Session 2 Wiring and Setting - LATAM

The document discusses wiring and dip switch settings for LG communication kits. It shows that control methods can be LG control, contact signal (DDC), or Modbus control (DDC). It provides a wiring diagram and describes the terminal block connections and functions for the return air communication kit (PAHCMR000). These include communication lines, universal inputs, digital outputs, air temperature sensors, and connections for the EEV kit and remote controller. The dip switches are used to set the control method.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
215 views58 pages

Session 2 Wiring and Setting - LATAM

The document discusses wiring and dip switch settings for LG communication kits. It shows that control methods can be LG control, contact signal (DDC), or Modbus control (DDC). It provides a wiring diagram and describes the terminal block connections and functions for the return air communication kit (PAHCMR000). These include communication lines, universal inputs, digital outputs, air temperature sensors, and connections for the EEV kit and remote controller. The dip switches are used to set the control method.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 58

New Comm.

Kit
Wiring and Settings

Note : Some infomraiton may be changed due to improve product quality. Please contact LG engineer to get more information
Wiring and dip-switch setting are changed
by control method

Communication Kit

Control Method

LG Control

Contact Signal (DDC)


Communication Kit Communication Kit
Return Air Discharge Air
(PAHCMR000) (PAHCMS000)
Modbus Control (DDC)
PAHCMR000
(Return Air)
Control Method
LG Control Contact Signal (DDC) Modbus (DDC)

DDC

. .
LG Central AI / DI / LG Central
TRoom Controller TRoom DO Controller
Room Room Or
Remote Remote Modbus
Controller Controller

Tr Tr

DX DX
AHU Controller AHU Controller
AHU Coil Outdoor Unit AHU Coil Outdoor Unit
Te PAHCMR000 PAHCMR000
Te

LG LG LG LG LG LG
Contact Signal Modbus
  Function List Remote Central
(by DDC)
Remote Central
(by DDC)
Remote Central
Controller Controller Controller Controller Controller Controller
Operating On/Off O O O X X O O O
Operation Mode O O O X X O O O
Return Air Temperature O O O X X O O O
Control Discharge Air Temperature X X X X X X X X
Forced Thermal On/Off X X O X X X X X
Capacity Control X X X X X X X X
Emergency Stop X O X X X X X O
Operating On/Off O O O O O O O O
Operation Mode O O X O O O O O
Return Air Temperature O O X O O O O O
Monitor Discharge Air Temperature X X X X X X X X
Defrost status O X O O X O O X
Error Alarm O O O O O O O O
Compressor On/Off O X X O X O O X

LG Controllers can not control comm kit through


‘Contact Signal’ control by DDC
Communication Module

Dip Switch Terminal Block


Fan speed output
Outdoor-Indoor communication
Room thermistor
Pipe in/out thermistor
Remote controller connector
EEV connector, etc

PHOTO : Comm. Module


Contact Control

DDC (AHU Controller)

Digital Output
DO

If DDC closes switch, we call it ‘Short’ circuit


 Opertion ON (according to programed logic)

If DDC opens switch ‘Open’, we call it ‘Open’ circuit


 Operation OFF (according to programed logic)

Digital Input DI
Terminal block of PAHCMR000
Communication Line
1) MULTI V IDU Communication
2) Single Communication
3) DDC Comm. (Modbus) or
Module Comm. (modbus)
(for discharge air control)

Universal Input
1) Operation On/Off
2) Cool/Heat
3) Forced Th. On/Off
4) Target temperature(0~10V)

Digital Output
mode 1 : Status
1) Operation On/Off
2) Defrost
3) Alarm (Error status)
mode 2 : Fan
4) High
5) Mid
6) Low

Air Temp. Thermistor


1) Room Thermistor
2) Pipe in Thermistor
3) Pipe out Thermistor
4) Reserved

EEV Kit Comm. (6 lines)

REMO (3 lines)
Terminal block of PAHCMR000
Communication Line
1) MULTI V IDU Communication
2) Single Communication

Modbus
3) DDC Comm. (Modbus) or
Module Comm. (modbus)
(for discharge air control)

Universal Input
Contact Mandatory 1) Operation On/Off
2) Cool/Heat
3) Forced Th. On/Off
4) Target temperature(0~10V)

Digital Output
mode 1 : Status
1) Operation On/Off
2) Defrost
Contact Mandatory EEV only 3) Alarm (Error status)
mode 2 : Fan
Optional 4) High
5) Mid
6) Low

Air Temp. Thermistor


1) Room Thermistor
2) Pipe in Thermistor
3) Pipe out Thermistor
4) Reserved

EEV Kit Comm. (6 lines)

REMO (3 lines)
Communication line
Modbus (DDC) Common

DDC SW 1 SW 1
of Comm. module of Comm. module
(3rd party)

Modbus Communication IDU Communication

Max wiring length : 500 m Max wiring length(end to end) : 1,000 m


2C x (1.0 ~ 1.5) mm2 2C x (1.0 ~ 1.5) mm2
Shiled wire Shiled wire

Note that to control AHU


comm. kit through contact
signal ‘Dip SW 1-2’ should
be ‘off’

<PAHCMR000 Communicatino Module>


UI Setting #1 Contact Signal (DDC)

UI1 : Operation On/Off, Short:On, Open:Off

UI2 : Heating/Cooling, Short:Heating, Open:Cooling


If operation mode (Dip SW 3-2, 3-3) is set to cooling/fan mode
Short:Fan, Open:Cooling
If operation mode (Dip SW 3-2, 3-3) is set to heating/fan mode
Short:Heating, Open:Fan

UI3 : Forced Thermo On/Off, Short:Thermal On, Open:Thermal Off


Note : This function is activated when UI4 input voltate is less than 1.5 V

UI4 : Target temp. setting range 16 ~ 30℃(DC 0 ~ 10V, 20 mA)

Set temp UI4 Target temp. (0~10V)


Under 1.5 V, Comm. Kit is operated
30 ℃ according to UI3 status

28 ℃

26 ℃

24 ℃

22 ℃

20 ℃

18 ℃

<PAHCMR000 Communicatino Module> 16 ℃

14 ℃

12 ℃
1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0
Voltage
UI Setting #2 Contact Signal (DDC)

UI1 : Operation On/Off, Short:On, Open:Off

UI2 & UI 3 : Operation Mode Setting


Cooling : UI2 Short & UI3 Open
Heating : UI2 Open & UI3 Short
Fan : UI2 Open & UI2 Open or UI2 Short & UI3 Short

UI4 : Forced Thermo On/Off, Short:Thermal On, Open:Thermal Off

<PAHCMR000 Communicatino Module>


Digital Output Contact Signal (DDC) Optional

Option1 – Status output Option2 – Fan speed output

SW 1 SW 1
of Comm. module of Comm. module

<PAHCMR000 Communicatino Module> <PAHCMR000 Communicatino Module>

DO3 : Error Status, Short:Error, Open:Normal DO3 : Fan Low, Short:Low, Open:Fan Stop

DO2 : ODU Defrost Status, Short:Defrost, Open:Normal


(only for total defrost) DO2 : Fan Mid, Short:Mid, Open:Fan Stop

DO1 : Operation On/Off Stauts, Short:On, Open:Off DO1 : Fan High, Short:Mid, Open:Fan Stop

DO1~3 electrical specification : 12 VDC / 1 A, 250 VAC / 3 A


Air Themistors Mandatory

Return air thermistor also can be installed the


suction part of DX coil
EEV Kit - Pipe thermistor installation

Pipe in (Liquid) thermistor


Return Air
Thermistor (5m) x 1
NTC 10 kΩ

Pipe out (Gas) thermistor


Retrun air

Supply air

DX Coil

AHU TXV Kit - Pipe thermistor installation

Refrigerant pipe

EEV Kit TXV Kit Pipe in (Liquid)


thermistor
or
Pipe out (Gas)
Pipe In (Liquid) Pipe Out (Gas)
thermistor
Thermistor (5m) x 1 Thermistor (5m) x 1
NTC 5 kΩ NTC 5 kΩ

To ODU
Remote Controller and EEV Kit Mandatory

Premium Standard III Standard II

Max wiring length : 50 m

Max wiring length : 10 m

Note that in case of applying TXV


kit or Single split system, wiring is
not required
TXV Kit
EEV Kit
LG Central Controller Optional

Ethernet
AC EZ AC EZ AC Smart ACP AC Manager
Touch (CH 2) (CH 1~4)

AC Smart BACnet ACP BACNET ACP LONWORKS


(CH 2) (CH 1~4) (CH 1~4)

(CEN A-B)
SW 1
of Comm. module
ODU Communication
Max wiring length (End to End) : 1,000 m
2C x (0.7 ~ 1.5) mm2 IDU Communication (IDU A-B)
Shiled wire
Max wiring length(end to end) : 1,000 m
2C x (1.0 ~ 1.5) mm2
Shiled wire

<PAHCMR000 Communicatino Module>


Dip Switch of PAHCMR000
Wiring Example Multi V
CEN_A Thermistor
(AHU_RA) : NTC 10 kΩ, 5 m
CEN_B
A B DDC
Remote Controller

IDU A
IDU B
Th. On/Off
(DDC_DO)

LG Central controller Off/On Cool/Heat Target Temp.


BUS A/B (DDC_DO) (DDC_DO) (DDC_AO)

SIG
GND
12V
Status Defrost Alarm
(DDC_DI)(DDC_DI)(DDC_DI)

Thermistor
(Pipe in)

Thermistor
(Pipe Out)
EEV Kit

NTC 5 kΩ, 5 m
Capacity Setting (only for EEV Kit)
Fan Speed Interlock
- DI of Fan speed control is supported via Dry Contact - DI of Fan speed control is not supported
- DO of Fan speed is Voltage type(220~240V) - DO of Fan speed is Non Voltage type
- Modbus is not supported - Modbus supported Fan Control
Dry Contact

AHU AHU Modbus


Fan Motor Fan Motor
DDC
DDC
HEX

HEX
Low
Med
High(L)

High(L)
Hig
Med(L)

Low(L)

Med(L)

Low(L)
h
N

N
R/C High(DO1)
1 2 3
R/C
Med(DO2)

Low(DO3)

*DO signal of Fan speed is


available when Dip SW1-3 is ON
Relay (In this case, DO signal of On/Off,
Live Defrost and Error Alarm status is
disable)
If the motor is On/Off type,
Hi/Med/Low wire have to be
connected as common
L N L N
Legend NEW MODEL
PREVIOUS MODEL (PAHCMR000)
Relay
Motor input power (PRCKA1) Motor input power
SW 1
Power source of Comm. module
Field supply Field supply
Fan On/Off Interlock

If the Fan motor is On/Off type, fan signal can be interfaced with operation status signal at DO 1

*In this case, Dip SW1-3 needs to be set as


‘Status’

SW 1
of Comm. module
Note that the fan is kept ON,
during Thermo Off
Communication Status LED

<Communication Module>

Name Port Function

LD01L LED1 Modbus Comm. Tx

LD02L LED2 Modbus Comm. Rx

LD03L LED3 Inner Comm. Tx (Between PCBA)

LD04L LED4 Inner Comm. Rx (Between PCBA)

LD05L LED5 ODU Comm. (Repeat On/Off when communicating with ODU)

LD06L LED6 Error Status (Repeat On/Off when error occurs)

: Comm. Condition between PCBA 1st and 2nd.


2nd
2nd

1st
1st
Case Study

Case Study

Coil Capacity 192 kbtu/h (20 HP)

Expansion
EEV kit
Device

Remote controller O

ACP O

DDC Control X

Note LG controls AHU DX coil.


Case Study – Wiring / Setting
ACP R/C

Retrun air

Supply air

DX Coil

MULTI V
Case Study – Wiring / Setting _ 강사 Only
ACP R/C

CH1~4
NTC 10K Thermistor
CH2 Retrun air

Supply air

DX Coil
CEN A/B

IDU A/B
Pipe In T.
Pipe Out T.
MULTI V
Dip S/W 1-2 On
Dip S/W 4 All On
Case Study

Case Study

Coil Capacity 394 kbtu/h (40 HP)

Expansion
TXV kit
Device

Remote controller O

ACP O

DDC Control O (Contact Signal)

Customer wants to know status of Comm. Kit


Note
Fan is controller by DDC directly
Case Study – Wiring / Setting
ACP R/C

Retrun air

DO, AO of DDC
Supply air

DX Coil

DI, AI of DDC

MULTI V
Case Study – Wiring / Setting_ 강사 Only No need to set capa
Dip S/W 1-2 Off.
ACP R/C Dip S/W 1-3 Off
Dip S/W 2-3 Off
Dip S/W 2-4 Off

CH1~4 Retrun air


NTC 10K Thermistor

DO, AO of DDC
Supply air
From AO/DO of DDC
DX Coil

Set Temp./ Forced Th.


Cool / Heat
DI, AI of DDC

On / Off
CH2
CEN A/B

MULTI V

Pipe Out T.
Pipe In T.
Defrost

Alarm
Status

IDU A/B To AI/DI of DDC


PAHCMS000
(Supply Air)
Control Method
LG Control (No DDC) Contact Signal (DDC) Modbus (DDC)

DDC
LG Central

.
AI / DI / LG Central
Controller DO
TRoom Controller
Room (Optional) Room Or
Remote Remote Modbus
Controller Controller

Td Td
DX DX
AHU Controller AHU Controller
AHU Coil Outdoor Unit AHU Coil T1) Outdoor Unit
PAHCMS000 PAHCMS000
Te Te

LG LG LG LG LG LG
Contact Signal Modbus
  Function List Remote Central
(by DDC)
Remote Central
(by DDC)
Remote Central
Controller Controller Controller Controller Controller Controller
Operating On/Off O O O X X O O O
Operation Mode O O O X X O O O
Return Air Temperature X X X X X X X X
Control Discharge Air Temperature O O X X X O O O
Forced Thermal On/Off X X X X X X X X
Capacity Control X X O X X O X X
Emergency Stop X O O X X X X O
Operating On/Off O O O O O O O O
Operation Mode O O X O O O O O
Return Air Temperature X X X X O O X O
Monitor Discharge Air Temperature X O X X O O X O
Defrost status O X O O X O O X
Error Alarm O O O O O O O O
Compressor On/Off O X O O X O O X
NOTE
LG Controllers can not control comm kit through
1) Temperature sensor of AHU Controller can be installed at discharge or return air side to
‘Contact Signal’ control by DDC
monitor temperature status.
Main Module

Terminal Block
88 Segment

Dip Switch Tact Switch

Communication moduel of PAHCMS000


is just same as PAHCMR000’s Comm.
Module
Terminal port of PAHCMS000

Communication Line
1) ODU Central Control (Capacity Control)
2) LG Central Control Communication
3) DDC Comm. (Modbus)

Universal Input
1) Capacity Control 0~10V
2) Cool/Heat
3) Emergency Stop

Main Module Communication Module Digital Output


1) Operation On/Off
2) Defrost
3) Alarm (Error status)
4) Compressor Status

■ Comm. Module output signal for Fan


1) High
2) Mid
3) Low

with Function of Return Air Controller

▶ Supply Air Controller support various


need and make application.
One Supply Air Controller can control
multiple Return Air Controller.
Terminal port of PAHCMS000
Mandatory

Communication Line
1) ODU Central Control (Capacity Control)
2) LG Central Control Communication
Modbus 3) DDC Comm. (Modbus)

Universal Input
1) Capacity Control 0~10V
Contact Mandatory Mandatory 2) Cool/Heat
3) Emergency Stop

Main Module Communication Module Digital Output


1) Operation On/Off
Optiona 2) Defrost
Optional l
Mandatory 3) Alarm (Error status)
4) Compressor Status

■ Comm. Module output signal for Fan


1) High
2) Mid
3) Low

with Function of Return Air Controller

▶ Supply Air Controller support various


need and make application.
One Supply Air Controller can control
multiple Return Air Controller.
Communication line Mandatory

Common

(Cen A-B)

SW 1
ODU Communication of Comm. module
Max wiring length (End to End) : 1,000 m
2C x (0.7 ~ 1.5) mm2
Shiled wire (IDU A-B) IDU Communication

Max wiring length(end to end) : 1,000 m


Module communication (Factory wired)
2C x (1.0 ~ 1.5) mm2
Shiled wire

<Main Module> <Communication Module>


UI Setting (UI7, DI1 ~ DI3) Contact Signal (DDC)

UI7 : Outdoor unit capacity control 40% ~ 100% (DC 0 ~ 10V, 20 mA)
ODU capacity control option #1 (SW2-1 of Main Module is off)
ODU capacity control option #2 (SW2-1 of Main Module is on)

DI1 : Operation On/Off, Short:On, Open:Off

DI2 : Heating/Cooling, Short:Heating, Open:Cooling


If operation mode (Dip SW 3-2, 3-3 of Comm module) is set to cooling only mode
Short:Fan, Open:Cooling
If operation mode (Dip SW 3-2, 3-3 of Comm module) is set to heating only mode
Short:Heating, Open:Fan

DI3 : Emergency Stop,


If dip switch 4-1 of matin Module is off, Short:Stop, Open: Normal
If dip switch 4-1 of matin Module is On) Short:Normal, Open: Short

<Main Module> <Communication Module>


UI Setting (UI4 ~ UI6) Contact Signal (DDC)

UI4 : Fan Speed Low, Short:On, Open: -

UI5 : Fan Speed Mid, Short:On, Open: -

UI6 : Fan Speed High, Short:On, Open: -

Note : +12V ~ DCOM should be “Short” for UI Control (Non voltage)

<Main Module> <Communication Module>


Remote Controller and EEV Kit Mandatory

Premium Standard III Standard II


(PREMTB001 only)

Max wiring length : 50 m

Max wiring length : 10 m

Note that in case of applying TXV kit or Single split


system, wiring is not required
TXV Kit

EEV Kit
Air Themistors Mandatory

Discharge air thermistor also can be installed the


supply air duct connected to AHU
EEV Kit - Pipe thermistor installation

Pipe in (Liquid) thermistor

Discharge Air
Thermistor (5m) x 1
NTC 10 kΩ

Pipe out (Gas) thermistor


<Communication Module
of PAHCMS000> Retrun air

Supply air

DX Coil

TXV Kit - Pipe thermistor installation


AHU

Refrigerant pipe

Pipe in (Liquid)
EEV Kit TXV Kit
thermistor

or Pipe out (Gas)


Pipe In (Liquid) Pipe Out (Gas) thermistor
Thermistor (5m) x 1 Thermistor (5m) x 1
NTC 5 kΩ NTC 5 kΩ

To ODU
Digital Output Contact Signal (DDC) Optional

<Main Module> <Communication Module>

DO3 : Fan Low, Short:Low / Open:Fan Stop

DO2 : Fan Mid, Short:Mid / Open:Fan Stop

DO1 : Fani High, Short:Mid / Open:Fan Stop


DO1 : Alram (error output)

DO4 : Compressor Status, Short:On, Open:Off

DO3 : ODU Defrost Status, Short:Defrost, Open:Normal


(only for total defrost)

DO2 : Operation On/Off Stauts, Short:On, Open:Off

Main module Communication module


DO1 electrical specification : 30 VDC / 5 A, 250 VAC / 5 A DO1~3 electrical specification : 12 VDC / 1 A, 250 VAC / 3 A
DO2~4 electrical specification : 12 VDC / 1 A, 250 VAC / 3 A
Multi V

Wiring Example CEN_A


Thermistor
(AHU_SA)

LG Central controller CEN_B


(Monitoring Only) Remote Controller

IDU A
IDU B
Emer.Stop
(DDC_DO)
DDC
BUS A/B Cool/Heat
Fan_Low Fan_Mid Fan_High Capacity Control
(CH5) BUS A/B (DDC_DO)
(DDC_DO)(DDC_DO)(DDC_DO) (DDC_AO)

Off/On
(DDC_DO)

SIG
GND
12V
Alarm Status Defrost Comp. Status Fan_High Fan_Mid Fan_Low
(DDC_DI) (DDC_DI)(DDC_DI) (DDC_DI) (DDC_DI)(DDC_DI)(DDC_DI)

Thermistor
(Pipe in)

Thermistor
(Pipe Out)
EEV Kit
Dip SW Setting
NOTE
1) Function of defrost operation type can be applied only to Multi V outdoor units(after Multi V 5 model).
S/W name No Item Setting Note
On Communication Controlled by DDC through Modbus or LG centralized controller
1 Control Type Controlled by DDC through Contact signal AI and DI
Off Contact signal
LG Centralized controller can only monitor status
Discharge temp. control by LG controller using own discharge temp.
On Stand alone
Discharge Temp. sensor
2
Control Type Discharge temp. control by DDC using filed supplied discharge temp.
Off Manual by DDC
sensor
SW1
In case of multiple outdoor units, Defrost operation can be operated
On Normal
Defrost simultaneously
3 Operation
Type 1) Sequential In case of multiple outdoor units, the outdoor unit is sequentially
Off
Start up started at intervals of 10 minutes
Central On Modbus Modbus Communication (Control/Monitoring)
4 Communication
Type Off LGAP LGAP Communication(Monitoring only)

ODU Capacity
On ODU capacity control #2
ODU Capacity Setting #2
SW2 1
Control ODU Capacity
Off ODU capacity control #1
Setting #1
Emergency stop
On The product stops when emergency stop input is open.
Emergency stop setting #2
SW4 1
setting Emergency stop
Off The product stops when emergency stop input is short.
setting #1

S/W name No Item Setting Note

On Single Comm. Using Single Split outdoor unit


1 ODU Type
SW1 Off MULTI V Comm. Using MULTI V outdoor unit
2 Control Type On Communication Controlled by Modbus between modules

Master On Slave mode Not used


1
/Slave Off Master mode Master is default for single AHU Controller installation
SW3 Off/Off Heat Pump Cooling or Heating operation mode is available
Operation mode
2/3 Off/On Heating Only Operation mode is Heating only (Heating / Ventilation)
setting
On/Off Cooling Only Operation mode is Cooling only (Cooling / Ventilation )
Capacity According to ODU Type, you can setup the capacity index of MULTI
SW4 1~4 - -
Setting V or Single Split
3. Dip SW Setting
2. Control Type Setting #1
S/W name No Item Setting Note
On Communication Controlled by DDC through Modbus or LG centralized controller
SW1 1 Control Type Controlled by DDC through Contact signal AI and DI
Off Contact signal
LG Centralized controller can only monitor status
SW 1

■ Digital Input
■ Digital Input
Value
Value Name Port Function
Name Port Short Open
Short Open
On/Off DI1 On Off Operation On/Off
Fan Low UI4 On Off
Cool/Heat DI2 Heating Cooling Operation Mode
Fan Middle UI5 On Off
Emergency Stop Input
Emer. Stop DI3 Emer. Stop Normal
Fan High UI6 On Off (Priority operation)

■ Digital Output
■ Digital Output
Value
Name Port Function Value
Short Open Name Port Function
Short Open
On/Off DO2 On Off Operation On/Off status Fan High DO1 On Off High Fan Speed
Fan Middle DO2 On Off Middle Fan Speed
Defrost DO3 Defrost Normal ODU Defrost status
Fan Low DO3 On Off Low Fan Speed
Comp.
DO4 On Off Compressor operation On/Off status
Status
41
3. Dip SW Setting
2. Control Type Setting #2
S/W name No Item Setting Note
On Communication Controlled by DDC through Modbus or LG centralized controller
SW1 1 Control Type Controlled by DDC through Contact signal AI and DI
Off Contact signal
LG Centralized controller can only monitor status
SW 1

42
3. Dip SW Setting
3. Discharge Temp. Control Type
S/W name No Item Setting Note

Discharge temp. control by LG controller using own discharge temp.


Discharge On Stand alone
sensor
SW1 2 Temp. Control
Type Discharge temp. control by DDC using filed supplied discharge temp.
SW 1 Off Manual by DDC
sensor

DDC

.
AI / DI / LG Central
TRoom DO Controller
Room Or
Remote Modbus
Controller

Off

Td
DX
AHU Coil T1) On AHU Controller
Outdoor Unit
PAHCMS000
Te

ON : LG Controls ODU capacity for discharge

43
3. Dip SW Setting
4. LG Central Controller
S/W name No Item Setting Note

Central On Modbus Comm. Modbus Communication


SW1 4 Communication
Type Off Lgap Comm. LGAP Communication(Monitoring only(ACP_CH5)
SW 1

44
3. Dip SW Setting
5. Capacity Control
S/W name No Item Setting Note

ODU Capacity
On ODU capacity control #2
ODU Capacity Setting #2
SW2 1
Control ODU Capacity
SW 2 Off
Setting #1
ODU capacity control #1

■ Universal Input
Name Port Value Function

ODU Capacity control input(0~10 V)


Capacity UI7 0~10 V
*When Temp. Control Type is ‘Manual by DDC’(SW 1-2 :
Control (AI) Input
Off), below UI7 Table setting is available
45
3. Dip SW Setting
5. Capacity Control

NOTE
1) ODU Capacity ratios mentioned in the table above are not exact.
2) ‘Evaporative temperature / Condenser temperature’ may vary depending on system operating frequency,
pressure option setting and piping installation conditions.
Capacity Setting (only for EEV Kit)
Fan Speed Interlock
- DI of Fan speed control is supported via Dry Contact - DI of Fan speed control is not supported
- DO of Fan speed is Voltage type(220~240V) - DO of Fan speed is Non Voltage type
- Modbus is not supported - Modbus supported Fan Control
Dry Contact

AHU AHU Modbus


Fan Motor Fan Motor
DDC
DDC
HEX

HEX
High

Low
Med
High(L)

High(L)
Med(L)

Low(L)

Med(L)

Low(L)
N

N
R/C High(DO1)
1 2 3
R/C
Med(DO2)

Low(DO3)

*DO signal of Fan speed is


available when Dip SW1-3 is ON
Relay (In this case, DO signal of On/Off,
Live Defrost and Error Alarm status is
disable)
If the motor is On/Off type,
Hi/Med/Low wire have to be
connected as common
L N L N
Legend NEW MODEL
PREVIOUS MODEL (PAHCMR000)
Relay
Motor input power (PRCKA1) Motor input power
SW 1
Power source of Comm. module
Field supply Field supply
Fan On/Off Interlock
Fan operating signal can be interfaced with operation status signal at DO 2 of main module

Note that the fan is kept ON,


during Thermo Off
Communication Status LED

<Main Module>

Name Port Function

L01L LED1 Module Comm. Tx

L02L LED2 Module Comm. Rx

L03L LED3 ODU Comm. Tx

L04L LED4 ODU Comm. Rx

L05L LED5 Central Comm. Tx

L06L LED6 Central Comm. Rx

50
SA system Addressing
■ Main Module Address Setting

Address for main module is needed to when PAHCMS000 is connected LG central


controller. Address of main module can be set within ‘1~247’. In this case, 1. Note
that address of main module should be started from ‘01’
2. ODU address and LG central address of Comm Module should be same

◆ Setting Method
- Press ‘Set’ button(red)
- Select ‘Addr’ in 7- Segment using ▲▼ button and then press ‘Set’ button
- Press ‘ESC’ button to exit

※ Modbus Add. Setting RA


IDU : CC Add. by remote controller (Ex. 00)
Modbus Add : CC add(00) + 1 = 1

■ Program Version Check

The letter 'Pv' is the program version and the number is the program version.

◆ Setting Method
- Press ‘Set’ button(red)
- Press ‘▼’ button
- Program Version check.
- Press ‘ESC’ button to exit
ODU Addressing
Case Study

Case Study

Coil Capacity 192 kbtu/h (20 HP)

Expansion
EEV kit
Device

Remote controller O

ACP O

DDC Control X

Note Send the Fan operation signal from Comm. Kit to MCC by DO
Case Study – Wiring / Setting
ACP R/C

Retrun air

Supply air

DX Coil

MULTI V
Case Study – Wiring / Setting _ 강사 Only <Main> <Comm.>
Dip S/W 1-2 On Dip S/W 4 All On
ACP R/C Dip S/W 1-4 Off Dip S/W 1-2 On

CH 5 Retrun air
(LGAP)

Supply air

DX Coil

NTC 10K Thermistor

IDU A/B

MULTI V

Pipe Out T.
CEN A/B

Pipe In T.
To MCC
Case Study

Case Study

Coil Capacity 394 kbtu/h (40 HP)

Expansion
TXV kit
Device

Remote controller O

ACP O (Monitoring Only)

DDC Control O (Contact Signal)

Customer wants to know status of Comm. Kit


Note
Fan is controlled by Comm. Kit, DO
Case Study – Wiring / Setting / Refrigerant piping
ACP R/C

Retrun air

DO, AO of DDC
Supply air

DX Coil

DI, AI of DDC

MULTI V
Case Study – Wiring / Setting_ 강사 Only <Main> <Comm.>
Dip S/W 1-2 On Dip S/W 1-2 On
ACP R/C Dip S/W 1-4 Off

DO, AO of DDC
CH 5 Retrun air
(LGAP)

Supply air
DI, AI of DDC
DX Coil NTC 10K Thermistor

DI 1 : On/Off
From AO/DO of DDC DI 2 : Mode
DI 3 : Emerg. stop

Middle
High
Low
IDU A/B

MULTI V

Operation

Comp Sta

Pipe Out T.
CEN A/B
Defrost

Pipe In T.
Alarm

Middle
High

Low
To AI/DI of DDC