Session 2 Wiring and Setting - LATAM
Session 2 Wiring and Setting - LATAM
Kit
Wiring and Settings
Note : Some infomraiton may be changed due to improve product quality. Please contact LG engineer to get more information
Wiring and dip-switch setting are changed
by control method
Communication Kit
Control Method
LG Control
DDC
. .
LG Central AI / DI / LG Central
TRoom Controller TRoom DO Controller
Room Room Or
Remote Remote Modbus
Controller Controller
Tr Tr
DX DX
AHU Controller AHU Controller
AHU Coil Outdoor Unit AHU Coil Outdoor Unit
Te PAHCMR000 PAHCMR000
Te
LG LG LG LG LG LG
Contact Signal Modbus
Function List Remote Central
(by DDC)
Remote Central
(by DDC)
Remote Central
Controller Controller Controller Controller Controller Controller
Operating On/Off O O O X X O O O
Operation Mode O O O X X O O O
Return Air Temperature O O O X X O O O
Control Discharge Air Temperature X X X X X X X X
Forced Thermal On/Off X X O X X X X X
Capacity Control X X X X X X X X
Emergency Stop X O X X X X X O
Operating On/Off O O O O O O O O
Operation Mode O O X O O O O O
Return Air Temperature O O X O O O O O
Monitor Discharge Air Temperature X X X X X X X X
Defrost status O X O O X O O X
Error Alarm O O O O O O O O
Compressor On/Off O X X O X O O X
Digital Output
DO
Digital Input DI
Terminal block of PAHCMR000
Communication Line
1) MULTI V IDU Communication
2) Single Communication
3) DDC Comm. (Modbus) or
Module Comm. (modbus)
(for discharge air control)
Universal Input
1) Operation On/Off
2) Cool/Heat
3) Forced Th. On/Off
4) Target temperature(0~10V)
Digital Output
mode 1 : Status
1) Operation On/Off
2) Defrost
3) Alarm (Error status)
mode 2 : Fan
4) High
5) Mid
6) Low
REMO (3 lines)
Terminal block of PAHCMR000
Communication Line
1) MULTI V IDU Communication
2) Single Communication
Modbus
3) DDC Comm. (Modbus) or
Module Comm. (modbus)
(for discharge air control)
Universal Input
Contact Mandatory 1) Operation On/Off
2) Cool/Heat
3) Forced Th. On/Off
4) Target temperature(0~10V)
Digital Output
mode 1 : Status
1) Operation On/Off
2) Defrost
Contact Mandatory EEV only 3) Alarm (Error status)
mode 2 : Fan
Optional 4) High
5) Mid
6) Low
REMO (3 lines)
Communication line
Modbus (DDC) Common
DDC SW 1 SW 1
of Comm. module of Comm. module
(3rd party)
28 ℃
26 ℃
24 ℃
22 ℃
20 ℃
18 ℃
14 ℃
12 ℃
1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0
Voltage
UI Setting #2 Contact Signal (DDC)
SW 1 SW 1
of Comm. module of Comm. module
DO3 : Error Status, Short:Error, Open:Normal DO3 : Fan Low, Short:Low, Open:Fan Stop
DO1 : Operation On/Off Stauts, Short:On, Open:Off DO1 : Fan High, Short:Mid, Open:Fan Stop
Supply air
DX Coil
Refrigerant pipe
To ODU
Remote Controller and EEV Kit Mandatory
Ethernet
AC EZ AC EZ AC Smart ACP AC Manager
Touch (CH 2) (CH 1~4)
(CEN A-B)
SW 1
of Comm. module
ODU Communication
Max wiring length (End to End) : 1,000 m
2C x (0.7 ~ 1.5) mm2 IDU Communication (IDU A-B)
Shiled wire
Max wiring length(end to end) : 1,000 m
2C x (1.0 ~ 1.5) mm2
Shiled wire
IDU A
IDU B
Th. On/Off
(DDC_DO)
SIG
GND
12V
Status Defrost Alarm
(DDC_DI)(DDC_DI)(DDC_DI)
Thermistor
(Pipe in)
Thermistor
(Pipe Out)
EEV Kit
NTC 5 kΩ, 5 m
Capacity Setting (only for EEV Kit)
Fan Speed Interlock
- DI of Fan speed control is supported via Dry Contact - DI of Fan speed control is not supported
- DO of Fan speed is Voltage type(220~240V) - DO of Fan speed is Non Voltage type
- Modbus is not supported - Modbus supported Fan Control
Dry Contact
HEX
Low
Med
High(L)
High(L)
Hig
Med(L)
Low(L)
Med(L)
Low(L)
h
N
N
R/C High(DO1)
1 2 3
R/C
Med(DO2)
Low(DO3)
If the Fan motor is On/Off type, fan signal can be interfaced with operation status signal at DO 1
SW 1
of Comm. module
Note that the fan is kept ON,
during Thermo Off
Communication Status LED
<Communication Module>
LD05L LED5 ODU Comm. (Repeat On/Off when communicating with ODU)
1st
1st
Case Study
Case Study
Expansion
EEV kit
Device
Remote controller O
ACP O
DDC Control X
Retrun air
Supply air
DX Coil
MULTI V
Case Study – Wiring / Setting _ 강사 Only
ACP R/C
CH1~4
NTC 10K Thermistor
CH2 Retrun air
Supply air
DX Coil
CEN A/B
IDU A/B
Pipe In T.
Pipe Out T.
MULTI V
Dip S/W 1-2 On
Dip S/W 4 All On
Case Study
Case Study
Expansion
TXV kit
Device
Remote controller O
ACP O
Retrun air
DO, AO of DDC
Supply air
DX Coil
DI, AI of DDC
MULTI V
Case Study – Wiring / Setting_ 강사 Only No need to set capa
Dip S/W 1-2 Off.
ACP R/C Dip S/W 1-3 Off
Dip S/W 2-3 Off
Dip S/W 2-4 Off
DO, AO of DDC
Supply air
From AO/DO of DDC
DX Coil
On / Off
CH2
CEN A/B
MULTI V
Pipe Out T.
Pipe In T.
Defrost
Alarm
Status
DDC
LG Central
.
AI / DI / LG Central
Controller DO
TRoom Controller
Room (Optional) Room Or
Remote Remote Modbus
Controller Controller
Td Td
DX DX
AHU Controller AHU Controller
AHU Coil Outdoor Unit AHU Coil T1) Outdoor Unit
PAHCMS000 PAHCMS000
Te Te
LG LG LG LG LG LG
Contact Signal Modbus
Function List Remote Central
(by DDC)
Remote Central
(by DDC)
Remote Central
Controller Controller Controller Controller Controller Controller
Operating On/Off O O O X X O O O
Operation Mode O O O X X O O O
Return Air Temperature X X X X X X X X
Control Discharge Air Temperature O O X X X O O O
Forced Thermal On/Off X X X X X X X X
Capacity Control X X O X X O X X
Emergency Stop X O O X X X X O
Operating On/Off O O O O O O O O
Operation Mode O O X O O O O O
Return Air Temperature X X X X O O X O
Monitor Discharge Air Temperature X O X X O O X O
Defrost status O X O O X O O X
Error Alarm O O O O O O O O
Compressor On/Off O X O O X O O X
NOTE
LG Controllers can not control comm kit through
1) Temperature sensor of AHU Controller can be installed at discharge or return air side to
‘Contact Signal’ control by DDC
monitor temperature status.
Main Module
Terminal Block
88 Segment
Communication Line
1) ODU Central Control (Capacity Control)
2) LG Central Control Communication
3) DDC Comm. (Modbus)
Universal Input
1) Capacity Control 0~10V
2) Cool/Heat
3) Emergency Stop
Communication Line
1) ODU Central Control (Capacity Control)
2) LG Central Control Communication
Modbus 3) DDC Comm. (Modbus)
Universal Input
1) Capacity Control 0~10V
Contact Mandatory Mandatory 2) Cool/Heat
3) Emergency Stop
Common
(Cen A-B)
SW 1
ODU Communication of Comm. module
Max wiring length (End to End) : 1,000 m
2C x (0.7 ~ 1.5) mm2
Shiled wire (IDU A-B) IDU Communication
UI7 : Outdoor unit capacity control 40% ~ 100% (DC 0 ~ 10V, 20 mA)
ODU capacity control option #1 (SW2-1 of Main Module is off)
ODU capacity control option #2 (SW2-1 of Main Module is on)
EEV Kit
Air Themistors Mandatory
Discharge Air
Thermistor (5m) x 1
NTC 10 kΩ
Supply air
DX Coil
Refrigerant pipe
Pipe in (Liquid)
EEV Kit TXV Kit
thermistor
To ODU
Digital Output Contact Signal (DDC) Optional
IDU A
IDU B
Emer.Stop
(DDC_DO)
DDC
BUS A/B Cool/Heat
Fan_Low Fan_Mid Fan_High Capacity Control
(CH5) BUS A/B (DDC_DO)
(DDC_DO)(DDC_DO)(DDC_DO) (DDC_AO)
Off/On
(DDC_DO)
SIG
GND
12V
Alarm Status Defrost Comp. Status Fan_High Fan_Mid Fan_Low
(DDC_DI) (DDC_DI)(DDC_DI) (DDC_DI) (DDC_DI)(DDC_DI)(DDC_DI)
Thermistor
(Pipe in)
Thermistor
(Pipe Out)
EEV Kit
Dip SW Setting
NOTE
1) Function of defrost operation type can be applied only to Multi V outdoor units(after Multi V 5 model).
S/W name No Item Setting Note
On Communication Controlled by DDC through Modbus or LG centralized controller
1 Control Type Controlled by DDC through Contact signal AI and DI
Off Contact signal
LG Centralized controller can only monitor status
Discharge temp. control by LG controller using own discharge temp.
On Stand alone
Discharge Temp. sensor
2
Control Type Discharge temp. control by DDC using filed supplied discharge temp.
Off Manual by DDC
sensor
SW1
In case of multiple outdoor units, Defrost operation can be operated
On Normal
Defrost simultaneously
3 Operation
Type 1) Sequential In case of multiple outdoor units, the outdoor unit is sequentially
Off
Start up started at intervals of 10 minutes
Central On Modbus Modbus Communication (Control/Monitoring)
4 Communication
Type Off LGAP LGAP Communication(Monitoring only)
ODU Capacity
On ODU capacity control #2
ODU Capacity Setting #2
SW2 1
Control ODU Capacity
Off ODU capacity control #1
Setting #1
Emergency stop
On The product stops when emergency stop input is open.
Emergency stop setting #2
SW4 1
setting Emergency stop
Off The product stops when emergency stop input is short.
setting #1
■ Digital Input
■ Digital Input
Value
Value Name Port Function
Name Port Short Open
Short Open
On/Off DI1 On Off Operation On/Off
Fan Low UI4 On Off
Cool/Heat DI2 Heating Cooling Operation Mode
Fan Middle UI5 On Off
Emergency Stop Input
Emer. Stop DI3 Emer. Stop Normal
Fan High UI6 On Off (Priority operation)
■ Digital Output
■ Digital Output
Value
Name Port Function Value
Short Open Name Port Function
Short Open
On/Off DO2 On Off Operation On/Off status Fan High DO1 On Off High Fan Speed
Fan Middle DO2 On Off Middle Fan Speed
Defrost DO3 Defrost Normal ODU Defrost status
Fan Low DO3 On Off Low Fan Speed
Comp.
DO4 On Off Compressor operation On/Off status
Status
41
3. Dip SW Setting
2. Control Type Setting #2
S/W name No Item Setting Note
On Communication Controlled by DDC through Modbus or LG centralized controller
SW1 1 Control Type Controlled by DDC through Contact signal AI and DI
Off Contact signal
LG Centralized controller can only monitor status
SW 1
42
3. Dip SW Setting
3. Discharge Temp. Control Type
S/W name No Item Setting Note
DDC
.
AI / DI / LG Central
TRoom DO Controller
Room Or
Remote Modbus
Controller
Off
Td
DX
AHU Coil T1) On AHU Controller
Outdoor Unit
PAHCMS000
Te
43
3. Dip SW Setting
4. LG Central Controller
S/W name No Item Setting Note
44
3. Dip SW Setting
5. Capacity Control
S/W name No Item Setting Note
ODU Capacity
On ODU capacity control #2
ODU Capacity Setting #2
SW2 1
Control ODU Capacity
SW 2 Off
Setting #1
ODU capacity control #1
■ Universal Input
Name Port Value Function
NOTE
1) ODU Capacity ratios mentioned in the table above are not exact.
2) ‘Evaporative temperature / Condenser temperature’ may vary depending on system operating frequency,
pressure option setting and piping installation conditions.
Capacity Setting (only for EEV Kit)
Fan Speed Interlock
- DI of Fan speed control is supported via Dry Contact - DI of Fan speed control is not supported
- DO of Fan speed is Voltage type(220~240V) - DO of Fan speed is Non Voltage type
- Modbus is not supported - Modbus supported Fan Control
Dry Contact
HEX
High
Low
Med
High(L)
High(L)
Med(L)
Low(L)
Med(L)
Low(L)
N
N
R/C High(DO1)
1 2 3
R/C
Med(DO2)
Low(DO3)
<Main Module>
50
SA system Addressing
■ Main Module Address Setting
◆ Setting Method
- Press ‘Set’ button(red)
- Select ‘Addr’ in 7- Segment using ▲▼ button and then press ‘Set’ button
- Press ‘ESC’ button to exit
The letter 'Pv' is the program version and the number is the program version.
◆ Setting Method
- Press ‘Set’ button(red)
- Press ‘▼’ button
- Program Version check.
- Press ‘ESC’ button to exit
ODU Addressing
Case Study
Case Study
Expansion
EEV kit
Device
Remote controller O
ACP O
DDC Control X
Note Send the Fan operation signal from Comm. Kit to MCC by DO
Case Study – Wiring / Setting
ACP R/C
Retrun air
Supply air
DX Coil
MULTI V
Case Study – Wiring / Setting _ 강사 Only <Main> <Comm.>
Dip S/W 1-2 On Dip S/W 4 All On
ACP R/C Dip S/W 1-4 Off Dip S/W 1-2 On
CH 5 Retrun air
(LGAP)
Supply air
DX Coil
IDU A/B
MULTI V
Pipe Out T.
CEN A/B
Pipe In T.
To MCC
Case Study
Case Study
Expansion
TXV kit
Device
Remote controller O
Retrun air
DO, AO of DDC
Supply air
DX Coil
DI, AI of DDC
MULTI V
Case Study – Wiring / Setting_ 강사 Only <Main> <Comm.>
Dip S/W 1-2 On Dip S/W 1-2 On
ACP R/C Dip S/W 1-4 Off
DO, AO of DDC
CH 5 Retrun air
(LGAP)
Supply air
DI, AI of DDC
DX Coil NTC 10K Thermistor
DI 1 : On/Off
From AO/DO of DDC DI 2 : Mode
DI 3 : Emerg. stop
Middle
High
Low
IDU A/B
MULTI V
Operation
Comp Sta
Pipe Out T.
CEN A/B
Defrost
Pipe In T.
Alarm
Middle
High
Low
To AI/DI of DDC