What is CMC?
In coordinate master control ,it co-ordinates
between Boiler Master and EHG while in service.
the target load is given through either by
Automatic load dispatch(ADS) or set manually
through UNIT MASTER in the event ADS is not
functional. The target load signal is processed for
minimum / maximum load limits which are
manually adjustable, corrected for grid frequency
variation before feeding to Ramp circuit for
generation of Unit load demand. The Unit load
demand is fed to Boiler Master to generate Boiler
demand i.e. Air & Fuel requirement and to Turbine
Control to set Turbine demand i.e. MW.
IMPORTANT TERMS IN CMC
Unit Load
MS set point(manual or Sliding)
Boiler Master(BM) demand
Unit Capability
CMC Fuel demand
CMC Air Flow demand
Minimum & Maximum Load SP
Delta Pressure correction in EHTC
AUTO LOOPS FOR CMC
Increase blocked
Run down
Decrease blocked
Run up
Run back
RUN DOWN/INCREASE BLOCKED
Run down: Run down is switched ON automatically
when the Process error(negative) i.e. Feed water, Air
flow etc. becomes less AND(&) the controller output of
the particular loop(feed water, air flow, furnace pressure
and fuel) goes to maximum position making process
uncontrollable. Under the situation, Unit load demand is
reduced to a value as Permitted by the Process to get
over the blockage.
Increase blocked: In this if any of the condition comes
i.e. if process error (negative) OR the controller output
goes to maximum then Incr. blocked will come and it will
hold the unit load demand till process recovers within
limits.