Protection Principles and Components
Protection Principles and Components
Protection principles
and components
1
2.1. Protective Zone…
Regions (zones) of power system that can be protected adequately with
fault recognition and removal resulting in disconnection of a minimum
amount of equipment.
Requirements:
All power system elements must be encompassed by at least one zone
Zone of protection must overlap to prevent any system element from
being unprotected
B. For a fault at P1, located in zone 5, breakers B24 and B42 should open.
For a fault at P2, located in the overlap region of zones 4 and 5, breakers B24,
B42, B21, and B23 should open.
2.2 Power System Protection Components
1. Instrumentation transformers(Transducers)
Transform the high value of fault current or voltage into low levels
E.g. CTs and PTs
2. Protective Relay
Process the signal from the transducers and initiates tripping circuit breaker
Electromechanical relays: are the oldest generation of relay and have been in use f
long time
Static relays: represent the second generation of the relays
Microprocessor relays: represent the latest generation of relays, the most advance
generation of relays
3. Circuit Breaker
Responds to the trip signal from relay to interrupt an electric circuit
13
2.2.1. Instrument transformers
Instrument transformers are special types of transformers
intended for measuring of voltages and currents.
The main tasks of instrument transformers are:
To transform currents, or voltages, from a high value to a value
easy to handle for relays and instruments.
To insulate the metering circuit from the primary high voltage.
These are generally classified as:
Current transformers
Potential transformers
14
Current Transformer
used to step down current for metering and protection Purpose
The main parts of a CT are the iron core, the primary and secondary
windings, and the external insulation.
A current transformer basically has a primary coil of one or mor
turns of heavy cross-sectional area.
The secondary of the transformer is made up of a large number o
turns of fine wire having small cross-sectional area.
The primary winding connected in series with the conducto
carrying the current which to be measured or controlled.
The secondary winding is thus isolated from the high voltage an
then can be connected to low-voltage metering circuits.
This is usually rated for 1A or 5A.
15
Current Transformer…
from current point of view, CTs are step down transformers,
stepping down the current value considerably from primary to
secondary
16
Potential Transformer
The basic principle of these transformers is same as CTs
The high alternating voltage are reduced in a fixed proportion for
the measurement purpose with the help of potential transformers.
The construction of these transformers is similar to the normal
transformer. These are extremely accurate ratio step down
transformers.
Its ratio can be specified as:
18
Fig. connections of instrument transformers
Protective Relay
A protective relay is a device which responds to
conditions in an electrical power system, to control a
abnormal
circuit-
breaker so as to isolate the faulty section of the system, with
theit is a smart device that receive inputs, compares them t
setminimum interruption to service.
points, and be:
Inputs can provide outputs .
o current,
o voltage,
20
How Do Relays Detect Faults?
When a fault takes place, the current, voltage, frequency, and othe
electrical variables behave in a peculiar way. For example:
Current suddenly increases
Voltage suddenly decreases
Relays can measure the currents and the voltages and detect tha
there is an overcurrent, or an under-voltage, or a combination of both
Many other detection principles determine the design of protective
relays
22
Protective Relay Operation
Consider a typical relay circuit is shown in the figure below
When a short circuit occurs at point F on the transmission line, the curre
flowing in the line increases to an enormous value.
• This results in a heavy current flow through the
relay coil, causing the relay to operate by closing
its contacts.
• This in turn closes the trip circuit of the breaker,
making the circuit breaker open and isolating the
faulty section from the rest of the system.
• In this way, the relay ensures the safety of the
circuit equipment from damage and normal
working of the healthy portion of the system.
23
Fundamental Requirements of Protective Relaying
The principal function of protective relaying is to cause the prompt
removal from service of any element of the power system.
In order that protective relay system may perform this function
satisfactorily, it should have the following qualities :
1 . Selectivity: It is the ability of the protective system to select correctly that part of the system in
trouble and disconnect the faulty part without disturbing the rest of the system.
2. Speed: The relay system should disconnect the faulty section as fast as possible.
3 Sensitivity: It is the ability of the relay system to operate with low value of actuating quantity.
4. Reliability: It is the ability of the relay system to operate under the pre-determined conditions.
5. Simplicity: The relaying system should be simple so that it can be easily maintained. Reliability
is closely related to simplicity. The simpler the protection scheme, the greater will be its reliability
6. Economy: The most important factor in the choice of a particular protection scheme is the
economic aspect.
24
Important Terms
Pickup current: is the minimum current in the relay coil at which the
relay starts to operate.
Current Setting: It is often desirable to adjust the pick-up current to any
required value. This is known as current setting and is usually achieved by the
use of tappings on the relay operating coil.
PSM 2 4 5 8 10 20
Operating 10.2 5 4.5 3 2.5 2.4
Time (sec)
Overcurrent Relay
Over current protection is that protection in which the relay picks
up when the magnitude of current exceeds the pick-up value (level).
The relay has the time setting and the plug setting.
The time setting decides the operating time of the relay while the
plug setting decides the current required for the relay to pick up.
29
Types of overcurrent Relay
30
Instantaneous over current relay
• The preset value of current in the relay coil
is referred as pick up setting current.
• This relay is referred as instantaneous over
current relay, as ideally, the relay operates as
soon as the current in the coil gets higher
than pick up setting current.
• There is no intentional time delay applied.
• But there is always an inherent time delay
which can not be avoided practically.
31
Definite time over current relay
Modern relays may contain more than one stage of protection each stage
includes each own current and time setting. Figure next slide shows a mult
stage overcurrent relay.
32
Definite time over current relay…
Definite time over current relay is the most applied type of over current.
It is used as :
• Backup protection of distance relay of
transmission line with time delay
• Backup protection to differential relay
of power transformer with time delay
• Main protection to out going feeders
and bus couplers with adjustable time
Tripping Characteristics of Multi-Stage
delay setting. Definite Time Over Current Relay
33
Inverse time over current relay
34
Inverse time over current relay…
35
Inverse time over current relay…
36
Directional Over Current Relay
38
Directional Protection Relay
is used where the selectivity can be achieved by directional relaying.
recognizes the direction in which fault occurs, relative to location of the
relay.
It is set such that, it actuates for fault occurring in one direction only, it
doesn’t act for faults occurring in the other direction.
47
Differential Protection
50
Differential Protection…
Principle of Merz-price Protection (circulating current
differential protection):
fig.: No fault
51
Differential Protection…
Principle of Merz-price Protection (circulating current
differential protection)…
52
Distance Protection
A distance relay has the ability to detect a fault within a pre-set distance
along a transmission line or power cable from its location.
Every power line has a resistance and reactance per kilometer related to
its design and construction so its total impedance will be a function of
its length.
A distance relay therefore looks at current and voltage and compares
these two quantities on the basis of Ohm’s law.
53
Distance Protection…
56
Principles of Arc Extinction
Factors responsible for the maintenance of arc between the contacts are:
Potential difference between the contacts
ionized particles between contacts
57
Methods of Arc Extinction
There are two methods of extinguishing the arc in circuit breakers viz.
1. High resistance method:
is employed only in dc circuit breakers and low-capacity ac CBs
The resistance of the arc may be increased by:
Lengthening the arc-increasing the gap b/n contacts
Cooling the arc: helps in the deionization of the medium between the
contacts
Reducing X-section of the arc: The cross-section of the arc can be
reduced by letting the arc pass through a narrow opening or by having sm
area of contacts
Splitting the arc: The arc may be split by introducing some
conducting plates between the contacts.
58
Methods of Arc Extinction…
2. Low resistance or Current zero method :
is employed for arc extinction in ac circuits only.
In this method, arc resistance is kept low until current is zero where the
arc extinguishes naturally and is prevented from restriking inspite of th
rising voltage across the contacts.
All modern high power ac circuit breakers employ this method for arc
extinction
59
Types of Circuit Breakers
60
Oil Circuit Breaker
Advantages:
Oil has good dielectric strength.
Low cost.
Oil is easily available.
It has wide range of breaking capability.
Disadvantages:
Slower operation , takes about 20 cycles for arc quenching.
It is highly inflammable , so high risk of fire.
High maintenance cost.
62
VACCUM CIRCUIT BREAKER
63
VACCUM CIRCUIT BREAKER…
Advantages:
Free from arc and fire hazards.
Low cost for maintenance & simpler mechanism.
Low arcing time & high contact life.
Silent and less vibrational operation.
Due to vacuum contacts remain free from corrosion.
No byproducts formed.
Disadvantages:
High initial cost due to creation of vacuum.
Surface of contacts are depleted due to metal vapors.
High cost & size required for high voltage breakers.
64
AIR BLAST CIRCUIT BREAKERS
This operates using high velocity
blast of air which quenches the arc.
It consists of blast valve , blast tube
& contacts.
Blast valve contains air at high
pressure.
Blast tube carries the air at high
pressure & opens the moving contact
attached to spring.
There is no carbonization of surface
as in VCB.
Air should be kept clean & dry to
operate it properly.
65
AIR CIRCUIT BREAKER…
Advantages:
High speed operation as compared to OCB.
Ability to withstand frequent switching.
Facility for high speed reclosure.
Less maintenance as compared to OCB.
Disadvantages:
Little moisture content prolongs arcing time.
Pressure should be checked frequently for frequent operation.
Risk of fire hazards due to over voltages.
It can’t be used for high voltage operation due to prolonged arc
quenching.
66
SF6 CIRCUIT BREAKERS
68
SF6 CIRCUIT BREAKERS…
Advantages:
Very short arcing period due to superior arc quenching property
of SF6 .
Can interrupt much larger currents as compared to other breakers.
No risk of fire.
Low maintenance, light foundation.
No over voltage problem.
There are no carbon deposits.
Disadvantages:
SF6 breakers are costly due to high cost of SF6.
SF6 gas has to be reconditioned after every operation of the breaker,
additional equipment is required for this purpose.
69
Selection of Circuit Breaker
70
Circuit Breaker Ratings
71
72