PPT
PPT
Presented By:
Therefore,
Power-flow Analysis Equations
Power-flow Analysis Equations
For the formulation of the real and reactive power entering a bus, we need to define the
following quantities. Let the voltage at the ith bus be denoted by
Let the power system contains a total number of n buses. The current injected at bus-i is given
as
Power-flow Analysis Equations
•It is to be
noted we shall assume the current entering a bus to be positive and that
leaving the bus to be negative. As a consequence the power and reactive power
entering a bus will also be assumed to be positive. The complex power at bus-i is then
given by,
Power-flow Analysis Equations
Note that,
Therefore, substituting above result in complex power equation we get the real and reactive
power as,
The Load Flow Problem
üIn
a power system each node or bus is associated with 4 quantities, such as
1. Magnitude of voltage V
2. Phage angle of voltage δ
3. Active power P
4. Reactive power Q
üIn
load flow problem two out of these 4 quantities are specified and remaining 2 are required to be
determined through the solution of equation.
Bus Classification
Depending on the quantities
that have been specified, the buses are classified into 3 categories.
Each bus
is categorized into one of the following bus types:
•The power flow equations are non-linear, thus cannot be solved analytically. A
numerical iterative algorithm is required to solve such equations
There are 4 methods of solving the load flow problem.
A) The Gauss Seidel Method
B) The Newton Raphson Method
C) Decoupled Newton Method
D) Fast decoupled method
A standard procedure follows
5.Repeat the above process until the deviations from the solution are minimal.
LOAD FLOW BY GAUSS-SEIDEL METHOD
Step 4. Computation of slack bus power : Computation of all bus voltages in step 3 yields Si*=
(Pi -jQi )
Step 5.Computation of line flows :Power flows on the various lines of the network are computed
.
Algorithm modification when PV buses are also present
At PV buses
P and │V│ are specified and Q and δ are unknowns to be determined .
Therefore the values of Q and δ are to be updated in every GS iteration.
Let 2,3,…..m are PV buses and remaining m+1,…..n are PQ buses
Step1: Qi is calculated for each bus using equation
n
Qi ,inj Im Vi YikVk Im Vi Yi1V1 Yi 2V2 YiiVi YinVn
k 1
equation
Qi ,inj
k
Im Vi k 1
Y V Y V
i1 1 i2 2
k
YiiVi
k 1
YinVn
k 1
Disadvantages
It s convergence much slower and may be sometimes fail to do so.
Example Problem
Q:For a sample system of fig 6.7 ,the impedances are given in table 6.6 .Its Admittance
diagram and corresponding Y-bus matrix is also given. The generators are connected at all
the four buses ,While loads are at buses 2 and 3.Values of real and reactive powers are
listed in table 6.7. All buses other than the slack bus are PQ type. Determine Unknowns at
all buses by using Gauss seidel iteration method(1-iteration)
1/18/19
Fig:6.7
Impedance & Admittance Tables & Line Diagrams for a given
Impedance Table 6.5 Admittance Table 6.6
Problem
1/18/19
Bus Admittance Matrix for a given Power System Network
1 1 P2,inj jQ2,inj 0 0
V2 0 Y21V1 Y23V3 Y24V4
Y22
V 2
1 1 0.5 j 0.2
V2 1.04(2 j 6) (0.666 j 2) (1 j 3)
Y22 1 j 0
1 1 1 j 0.5
V3 1.04(1 j 3) (0.666 j 2)(1.019 j 0.046) (2 j 6)
Y33 1 j 0
1 2.81 j11.627
V3
3 .666 j11
1
V3 1.028 j 0.087
1 1 P4,inj jQ4,inj 1 1
V4 0 Y41V1 Y42V2 Y43V3
Y44
V 4
1/18/19
Let bus 2 be a PV bus now with v2=1.04 pu.Once again assuming a flat
voltage start, find Q2,δ2,V3,V4 at the end of the first GS Iteration. Given
, 0.2≤ Q2 ≤1 pu,
(Note δ20=0; i.e V20=1.04+j0)
Qi , inj
k
Y V Y V Y V
Im Vi k 1
i1 1 i2 2
k
ii i
k 1
YinVn
k 1
ImV Y V Y V Y V
0
1 0 0
Y24V4
0
Q2 ,inj 1 21 1 22 2 23 3