RCD Introduction
RCD Introduction
DESIGN
PREPARED BY:
ENGR. RAYMOND JAY G. SEVERO
OBJECTIVES
𝑠28 = 𝑠7 + 2.5 𝑠7
𝑠28 - 28 – day compressive strength, Mpa
𝑠7 - 7 – day compressive strength, Mpa
Standard Hooks
• 180 – degree bend plus 4𝑑𝑏 extension but not less than 60 mm
at free end of bar.
• 90 – degree bend plus 12𝑑𝑏 extension at free end of bar
• For stirrups and tie hooks:
a. 16mm diameter bar and smaller, 90 – degree bend plus
6𝑑𝑏 extension at free end of bar.
b. 20mm and 25mm diameter bar, 90 – degree bend, plus
12𝑑𝑏 extension at free end of bar.
c. 25 mm diameter bar and smaller, 135 – degree bend,
plus 6𝑑𝑏 extension at free end of bar.
INTRODUCTION
MINIMUM BEND DIAMETER (SECTION 407.3)
Minimum
CAST-IN-PLACE CONCRETE (NON-PRE-STRESSED) Concrete
Cover
a Concrete cast against and permanently exposed to earth 75 mm
Concrete exposed to earth or weather:
b 20 mm through 36 mm bars 50 mm
16 mm bars, W31 or D31 wire, and smaller 40 mm
Concrete not exposed to weather or in contact with ground
Slabs, Walls, Joists:
32 mm bar and smaller 20 mm
Beams, Columns
c
Primary reinforcement, ties, stirrups, spirals 40 mm
Shells, folded place members:
20 mm bar and larger 20 mm
16 mm bars, W31 or D31 wire, and smaller 12 mm
INTRODUCTION
CONCRETE PROTECTION FOR REINFORCEMENT (SECTION 407.8.1)
PRE-CAST CONCRETE (MANUFACTURED UNDER PLANT CONDITIONS) Minimum Concrete Cover
DEAD LOAD
Loads of constant magnitude that remains in one position. This
consist mainly of the structure and other permanent attachment of
the frame.
INTRODUCTION
LIVE LOAD
Loads that may change in magnitude and position. Live loads that
move under their own power are called moving loads. Other live loads
are those caused by wind, rain, earthquakes, soils, and temperature
change. Wind and Earthquake loads are called lateral load.
𝑾𝒖 = 1.4𝐷𝐿 + 1.7𝐿𝐿
𝑾𝒖 = 0.75 (1.4𝐷𝐿 + 1.7𝐿𝐿 + 1.7𝑊𝐿)
𝑾𝒖 = 0.9𝐷𝐿 + 1.3𝑊
𝑾𝒖 = 1.1𝐷𝐿 + 1.3𝐿𝐿 + 1.1𝐸𝐿
𝑾𝒖 = 0.9𝐷𝐿 + 1.1𝐸𝐿
𝑾𝒖 = 1.4𝐷𝐿 + 1.7𝐿𝐿 + 1.7𝐻𝐿
𝑾𝒖 = 1.75 (1.4𝐷𝐿 + 1.4𝑇 + 1.7𝐿𝐿)
𝑾𝒖 = 1. 4(𝐷𝐿 + 𝑇)
INTRODUCTION
Strength Reduction Factors, ∅ (PHI)
The design strength provided by a concrete member, its
connections to other members, and its cross sections, in term of flexure,
axial load, shear, and torsion shall be taken as the nominal strength
multiplied by a strength reduction factor ∅ having the following values:
Flexure without axial load -------------------------------------------- 0.90
Axial tension, and axial tension with flexure ------------------- 0.90
Axial compression and axial compression with flexure
Spiral Reinforcement ------------------------------------------ 0.75
Tie Reinforcement and other reinforcement --------- 0.70
Shear and Torsion -------------------------------------------------------- 0.85
Bearing on Concrete --------------------------------------------------- 0.70
Post- tensioned anchorage zones --------------------------------- 0.85
view
THANK YOU!!!
QUESTION?
QUIZ NO. 1
IDENTIFY WHAT IS BEING ASKED: QUIZ 1
LIVE LOAD
_________________1. Loads that may change in magnitude and position.
FINE AGGREGATES
_________________2. Aggregates that pass through a No. 4 sieve.
_________________3.
WATER used in mixing concrete. It must be clean and free from injurious
amounts of oils, acids, alkalis, salts organic materials or other substance that may be
deleterious to concrete or reinforcement.
0.75
_________________4. Reduction factor for an axial compression and axial compression
with flexure for spiral reinforcement.
CEMENT
_________________5. it is used as a binder into a concrete mixture.
75mm
_________________6. What is the concrete cover of concrete cast against and
permanently exposed to earth in a pre-stressed concrete.
_________________7.
40mm What is the concrete cover of column and beam primary
reinforcement in a non-pre-stressed concrete.
CONCRETE
_________________8. Is a mixture of water, cement, sand, gravel, crushed rock, or other
aggregates.
_____________________9.
TEMPERATURE/SHRINKAGE reinforcement to minimize cracking and to tie the structure
together to ensure its acting as assumed in the design.
10. Explain why do we need to reinforced concrete?