Opeartion & Maintenance of SS Equipments CT PT CVT LA ISO 29.6.2020
Opeartion & Maintenance of SS Equipments CT PT CVT LA ISO 29.6.2020
Opeartion & Maintenance of SS Equipments CT PT CVT LA ISO 29.6.2020
1
Overview
2
Importance of maintenance of S/S equipments
Sub-Stations are the most vital part in Electrical
Transmission system.
Grid operation & power transmission can be reliable only if
sub-stations perform well.
3
Importance of maintenance of S/S equipments
If proper and timely care is taken of equipments in service,
the disturbances in supply will be minimum taken of
equipments in service, the disturbances in supply will be
minimum
4
Switch Yard-Daily and Routine maintenance
Sub-Station
5
Switch Yard – Daily, Routine & Schedule Maint.
TRF
MK CT/ PT
Boxes CVT
Earthing CB
Switch
Cable Yard
LA
Trench
Capacitor Isolator
Yard
Bus Bar
Lighting
6
Operation and Maintenance of CT
It is electromagnetic device.
It is a instrument transformer that transform high
ampere at high voltage level into low ampere at low
voltage level.
Instruments transformers are Eye, Nose and Ears of
Substation.
Function of CT :
8
Operation and Maintenance of CT
Construction:
Primary winding :
Copper Bar , Copper Strip , Copper Rope able to take
Normal as well as Short Circuit Current 1200 Amp CT :
730Sq.mm, 600 Amp. CT 250 Sq.mm for 40KA/ 3sec.
Secondary winding:
1,2,3,4 or 5 core as per requirement 1Amp. Or 5 Amp.
Core :
CRGO ,Nickel Iron for higher accuracy
Insulating medium :
Cast Resin, Paper / Polyester, oil and Paper , SF6 Gas
9
Operation and Maintenance of CT
10
Operation and Maintenance of CT
11
Operation and Maintenance of CT
12
Operation and Maintenance of CT
13
Operation and Maintenance of CT
14
Operation and Maintenance of CT
15
Operation and Maintenance of CT
Classification:
Types as per Primary winding
1.Wound type CT
2.Bar type CT
3.Ring type CT
Types as per Insulation Used
Resin Cast CT :
1.Indoor Application up to 33KV, Poor resistance to
moisture and heat transfer capability
2.Oil and paper insulated CT with porcelain support
3.SF6 Gas Insulated CT
16
Operation and Maintenance of CT
Types of Core in CT:
Metering core :
1)Smaller Size , Higher Accuracy 1,0.5,0.2,0.2s , lower
Saturation point for Metering purpose
2)P Class Core : Protection Core for O/C & E/F Protection
5p10 ,5p20 LBB Protection
17
Operation and Maintenance of CT
Types as per Secondary rating
1 Amp. :
More No. of Turns , Higher Accuracy , larger size
18
Operation and Maintenance of CT
Types as per Design
66/132/220/400KV Outdoor CT
Live Tank w/o Bellow: N2 Cushioning
Live Tank with bellow: Steel or Rubber bellow
Dead Tank W/O Bellow: N2 Cushioning
Dead tank with bellow: Steel or rubber bellow. Hair pin
Type, Eye Bolt Type 19
HIVOLTRANS
20
Operation and Maintenance of CT
21
CONSTRUCTION OF CT
HIVOLTRANS
22
HIVOLTRANS
PROFILE OF AN INSULATOR
23
HIVOLTRANS
24
HIVOLTRANS
25
SF-6 INSULATED CURRENT
TRANSFORMER
26
Operation and Maintenance of CT
27
Operation and Maintenance of CT
28
DIFFERENCES BETWEEN
HIVOLTRANS
LIVE TANK AND DEAD TANK DESIGNS
30
Operation and Maintenance of CT
IS for CT is 2705 – 1992, and according
32
Operation and Maintenance of CT
33
Operation and Maintenance of CT
According to IS 2705 – 1992, following test of CT carried
out at factory.
1) Primary high voltage test
2) Secondary high voltage test
3) Inter turn insulation test
4) Partial discharge
5) Tan –Delta test
6) Accuracy Test
7) Polarity test
8) ISF test
9)Temperature rise test
34
Operation and Maintenance of CT
CT symbols & Drawing
35
Operation and Maintenance of CT
CHANGE OF CT RATIO
Many times it is required to change ratio of CT, due to rated P2
P1
current of equipment, load etc. procedure for changing CT ratio is as
under.
For example
I S1 IS 2 Idetails
S3 2 S1
of
2 S 2CT
2S 3are3 S1
as under
3S 2 3 S 3for which
4 S1 4 S2 4CT
S3 ratio
5 S1 5Srequired
2 5 S3
to
36
Operation and Maintenance of CT
Change of CT ratio
Many times it is required to change ratio of CT, due to
rated current of equipment, load etc. procedure for
changing CT ratio is asunder.
For example details of CT are as under for which CT
ratio required to be change.
Ratio 150-300/5-5
Core-1, Core-2
Class 0.5, 5p
Burden 10 VA, 10 VA
ISP/ALF <5 ,10
Now at present 100/5 is connected then connection will
be as drawing
Thus connection for CT ratio 150/5 is 1S1-1S2 and 2S1-
2S2 terminals are connected.
To change ratio from 150/5 to 300/5 it is required to
connect wires to 1S1-1S3 & 2S1-2S3 as drawing 37
Operation and Maintenance of CT
CHANGE OF CT RATIO
Many times it is required to change ratio of CT, due to rated
Co re -1 Co re -2
current ofP1equipment, load etc. procedure for changing CT ratio
P2 is as
under.
For example details of CT are as under for which CT ratio required
to I S1 IS 2 IS 3 2 S1 2 S2 2 S3
38
CAPACITANCE GRADING OF THE
HIVOLTRANS
INSULATION
39
Operation and Maintenance of CT
Daily – Routine Checks
Sr. No. Description
1 Check oil level and leakage of oil if any.
3 Check level of bellow
2 Check corona effect.
4 Check clamp connectors
40
Operation and Maintenance of CT
CHANGE OF CT RATIO
Many times it is required to change ratio of CT, due to rated
current of equipment, load etc. procedure for changing CT ratio is as
under.
For example details of CT are as under for which CT ratio required
to
41
Operation and Maintenance of CT
CHANGE OF CT RATIO
Many times it is required to change ratio of CT, due to rated
current of equipment, load etc. procedure for changing CT ratio is as
under.
For example details of CT are as under for which CT ratio required
to
42
Operation and Maintenance of CT
CHANGE OF CT RATIO
Many times it is required to change ratio of CT, due to rated
current of equipment, load etc. procedure for changing CT ratio is as
under.
For example details of CT are as under for which CT ratio required
to
43
Operation and Maintenance of CT
CHANGE OF CT RATIO
Many times it is required to change ratio of CT, due to rated
current of equipment, load etc. procedure for changing CT ratio is as
under.
For example details of CT are as under for which CT ratio required
to
44
Operation and Maintenance of CT
CHANGE
Do’s OF CT RATIO
Many
times use
Always it is required
crane oftoproper
change capacity
ratio of CT,for
due to rated
handling.
current
Kept of
inequipment, load etc. procedure
vertical direction only withfor changing
proper baseCT ratio is as
under.
Proper earthing of Tank
For
example
Check details of CT
leveling are as under for which CT ratio required
structure
to
Check oil level or any leakages regularly
For Idle core high ratio terminal should be shorted
other terminal of used core should be opened
Terminal connector and porcelain should be cleaned
Ensure tightness of primary and secondary terminals
throughout the circuit
45
Operation and Maintenance of CT
CHANGE
Don’ts OF CT RATIO
Many
times
Don’t it isopen
kept required
thetosecondary
change ratiowinding
of CT, due to rated
current
Avoidofearthing
equipment, ofload
staretc. procedure
point forend
at both changing
i.e. inCT
MKratio
boxis and
as
under.
in C&R panel Primary terminal should be free from
Formechanical
example details of CT are as under for which CT ratio required
stress.
to
Don’t allow oil leakages for longer period.
Precautions for CT :
46
Operation and Maintenance of CT
47
Operation and Maintenance of CT
48
Operation and Maintenance of CT
49
Operation and Maintenance of CT
Core R Ph Y Ph B Ph N
Metering D11 D31 D51 D71
50
Operation and Maintenance of PT
Definition: Voltage Transformer (Potential transformer
largely called PT) converts high voltage level into low
voltage level for measurement and protection purpose.
Uses of PT:
PTs are used for measurement of energy and for
protection purpose.
Type of Construction:
1) Electro magnetic Type : - in which primary and
secondary wound on magnetic core like a usual
transformer.
2) Capacitor Potential transformer: - in which primary
voltage is applied to a series capacitor group. The voltage
across one of the capacitor is taken to auxiliary voltage
transformer. The secondary of auxiliary voltage
transformer is taken for measurement or protection.
51
Operation and Maintenance of PT
No of Cores
1) single core
2) Two core
3) Three or more core.
Specification of PT
5.0 Voltmeters
54
Operation and Maintenance of CVT
CAPACITOR VOLTAGE TRANSFORMER (CVT)
C1
V1
C2
Protec tive
Spark gap
56
Operation and Maintenance of CVT
However the burden current becomes relatively larger
and ratio error and also phase error is introduced.
58
Operation and Maintenance of CVT
59
Operation and Maintenance of CVT
Equivalent Capacitance for CVT might be 5500 pF+ 10% -
5%
Burden for
132KV 0.5 Class CVT= 100VA
220KV 0.5 Class CVT= 167 VA
400KV 0.5 Class CVT= 300 VA
61
Operation and Maintenance of CVT
62
Operation and Maintenance of CVT
63
Operation and Maintenance of CVT
64
Operation and Maintenance of CVT
65
Operation and Maintenance of CVT
66
Operation and Maintenance of CVT
Maintenance Check Point:
Measurement of IR Value with 500V Megger.
Measurement of Tan delta and Capacitance.
Measurement of sec. Voltage and compare with Past
Record.
Never Short circuit or earth secondary terminal.
Used proper rated fuses for secondary.
67
Thank You
68