiter connectors and/or cable glands depending on
model.
– Enclosure models:
• DCU STANDARD BOX (564732000)
• DCU SENSOR BOX (568273000)
• DCU RATE BOX (570257000)
• DCU 4 x 4 Box (570341000)
• DCU Express (570342000)
• DCU Shutdown

55 JHB
Revision: 1 21-Dec-2007
DCU
DCU Standard Enclosure Power Supply

DCU Board with Power supply: 10 9 8 7 6 5 4 3 2 1

 Hardware:
– DCU I, II or III
– CD/DC Converter 12 to 24V with

Schlumberger Private
conditioning board (50Watt)
12 TO 12 VOLT
– CD/DC Converter 12 to 12V with CONVERTER

conditioning board (50Watt) CIRCUIT BREAKER


7.5 AMP
12 TO 24 VOLT
– Circuit Breaker (7.5A) CONVERTER

56 JHB
Revision: 1 21-Dec-2007
DCU
DCU Standard Enclosure Power Supply Wiring

RED/WHT +12 IN WHT +24 IN

RED "LINE"

RED "LOAD"
GRN GND GRN GND

Schlumberger Private
CIRCUIT BREAKER
BLK POWER OUT - 7.5 AMP BLK POWER OUT -

RED POWER OUT + RED POWER OUT +

12/12 VOLT 12/24 VOLT


CONVERTER CONVERTER

LINE LOAD

GN GN
CANLCANHD CANLCANHD UNIT TYPE
P9 P6 1 P1 P9
JP2 BLK 12/12 -IN
SER TX1
JP3 P11 P7
SER RX1
JP4 SER TX2 BLK 12/24 -IN
PROFIBUS CAN 2 CAN 1 JP5 RS 232

+ OUT-
SER RX2
JP42
JP31 JP27 JP26 JP2-RDA S CAN TX1 LOAD RED 12/12 +IN

POWER
JP36
JP37

JP52 JP51 JP3-RDA R CAN RX1


JP30 JP4-JAB II STS1
STS2 RED 12/24 +IN
JP41
JP43
JP44
JP40

+ IN -
DIGITAL INPUTS

FLASH JP5-DCU
JP33 JP29 JP28 RA CAN TX2
M CAN RX2
JP32 CSD364

P8
DCU SENSOR
GRN 12/24 -OUT

GN
SLB P/N: 100338940-AA
P10

24V D
P3 ADDRESS : N/A WHT 12/24 +OUT

DC/DC INPUT
ATTRIBUTE: N/A
SW VER: FRCXXX GRN 12/12 -OUT

GN
12V D
RED/WHT 12/12 +OUT

ANALOG
OUTPUTS JP1 P5

SER LOADER
OUT4
P12

DIGITAL OUTPUT

+24
OUT3
JP34

JP23

JP22

FREQ1 +12

+24
OUT2

FREQ2
JP 35

JP25

JP24

+12 JP6 JP7 JP10


JP50
FREQ 8
JP39 JP12 JP11 JP15 JP14 JP18 JP19
OUT1

0-700MV JP8 JP9


JP38
JP45

JP46

JP47
JP48

FREQUENCY INPUTS FREQ 7 JP13 JP16 JP17 JP20 JP21


JP49

ANALOG
P4 INPUTS P2
+12V +24V

57 JHB
Revision: 1 21-Dec-2007
DCU
DCU Standard enclosures

 DCU STANDARD BOX (SLB Part#: 564732000)


– ROSE Part#: 02162609.00
– Dimension: 10.24 x 6.30 x 3.58” (260 x 160 x 91mm)
– Equipped with:

Schlumberger Private
• Power
• 7.5 Ampere breaker
• Termination block
• 12 / 24 VDC LED indicators
• DCU I, II or III
• Jupiter connectors and/or cable glands depending on
model.
– Enclosure models:
• DCU STANDARD BOX (564732000)
• DCU SENSOR BOX (568273000)
• DCU RATE BOX (570257000)
• DCU 4 x 4 Box (570341000)
• DCU Express (570342000)
• DCU Shutdown

58 JHB
Revision: 1 21-Dec-2007